Honeywell UDC3200 Eu/Hr Dn, SP Prog, Strt SEG END SEG, Rampunit, Recycles, Soak DEV Prog END

Page 36

Function

Selections or

Prompt

Range of Setting

Lower Display

Upper Display

EU/HR DN

0 to 9999 in

 

engineering units

 

per hour

 

 

Parameter Definition

RATE DOWN—Rate down value. When making a setpoint change, this is the rate at which the controller will change from the original setpoint down to the new one. The ramping (current) setpoint can be viewed as SPn in the lower display.

Entering a 0 will imply an immediate step change in Setpoint (i.e., no rate applies).

SP PROG

(optional

feature)

DISABLE

ENABLE

STRT SEG

1 to 11

END SEG

2 to 12 even

 

numbers

RAMPUNIT

 

 

TIME

 

EU/MIN

 

EU/HR

 

 

RECYCLES

0 to 99 recycles

 

 

SOAK DEV

0 to 99

 

 

PROG END

LASTSP

 

 

F SAFE

 

 

STATE

DISABLE

 

HOLD

 

 

KEYRESET

DISABLE

 

ToBEGIN

 

RERUN

 

 

HOTSTART

DISABLE

 

ENABLE

 

 

SEG1RAMP or

0-99 hours.0-59

SEG1RATE

minutes

 

Engineering

 

units/minute or

 

Engineering

 

units/hour

 

 

SEG2 SP

Within the Setpoint

 

limits

SETPOINT RAMP/SOAK PROGRAM—Available only with controllers that contain this option.

SP RAMP must be disabled.

DISABLE—Disables setpoint programming.

ENABLE—Enables setpoint programming.

SP Ramp must be disabled for SP Program prompts to appear. If SP Rate is enabled, it does not operate while an SP Program is running

Start Segment Number

End Segment Number, always end in a soak segment (2, 4, ... 12)

RAMPUNIT—Engineering Units for Ramp Segments

TIME in hours: minutes

RATE in Enineering units per minute RATE in Enineering units per hour

Number of Program Recycles

Guaranteed Soak Deviation Value

The number selected will be the PV value (in engineering units) above or below the setpoint outside of which the timer halts.

Program Termination State

Hold at last setpoint in the program

Manual mode/Failsafe output

Program State at Program End

Reset/Rerun SP Program

Hot Start

Segment #1 Ramp Time or

Segment #1 Ramp Rate

Select TIME, EU/MIN, or EU/HR at prompt RAMPUNIT. All ramps will use the same selection.

Segment #2 Soak Setpoint Value

30

UDC3200 Universal Digital Controller Operator Manual

04/08

Image 36
Contents UDC3200 Universal Digital Controller Operator Manual WARRANTY/REMEDY ContactsWorld Wide Web TelephoneSymbol Definitions Symbol DefinitionContents TROUBLESHOOTING/SERVICE Page Operator Interface Function of Displays and KeysFunction of Displays and Keys CE Conformity Europe Keys and FunctionsUDC3200 Universal Digital Controller Operator Manual Page Pre-installation Information Model Number InterpretationControl and Alarm Relay Contact Information Alarm RelaysAlarm Relay Contact Information Control RelaysOverall Dimensions MountingPhysical Considerations Mounting Method Step ActionWiring Wiring Diagrams Permissible Wiring BundlingBundle No Wire Functions Universal Output Functionality and RestrictionsINU Wiring the Controller CalloutDetails Earth Ground Hot AC/DCLine Neutral Voltage L2/N Input #1 RTDInput #2 Input 2 ConnectionsTime Simplex Time DuplexL2/N Power Supply PowerPower Load Relay Load Relay Load10 Open Collector Output Time Duplex with a Dual Relay Board L2/N Relay LoadUDC3200 Universal Digital Controller Operator Manual 04/08 15 RS-422/485 Communications Option Connections 17 Auxiliary Output and Digital Inputs Option Connections Digital Inputs26 + 12 +Configuration Configuration Prompt HierarchyConfiguration Procedure ProcedureConfiguration Procedure IntroductionTuning Set Up Group Configuration is Complete RSET2MIN 02 to RSET2RPM CYC SEC CYC SX3 CYC2 SEC CYC2 SX3 Security LockoutAuto MAN Disable Enable RUN Hold Disable EnableSP SEL SP Ramp Set Up Group Keyreset EU/HR DNSP Prog Strt SEG END SEGSEG2TIME SEG3RATESEG4 SP SEG4TIME SEG5RATE SEG6 SP SEG6TIMEAccutune Set Up Group Fuzzy Disable Enable Accutune TuneAT Error Algorithm Set Up Group ALG ON-OFFTimer ALG PD+MRStart KEY Alarm LOW Disp TI REM Time Period000 to INP ALG1Summer with Ratio and BIAS-The following formula Input High Select with Ratio and BIAS-This selectionInput LOW Select with Ratio and BIAS- This selection Multiplier Divider with Square Root -The followingFCC Math KCalc HI Calc LOALG1 INB ALG1 INCPCT CO ALG1 BiasOutput Set Up Group OUT ALGOUT RNG Rlystate RLY TypeMotor TI CUR OUTLOW VAL High VALInput 1 Set Up Group IN1 TypeXmitter IN1 LOWRatio Bias IN1Burnout None EMISSIV101 to Input 2 Set Up Group IN2 TypeXMITTER2 IN2 High IN2 LOWBias IN2 Burnout Burnout Protection Sensor BreakEMISSIV2 Control Set Up Group PV Source Input ALG1 PID SetsInput Input Algorithm PID Sets 2PV SWPWR Mode RSP SRC None Input ALG1 AutobiasSP Track PWR OUTAction OUT RatePCT/M UP PCT/M DNFailsafe Mode DeadbandFailmode MAN OUTRPM MinutesOptions Group AUX OUTAuxiliary Output Selection No Auxiliary OutputDIG INP1 No Digital Input SelectionsWas not previously started via To RUN DIG 1COMB DIG INP2DIG2COMB Digital Input 2 Selections Digital Input 2 CombinationsCommunications Group Shed SP UnitsCSP Rato CSP BiasAlarms Set Up Group High Alarm LOW AlarmA1S1 EV Beginning of SegmentA1S2 EV A2S1TYPEA2S1 EV A2S2TYPEALARM12 DiagnostDisplay Set Up Group Page Entering a Security Code Operator InterfaceProcedure to Enter a Security Code Key errorIndividual key lockout Monitoring Your Controller 4.4.1 Annunciators AnnunciatorsALM 1 OUT 1 DI 1 Or MAN None, F or C Viewing the operating parameters Lower Display Key Parameter PromptsDiagnostic Messages Diagnostic MessagesDescription Functional Overview Block Diagram of the UDC3200 Controller Configuration check Tuning indicatorsAccutune Procedure for Starting Tune Tune for Simplex OutputsOperation Step Operation Press ResultConfiguration Check for Duplex Tune for Duplex Heat/CoolUsing Automatic Tune at start-up for Duplex Heat/Cool Using Blended Tune at start-up for Duplex Heat/Cool Using Manual Tune at start-up for Duplex Heat/CoolStep Operation Press Result Error Codes 10 Procedure for Accessing Accutune Error Codes11 Accutune Error Codes Aborting AccutuneConfiguration Fuzzy Overshoot SuppressionHow it works Background Tests Background TestsEE Fail INP1 RNGRV Limit SegerrCAL MTR CurfailController Failure Symptoms Other symptomsSales and Service Page Http//hpsweb.honeywell.com