3.9Input 2 Set Up Group

 

 

Function Prompt

Selections or

 

 

Parameter

 

 

 

 

Lower Display

Range of Setting

 

 

Definition

 

 

 

 

 

 

Upper Display

 

 

 

 

 

 

 

IN2 TYPE

 

 

 

INPUT 2 ACTUATION TYPE – This selection

 

 

 

 

 

 

 

 

 

determines what actuation you are going to use for

 

 

ATTENTION

 

 

 

 

Input 2.

 

 

 

 

Changing the input

 

 

 

 

 

 

 

 

 

DISABLE—Disables Input.

 

 

 

 

type will result in the

DISABLE

 

 

 

 

 

 

loss of Field

B TC

 

 

B TC—B Thermocouple

 

 

 

 

Calibration values and

E TC H

 

 

E TC H—E Thermocouple High

 

 

 

 

will restore Factory

E TC L

 

 

E TC L—E Thermocouple Low

 

 

 

 

Calibration values.

J TC H

 

 

J TC H—J Thermocouple High

 

 

 

 

 

 

J TC M

 

 

J TC M—J Thermocouple Med

 

 

 

 

Selecting Position

J TC L

 

 

J TC L—J Thermocouple Low

 

 

 

 

Proportional Control in

K TC H

 

 

K TC H—K Thermocouple High

 

 

 

 

the Output Setup

K TC M

 

 

K TC M—K Thermocouple Med

 

 

 

 

Group forces Input 2

K TC L

 

 

K TC L—K Thermocouple Low

 

 

 

 

to the Slidewire

NNM H

 

 

NNM H—Ni-Ni-Moly Thermocouple High

 

 

 

 

Selection.

NNM L

 

 

NNM L—Ni-Ni-Moly Thermocouple Low

 

 

 

 

 

 

NIC H

 

 

NIC H—Nicrosil-Nisil Thermocouple High

 

 

 

 

 

 

NIC L

 

 

NIC L—Nicrosil-Nisil Thermocouple Low

 

 

 

 

 

 

R TC

 

 

R TC—R Thermocouple

 

 

 

 

 

 

S TC

 

 

S TC—S Thermocouple

 

 

 

 

 

 

T TC H

 

 

T TC H—T Thermocouple High

 

 

 

 

 

 

T TC L

 

 

T TC L—T Thermocouple Low

 

 

 

 

 

 

W TC H

 

 

W TC H—W5W26 Thermocouple High

 

 

 

 

 

 

W TC L

 

 

W TC L—W5W26 Thermocouple Low

 

 

 

 

 

 

100 PT

 

 

100 PT—100 Ohm RTD High

 

 

 

 

 

 

100 LO

 

 

100 LO—100 Ohm RTD Low

 

 

 

 

 

 

200 PT

 

 

200 PT—200 Ohm RTD

 

 

 

 

 

 

500 PT

 

 

500 PT—500 Ohm RTD

 

 

 

 

 

 

RAD RH

 

 

RAD RH—Radiamatic RH

 

 

 

 

 

 

RAD RI

 

 

RAD RI—Radiamatic RI

 

 

 

 

 

 

0-20mA

 

 

0-20mA—0 to 20 Milliamperes

 

 

 

 

 

 

4-20mA

 

 

4-20mA—4 to 20 Milliamperes

 

 

 

 

 

 

0-10mV

 

 

0-10mV—0 to 10 Millivolts

 

 

 

 

 

 

0-50mV

 

 

0-50mV—0 to 50 Millivolts

 

 

 

 

 

 

0-100mV

 

 

0-100mV—0 to 100 Millivolts

 

 

 

 

 

 

0-5 V

 

 

0-5V—0 to 5 Volts

 

 

 

 

 

 

1-5 V

 

 

1-5V—1 to 5 Volts

 

 

 

 

 

 

0-10 V

 

 

0-10V—0 to 10 Volts

 

 

 

 

 

 

TC DIFF

 

 

TC DIFF—Thermocouple Differential

 

 

 

 

 

 

SLIDEW

 

 

SLIDEW—Slidewire (For Position Proportional

 

 

 

 

 

 

 

Applications)

 

 

 

 

XMITTER2

B TC

S TC

 

TRANSMITTER CHARACTERIZATION—This

 

 

 

 

E TC H

T TC H

 

selection lets you instruct the controller to

 

 

 

 

 

 

E TC L

T TC L

 

characterize a linear input to represent a non-linear

 

 

 

 

J TC H

W TC H

 

one.

 

 

 

 

 

 

J TC M

W TC L

 

 

Prompt only appears when a linear

 

 

 

 

J TC L

100 PT

 

ATTENTION

 

 

 

 

K TC H

100 LO

 

actuation is selected at prompt IN2 TYPE.

 

 

 

 

 

 

K TC M

200 PT

 

Parameter definitions are the same as in IN2 TYPE.

 

 

 

 

K TC L

500 PT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NNM H

RAD RH

 

 

 

 

 

 

 

 

 

NNM L

RAD RI

 

 

 

 

 

 

 

 

 

NIC H

LINEAR

 

 

 

 

 

 

 

 

 

NIC L

SQROOT

 

 

 

 

 

 

 

 

 

R TC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

04/08

 

UDC3200 Universal Digital Controller Operator Manual

45

 

Image 51
Contents UDC3200 Universal Digital Controller Operator Manual Telephone WARRANTY/REMEDYContacts World Wide WebSymbol Definition Symbol DefinitionsContents TROUBLESHOOTING/SERVICE Page Operator Interface Function of Displays and KeysFunction of Displays and Keys Keys and Functions CE Conformity EuropeUDC3200 Universal Digital Controller Operator Manual Page Model Number Interpretation Pre-installation InformationControl Relays Control and Alarm Relay Contact InformationAlarm Relays Alarm Relay Contact InformationOverall Dimensions MountingPhysical Considerations Step Action Mounting MethodWiring Universal Output Functionality and Restrictions Wiring DiagramsPermissible Wiring Bundling Bundle No Wire FunctionsINU Wiring the Controller CalloutDetails Earth Ground Hot AC/DCLine Neutral Voltage L2/N RTD Input #1Input 2 Connections Input #2Time Duplex Time SimplexRelay Load L2/N PowerSupply Power Power Load Relay Load10 Open Collector Output L2/N Relay Load Time Duplex with a Dual Relay BoardUDC3200 Universal Digital Controller Operator Manual 04/08 15 RS-422/485 Communications Option Connections Digital Inputs 17 Auxiliary Output and Digital Inputs Option Connections12 + 26 +Configuration Prompt Hierarchy ConfigurationIntroduction Configuration ProcedureProcedure Configuration ProcedureTuning Set Up Group RSET2RPM CYC SEC CYC SX3 CYC2 SEC CYC2 SX3 Security Lockout Configuration is CompleteRSET2MIN 02 toAuto MAN Disable Enable RUN Hold Disable EnableSP SEL SP Ramp Set Up Group Strt SEG END SEG KeyresetEU/HR DN SP ProgSEG5RATE SEG6 SP SEG6TIME SEG2TIMESEG3RATE SEG4 SP SEG4TIMEAccutune Set Up Group Fuzzy Disable Enable Accutune TuneAT Error ALG ON-OFF Algorithm Set Up GroupALG PD+MR TimerINP ALG1 Start KEY Alarm LOW Disp TI REM TimePeriod 000 toMultiplier Divider with Square Root -The following Summer with Ratio and BIAS-The following formulaInput High Select with Ratio and BIAS-This selection Input LOW Select with Ratio and BIAS- This selectionCalc LO FCCMath K Calc HIALG1 Bias ALG1 INBALG1 INC PCT COOutput Set Up Group OUT ALGOUT RNG RLY Type RlystateHigh VAL Motor TICUR OUT LOW VALIN1 Type Input 1 Set Up GroupBias IN1 XmitterIN1 LOW RatioBurnout None EMISSIV101 to Input 2 Set Up Group IN2 TypeXMITTER2 Burnout Burnout Protection Sensor Break IN2 HighIN2 LOW Bias IN2EMISSIV2 PID Sets 2PV SW Control Set Up GroupPV Source Input ALG1 PID Sets Input Input AlgorithmPWR OUT PWR ModeRSP SRC None Input ALG1 Autobias SP TrackPCT/M DN ActionOUT Rate PCT/M UPMAN OUT Failsafe ModeDeadband FailmodeMinutes RPMNo Auxiliary Output Options GroupAUX OUT Auxiliary Output SelectionDIG INP1 No Digital Input SelectionsWas not previously started via To RUN Digital Input 2 Selections Digital Input 2 Combinations DIG 1COMBDIG INP2 DIG2COMBCommunications Group CSP Bias Shed SPUnits CSP RatoAlarms Set Up Group Beginning of Segment High AlarmLOW Alarm A1S1 EVA2S2TYPE A1S2 EVA2S1TYPE A2S1 EVDiagnost ALARM12Display Set Up Group Page Operator Interface Entering a Security CodeProcedure to Enter a Security Code Key errorIndividual key lockout Monitoring Your Controller 4.4.1 Annunciators AnnunciatorsALM 1 OUT 1 DI 1 Or MAN None, F or C Lower Display Key Parameter Prompts Viewing the operating parametersDiagnostic Messages Diagnostic MessagesDescription Functional Overview Block Diagram of the UDC3200 Controller Configuration check Tuning indicatorsAccutune Step Operation Press Result Procedure for Starting TuneTune for Simplex Outputs OperationTune for Duplex Heat/Cool Configuration Check for DuplexUsing Automatic Tune at start-up for Duplex Heat/Cool Using Manual Tune at start-up for Duplex Heat/Cool Using Blended Tune at start-up for Duplex Heat/CoolStep Operation Press Result Aborting Accutune Error Codes10 Procedure for Accessing Accutune Error Codes 11 Accutune Error CodesConfiguration Fuzzy Overshoot SuppressionHow it works INP1 RNG Background TestsBackground Tests EE FailCurfail RV LimitSegerr CAL MTROther symptoms Controller Failure SymptomsSales and Service Page Http//hpsweb.honeywell.com