3.2 Configuration Procedure

Introduction

Each of the Set Up groups and their functions are pre-configured at the factory. If you want to change any of these selections or values, follow the procedure in Table 3-1.This procedure tells you the keys to press to get to any Set Up group and any associated Function parameter prompt.

Procedure

ATTENTION

The prompting scrolls at a rate of 2/3 seconds when the SET UP or FUNCTION key is held in.

Also, or keys will move group prompts forward or backward at a rate twice as fast.

Table 3-1 Configuration Procedure

Step

Operation

 

Press

 

 

Result

1

Enter Set Up

 

 

 

Upper Display = SETUP

 

Setup

 

 

Mode

 

 

Lower Display = TUNING (This is the first Set Up Group title)

 

 

 

 

2

Select any Set

 

 

 

Sequentially displays the other Set Up group titles. You can also

 

Setup

 

 

Up Group

 

 

use the

or

keys to scan the Set Up groups in both

 

 

 

 

 

 

 

 

 

directions. Stop at the Set Up group title that describes the group of

 

 

 

 

 

parameters you want to configure. Then proceed to the next step.

3

Select a Function

Function

 

Parameter

 

 

4

Change the

or

 

Value or

 

 

Selection

 

5

Enter the Value

Function

 

or Selection

 

 

6

Exit Configuration

Lower

 

 

Display

Upper Display = the current value or selection for the first function prompt of the selected Set Up group.

Lower Display = the first Function prompt within that Set Up group. Sequentially displays the other function prompts of the Set Up group you have selected. Stop at the function prompt that you want to change, then proceed to the next step.

Increments or decrements the value or selection that appears for the selected function prompt. If you change the value or selection of a parameter while in Set Up mode but then decide not to enter it, press the MAN/AUTO key once. This will recall the original configuration. This “recall” procedure does not work for a Field Calibration process. Field Calibration is a one-way operation.

Enters value or selection made into memory after another key is pressed.

Exits configuration mode and returns controller to the same state it was in immediately preceding entry into the Set Up mode. It stores any changes you have made.

If you do not press any keys for 30 seconds, the controller times out and reverts to the mode and associated display used prior to entry into Set Up mode.

04/08

UDC3200 Universal Digital Controller Operator Manual

25

Image 31
Contents UDC3200 Universal Digital Controller Operator Manual Telephone WARRANTY/REMEDYContacts World Wide WebSymbol Definition Symbol DefinitionsContents TROUBLESHOOTING/SERVICE Page Function of Displays and Keys Operator InterfaceFunction of Displays and Keys Keys and Functions CE Conformity EuropeUDC3200 Universal Digital Controller Operator Manual Page Model Number Interpretation Pre-installation InformationControl Relays Control and Alarm Relay Contact InformationAlarm Relays Alarm Relay Contact InformationMounting Overall DimensionsPhysical Considerations Step Action Mounting MethodWiring Universal Output Functionality and Restrictions Wiring DiagramsPermissible Wiring Bundling Bundle No Wire FunctionsINU Callout Wiring the ControllerDetails AC/DC Earth Ground HotLine Neutral Voltage L2/N RTD Input #1Input 2 Connections Input #2Time Duplex Time SimplexRelay Load L2/N PowerSupply Power Power Load Relay Load10 Open Collector Output L2/N Relay Load Time Duplex with a Dual Relay BoardUDC3200 Universal Digital Controller Operator Manual 04/08 15 RS-422/485 Communications Option Connections Digital Inputs 17 Auxiliary Output and Digital Inputs Option Connections12 + 26 +Configuration Prompt Hierarchy ConfigurationIntroduction Configuration ProcedureProcedure Configuration ProcedureTuning Set Up Group RSET2RPM CYC SEC CYC SX3 CYC2 SEC CYC2 SX3 Security Lockout Configuration is CompleteRSET2MIN 02 toDisable Enable Auto MAN Disable Enable RUN HoldSP SEL SP Ramp Set Up Group Strt SEG END SEG KeyresetEU/HR DN SP ProgSEG5RATE SEG6 SP SEG6TIME SEG2TIMESEG3RATE SEG4 SP SEG4TIMEFuzzy Disable Enable Accutune Tune Accutune Set Up GroupAT Error ALG ON-OFF Algorithm Set Up GroupALG PD+MR TimerINP ALG1 Start KEY Alarm LOW Disp TI REM TimePeriod 000 toMultiplier Divider with Square Root -The following Summer with Ratio and BIAS-The following formulaInput High Select with Ratio and BIAS-This selection Input LOW Select with Ratio and BIAS- This selectionCalc LO FCCMath K Calc HIALG1 Bias ALG1 INBALG1 INC PCT COOUT ALG Output Set Up GroupOUT RNG RLY Type RlystateHigh VAL Motor TICUR OUT LOW VALIN1 Type Input 1 Set Up GroupBias IN1 XmitterIN1 LOW RatioEMISSIV1 Burnout None01 to IN2 Type Input 2 Set Up GroupXMITTER2 Burnout Burnout Protection Sensor Break IN2 HighIN2 LOW Bias IN2EMISSIV2 PID Sets 2PV SW Control Set Up GroupPV Source Input ALG1 PID Sets Input Input AlgorithmPWR OUT PWR ModeRSP SRC None Input ALG1 Autobias SP TrackPCT/M DN ActionOUT Rate PCT/M UPMAN OUT Failsafe ModeDeadband FailmodeMinutes RPMNo Auxiliary Output Options GroupAUX OUT Auxiliary Output SelectionNo Digital Input Selections DIG INP1Was not previously started via To RUN Digital Input 2 Selections Digital Input 2 Combinations DIG 1COMBDIG INP2 DIG2COMBCommunications Group CSP Bias Shed SPUnits CSP RatoAlarms Set Up Group Beginning of Segment High AlarmLOW Alarm A1S1 EVA2S2TYPE A1S2 EVA2S1TYPE A2S1 EVDiagnost ALARM12Display Set Up Group Page Operator Interface Entering a Security CodeKey error Procedure to Enter a Security CodeIndividual key lockout Annunciators Monitoring Your Controller 4.4.1 AnnunciatorsALM 1 OUT 1 DI 1 Or MAN None, F or C Lower Display Key Parameter Prompts Viewing the operating parametersDiagnostic Messages Diagnostic MessagesDescription Functional Overview Block Diagram of the UDC3200 Controller Tuning indicators Configuration checkAccutune Step Operation Press Result Procedure for Starting TuneTune for Simplex Outputs OperationTune for Duplex Heat/Cool Configuration Check for DuplexUsing Automatic Tune at start-up for Duplex Heat/Cool Using Manual Tune at start-up for Duplex Heat/Cool Using Blended Tune at start-up for Duplex Heat/CoolStep Operation Press Result Aborting Accutune Error Codes10 Procedure for Accessing Accutune Error Codes 11 Accutune Error CodesFuzzy Overshoot Suppression ConfigurationHow it works INP1 RNG Background TestsBackground Tests EE FailCurfail RV LimitSegerr CAL MTROther symptoms Controller Failure SymptomsSales and Service Page Http//hpsweb.honeywell.com