Honeywell UDC3200 manual Tuning Set Up Group

Page 32

3.3 Tuning Set Up Group

Function

Selections or

Prompt

Range of Setting

Lower Display

Upper Display

PROP BD

0.1 to 9999 %

or

or

GAIN

0.001 to 1000

RATE MIN

0.00 to 10.00

 

minutes

 

 

RSET MIN

0.02 to 50.00

or

 

RSET RPM

 

MAN RSET

–100 to +100

 

(in % output)

PROPBD2

0.1 to 9999 %

or

or

GAIN 2

0.001 to 1000

 

 

RATE2MIN

0.00 to 10.00

 

minutes

Parameter Definition

PROPORTIONAL BAND (simplex) is the percent of the range of the measured variable for which a proportional controller will produce a 100 % change in its output.

GAIN is the ratio of output change (%) over the measured variable change (%) that caused it.

G = 100 / %PB where PB is the proportional band(in %)

If the PB is 20 %, then the Gain is 5. And, at those settings, a 3 % change in the error signal (SP-PV) will result in a 15 % change in the controller's output due to proportional action. If the Gain is 2, then the PB is 50 %.

Also defined as "HEAT" Gain on Duplex models for variations of Heat/Cool applications.

The selection of Proportional Band or Gain is made in the CONTROL parameter group under prompt PBorGAIN.

RATE action, in minutes, affects the controller's output whenever the deviation is changing; and affects it more when the deviation is changing faster.

RSET MIN = Reset in Minutes per Repeat

RSET RPM = Reset in Repeats per Minute

RESET (or Integral Time) adjusts the controller's output in accordance with both the size of the deviation (SP–PV) and the time that it lasts. The amount of the corrective action depends on the value of Gain. The Reset adjustment is measured as how many times proportional action is repeated per minute or how many minutes before one repeat of the proportional action occurs.

Used with control algorithm PID-A or PID-B.

Also defined as "HEAT" Reset on Duplex models for variations of Heat/Cool applications.

ATTENTION The selection of whether Minutes per Repeat or Repeats per Minute is used is made in the CONTROL parameters group under the prompt MINorRPM.

MANUAL RESET is only applicable if you use control algorithm PD WITH MANUAL RESET in the Algorithm Set Up group. Because a proportional controller will not necessarily line out at setpoint, there will be a deviation (offset) from setpoint. This eliminates the offset and lets the PV line out at setpoint.

ATTENTION Bias is shown on the lower display.

PROPORTIONAL BAND 2 or GAIN 2, RATE 2, and RESET 2 parameters are the same as previously described for “Heat” except that they refer to the cool zone tuning constants on duplex models or the second set of PID constants, whichever is pertinent.

This is the same as above except that it applies to Duplex models for the "COOL" zone of Heat/Cool applications or for the second set of PID constants.

26

UDC3200 Universal Digital Controller Operator Manual

04/08

Image 32
Contents UDC3200 Universal Digital Controller Operator Manual WARRANTY/REMEDY ContactsWorld Wide Web TelephoneSymbol Definitions Symbol DefinitionContents TROUBLESHOOTING/SERVICE Page Function of Displays and Keys Operator InterfaceFunction of Displays and Keys CE Conformity Europe Keys and FunctionsUDC3200 Universal Digital Controller Operator Manual Page Pre-installation Information Model Number InterpretationControl and Alarm Relay Contact Information Alarm RelaysAlarm Relay Contact Information Control RelaysPhysical Considerations Overall DimensionsMounting Mounting Method Step ActionWiring Wiring Diagrams Permissible Wiring BundlingBundle No Wire Functions Universal Output Functionality and RestrictionsINU Details Wiring the ControllerCallout Line Neutral Voltage L2/N Earth Ground HotAC/DC Input #1 RTDInput #2 Input 2 ConnectionsTime Simplex Time DuplexL2/N Power Supply PowerPower Load Relay Load Relay Load10 Open Collector Output Time Duplex with a Dual Relay Board L2/N Relay LoadUDC3200 Universal Digital Controller Operator Manual 04/08 15 RS-422/485 Communications Option Connections 17 Auxiliary Output and Digital Inputs Option Connections Digital Inputs 26 + 12 +Configuration Configuration Prompt HierarchyConfiguration Procedure ProcedureConfiguration Procedure IntroductionTuning Set Up Group Configuration is Complete RSET2MIN02 to RSET2RPM CYC SEC CYC SX3 CYC2 SEC CYC2 SX3 Security LockoutSP SEL Auto MAN Disable Enable RUN HoldDisable Enable SP Ramp Set Up Group Keyreset EU/HR DNSP Prog Strt SEG END SEGSEG2TIME SEG3RATESEG4 SP SEG4TIME SEG5RATE SEG6 SP SEG6TIMEAT Error Accutune Set Up GroupFuzzy Disable Enable Accutune Tune Algorithm Set Up Group ALG ON-OFFTimer ALG PD+MRStart KEY Alarm LOW Disp TI REM Time Period000 to INP ALG1Summer with Ratio and BIAS-The following formula Input High Select with Ratio and BIAS-This selectionInput LOW Select with Ratio and BIAS- This selection Multiplier Divider with Square Root -The followingFCC Math KCalc HI Calc LOALG1 INB ALG1 INCPCT CO ALG1 BiasOUT RNG Output Set Up GroupOUT ALG Rlystate RLY TypeMotor TI CUR OUTLOW VAL High VALInput 1 Set Up Group IN1 TypeXmitter IN1 LOWRatio Bias IN101 to Burnout NoneEMISSIV1 XMITTER2 Input 2 Set Up GroupIN2 Type IN2 High IN2 LOWBias IN2 Burnout Burnout Protection Sensor BreakEMISSIV2 Control Set Up Group PV Source Input ALG1 PID SetsInput Input Algorithm PID Sets 2PV SWPWR Mode RSP SRC None Input ALG1 AutobiasSP Track PWR OUTAction OUT RatePCT/M UP PCT/M DNFailsafe Mode DeadbandFailmode MAN OUTRPM MinutesOptions Group AUX OUTAuxiliary Output Selection No Auxiliary OutputWas not previously started via DIG INP1No Digital Input Selections To RUN DIG 1COMB DIG INP2DIG2COMB Digital Input 2 Selections Digital Input 2 CombinationsCommunications Group Shed SP UnitsCSP Rato CSP BiasAlarms Set Up Group High Alarm LOW AlarmA1S1 EV Beginning of SegmentA1S2 EV A2S1TYPEA2S1 EV A2S2TYPEALARM12 DiagnostDisplay Set Up Group Page Entering a Security Code Operator InterfaceIndividual key lockout Procedure to Enter a Security CodeKey error ALM 1 OUT 1 DI 1 Or MAN None, F or C Monitoring Your Controller 4.4.1 AnnunciatorsAnnunciators Viewing the operating parameters Lower Display Key Parameter PromptsDescription Diagnostic MessagesDiagnostic Messages Functional Overview Block Diagram of the UDC3200 Controller Accutune Configuration checkTuning indicators Procedure for Starting Tune Tune for Simplex OutputsOperation Step Operation Press ResultConfiguration Check for Duplex Tune for Duplex Heat/CoolUsing Automatic Tune at start-up for Duplex Heat/Cool Using Blended Tune at start-up for Duplex Heat/Cool Using Manual Tune at start-up for Duplex Heat/CoolStep Operation Press Result Error Codes 10 Procedure for Accessing Accutune Error Codes11 Accutune Error Codes Aborting AccutuneHow it works ConfigurationFuzzy Overshoot Suppression Background Tests Background TestsEE Fail INP1 RNGRV Limit SegerrCAL MTR CurfailController Failure Symptoms Other symptomsSales and Service Page Http//hpsweb.honeywell.com