4.5.6 Error Codes

Table 4-10 Procedure for Accessing Accutune Error Codes

Step

Operation

Press

Result

1Select Accutune

Set-up Group

2Go to Error Code

Prompt

Setup

Function

Upper Display = SETUP

Lower Display = ACCUTUNE

Upper Display = (an error code)

Lower Display = AT ERROR

Table 4-11lists all the error codes, definitions, and fixes.

Table 4-11 Accutune Error Codes

Error Code

 

(Upper Display)

Definition

RUNNING

ACCUTUNE RUNNING

NONE

NO ERRORS OCCURRED

 

DURING LAST ACCUTUNE

 

PROCEDURE

ID FAIL

PROCESS IDENTIFICATION

 

FAILURE

 

Autotune has aborted

 

because an illegal value of

 

GAIN, RATE, or reset was

 

calculated.

ABORT

CURRENT ACCUTUNE

 

PROCESS ABORTED

 

caused by the following

 

conditions:

 

a. Operator changed to

 

Manual mode

 

b. Digital Input detected

 

c. In Heat region of output

 

and a Cool output calculated

 

or vice versa.

SP2

LSP2 not enabled or LSP1 or

 

LSP2 not in use (only applies

 

to Duplex Tuning)

Fix

The Accutune process is still active (Read Only)

None

Illegal Values

– try Accutune again.

untunable process -- contact local application engineer.

Try Accutune again

Enable LSP2 and configure the desired LSP1 and LSP2 setpoints.

Aborting Accutune

To abort Accutune and return to the last previous operation (SP or output level), press MAN-AUTOkey to abort the Accutune process or increment from the “DO SLOW” or “DO FAST” prompt to the “TUNE OFF” prompt.

Completing Accutune

When Accutune is complete, the calculated tuning parameters are stored in their proper memory location and can be viewed in the TUNING Set up Group, and the

04/08

UDC3200 Universal Digital Controller Operator Manual

77

Image 83
Contents UDC3200 Universal Digital Controller Operator Manual Telephone WARRANTY/REMEDYContacts World Wide WebSymbol Definition Symbol DefinitionsContents TROUBLESHOOTING/SERVICE Page Function of Displays and Keys Operator InterfaceFunction of Displays and Keys Keys and Functions CE Conformity EuropeUDC3200 Universal Digital Controller Operator Manual Page Model Number Interpretation Pre-installation InformationControl Relays Control and Alarm Relay Contact InformationAlarm Relays Alarm Relay Contact InformationPhysical Considerations Overall DimensionsMounting Step Action Mounting MethodWiring Universal Output Functionality and Restrictions Wiring DiagramsPermissible Wiring Bundling Bundle No Wire FunctionsINU Details Wiring the ControllerCallout Line Neutral Voltage L2/N Earth Ground HotAC/DC RTD Input #1Input 2 Connections Input #2Time Duplex Time SimplexRelay Load L2/N PowerSupply Power Power Load Relay Load10 Open Collector Output L2/N Relay Load Time Duplex with a Dual Relay BoardUDC3200 Universal Digital Controller Operator Manual 04/08 15 RS-422/485 Communications Option Connections Digital Inputs 17 Auxiliary Output and Digital Inputs Option Connections12 + 26 +Configuration Prompt Hierarchy ConfigurationIntroduction Configuration ProcedureProcedure Configuration ProcedureTuning Set Up Group RSET2RPM CYC SEC CYC SX3 CYC2 SEC CYC2 SX3 Security Lockout Configuration is CompleteRSET2MIN 02 toSP SEL Auto MAN Disable Enable RUN HoldDisable Enable SP Ramp Set Up Group Strt SEG END SEG KeyresetEU/HR DN SP ProgSEG5RATE SEG6 SP SEG6TIME SEG2TIMESEG3RATE SEG4 SP SEG4TIMEAT Error Accutune Set Up GroupFuzzy Disable Enable Accutune Tune ALG ON-OFF Algorithm Set Up GroupALG PD+MR TimerINP ALG1 Start KEY Alarm LOW Disp TI REM TimePeriod 000 toMultiplier Divider with Square Root -The following Summer with Ratio and BIAS-The following formulaInput High Select with Ratio and BIAS-This selection Input LOW Select with Ratio and BIAS- This selectionCalc LO FCCMath K Calc HIALG1 Bias ALG1 INBALG1 INC PCT COOUT RNG Output Set Up GroupOUT ALG RLY Type RlystateHigh VAL Motor TICUR OUT LOW VALIN1 Type Input 1 Set Up GroupBias IN1 XmitterIN1 LOW Ratio01 to Burnout NoneEMISSIV1 XMITTER2 Input 2 Set Up GroupIN2 Type Burnout Burnout Protection Sensor Break IN2 HighIN2 LOW Bias IN2EMISSIV2 PID Sets 2PV SW Control Set Up GroupPV Source Input ALG1 PID Sets Input Input AlgorithmPWR OUT PWR ModeRSP SRC None Input ALG1 Autobias SP TrackPCT/M DN ActionOUT Rate PCT/M UPMAN OUT Failsafe ModeDeadband FailmodeMinutes RPMNo Auxiliary Output Options GroupAUX OUT Auxiliary Output SelectionWas not previously started via DIG INP1No Digital Input Selections To RUN Digital Input 2 Selections Digital Input 2 Combinations DIG 1COMBDIG INP2 DIG2COMBCommunications Group CSP Bias Shed SPUnits CSP RatoAlarms Set Up Group Beginning of Segment High AlarmLOW Alarm A1S1 EVA2S2TYPE A1S2 EVA2S1TYPE A2S1 EVDiagnost ALARM12Display Set Up Group Page Operator Interface Entering a Security CodeIndividual key lockout Procedure to Enter a Security CodeKey error ALM 1 OUT 1 DI 1 Or MAN None, F or C Monitoring Your Controller 4.4.1 AnnunciatorsAnnunciators Lower Display Key Parameter Prompts Viewing the operating parametersDescription Diagnostic MessagesDiagnostic Messages Functional Overview Block Diagram of the UDC3200 Controller Accutune Configuration checkTuning indicators Step Operation Press Result Procedure for Starting TuneTune for Simplex Outputs OperationTune for Duplex Heat/Cool Configuration Check for DuplexUsing Automatic Tune at start-up for Duplex Heat/Cool Using Manual Tune at start-up for Duplex Heat/Cool Using Blended Tune at start-up for Duplex Heat/CoolStep Operation Press Result Aborting Accutune Error Codes10 Procedure for Accessing Accutune Error Codes 11 Accutune Error CodesHow it works ConfigurationFuzzy Overshoot Suppression INP1 RNG Background TestsBackground Tests EE FailCurfail RV LimitSegerr CAL MTROther symptoms Controller Failure SymptomsSales and Service Page Http//hpsweb.honeywell.com