Function | Selections or |
Prompt | Range of Setting |
Lower Display | Upper Display |
EU/HR DN | 0 to 9999 in |
| engineering units |
| per hour |
|
|
Parameter Definition
RATE
Entering a 0 will imply an immediate step change in Setpoint (i.e., no rate applies).
SP PROG
(optional
feature)
DISABLE
ENABLE
STRT SEG | 1 to 11 |
END SEG | 2 to 12 even |
| numbers |
RAMPUNIT |
|
| TIME |
| EU/MIN |
| EU/HR |
|
|
RECYCLES | 0 to 99 recycles |
|
|
SOAK DEV | 0 to 99 |
|
|
PROG END | LASTSP |
| |
| F SAFE |
|
|
STATE | DISABLE |
| HOLD |
|
|
KEYRESET | DISABLE |
| ToBEGIN |
| RERUN |
|
|
HOTSTART | DISABLE |
| ENABLE |
|
|
SEG1RAMP or | |
SEG1RATE | minutes |
| Engineering |
| units/minute or |
| Engineering |
| units/hour |
|
|
SEG2 SP | Within the Setpoint |
| limits |
SETPOINT RAMP/SOAK
SP RAMP must be disabled.
SP Ramp must be disabled for SP Program prompts to appear. If SP Rate is enabled, it does not operate while an SP Program is running
Start Segment Number
End Segment Number, always end in a soak segment (2, 4, ... 12)
TIME in hours: minutes
RATE in Enineering units per minute RATE in Enineering units per hour
Number of Program Recycles
Guaranteed Soak Deviation Value
The number selected will be the PV value (in engineering units) above or below the setpoint outside of which the timer halts.
Program Termination State
Hold at last setpoint in the program
Manual mode/Failsafe output
Program State at Program End
Reset/Rerun SP Program
Hot Start
Segment #1 Ramp Time or
Segment #1 Ramp Rate
Select TIME, EU/MIN, or EU/HR at prompt RAMPUNIT. All ramps will use the same selection.
Segment #2 Soak Setpoint Value
30 | UDC3200 Universal Digital Controller Operator Manual | 04/08 |