3.13 Alarms Set Up Group

Function

Selections or

Parameter Definition

Prompt

Range of Setting

 

Lower Display

Upper Display

 

A1S1 VAL

Value in

ALARM 1 SETPOINT 1 VALUE—This is the value at which you

 

engineering units

want the alarm type chosen in prompt A1S1TYPE to actuate. The

 

 

value depends on what the setpoint has been configured to

 

 

represent. No setpoint is required for alarms configured for

 

 

Communications SHED. For SP Programming the value is the

 

 

segment number for which the event applies.

 

 

This prompt does not appear for “Alarm on Manual” type alarm.

 

 

For example: A1S1TYPE = MANUAL.

 

 

 

A1S2 VAL

Value in

ALARM 1 SETPOINT 2 VALUE—This is the value at which you

 

engineering units

want the alarm type chosen in prompt A1S2TYPE to actuate.

 

 

The details are the same as A1S1 VAL.

 

 

 

A2S1 VAL

Value in

ALARM 2 SETPOINT 1 VALUE—This is the value at which you

 

engineering units

want the alarm type chosen in prompt A2S1TYPE to actuate.

 

 

The details are the same as A1S1 VAL.

 

 

 

A2S2 VAL

Value in

ALARM 2 SETPOINT 2 VALUE—This is the value at which you

 

engineering units

want the alarm type chosen in prompt A2S2TYPE to actuate.

 

 

The details are the same as A1S1 VAL.

 

 

 

A1S1TYPE

 

ALARM 1 SETPOINT 1 TYPE—Select what you want Setpoint 1

 

 

of Alarm 1 to represent. It can represent the Process Variable,

 

 

Deviation, Input 1, Input 2, Output, and if you have a model with

 

 

communications, you can configure the controller to alarm on

 

 

SHED. If you have setpoint programming, you can alarm when a

 

 

segment goes ON or OFF.

 

NONE

NO ALARM

 

INPUT 1

INPUT 1

 

INPUT 2

INPUT 2

 

PV

PROCESS VARIABLE

 

DEV

DEVIATION

 

OUTPUT

OUTPUT (NOTE 1)

 

SHED

SHED FROM COMMUNICATIONS

 

EV ON

EVENT ON (SP PROGRAMMING)

 

EV OFF

EVENT OFF (SP PROGRAMMING)

 

MANUAL

ALARM ON MANUAL MODE (NOTE 2)

 

REM SP

REMOTE SETPOINT

 

F SAFE

FAILSAFE

 

PV RATE

PV RATE OF CHANGE

 

DIG INP 1

DIGITAL INPUT 1 ACTUATED (NOTE 7)

 

DIG INP 2

DIGITAL INPUT 2 ACTUATED (NOTE 7)

 

DEV 2

DEVIATION FROM LSP 2 (NOTE 3)

 

BREAK

LOOP BREAK (NOTE 4)

 

TCWARN

THERMOCOUPLE WARNING (NOTE 5)

 

TCFAIL

THERMOCOUPLE FAIL (NOTE 6)

 

PVHOLD

PV HOLD

 

 

 

ATTENTION

NOTE 1. When the controller is configured for Three Position Step Control, alarms set for Output will not function.

NOTE 2. Alarm 1 is not available if the Timer is enabled because Alarm 1 is dedicated to Timer output.

NOTE 3. This Deviation Alarm is based upon deviation from the 2nd Local Setpoint or Remote SP

04/08

UDC3200 Universal Digital Controller Operator Manual

59

Image 65
Contents UDC3200 Universal Digital Controller Operator Manual Contacts WARRANTY/REMEDYWorld Wide Web TelephoneSymbol Definition Symbol DefinitionsContents TROUBLESHOOTING/SERVICE Page Function of Displays and Keys Operator InterfaceFunction of Displays and Keys Keys and Functions CE Conformity EuropeUDC3200 Universal Digital Controller Operator Manual Page Model Number Interpretation Pre-installation InformationAlarm Relays Control and Alarm Relay Contact InformationAlarm Relay Contact Information Control RelaysPhysical Considerations Overall DimensionsMounting Step Action Mounting MethodWiring Permissible Wiring Bundling Wiring DiagramsBundle No Wire Functions Universal Output Functionality and RestrictionsINU Details Wiring the ControllerCallout Line Neutral Voltage L2/N Earth Ground HotAC/DC RTD Input #1Input 2 Connections Input #2Time Duplex Time SimplexSupply Power L2/N PowerPower Load Relay Load Relay Load10 Open Collector Output L2/N Relay Load Time Duplex with a Dual Relay BoardUDC3200 Universal Digital Controller Operator Manual 04/08 15 RS-422/485 Communications Option Connections Digital Inputs 17 Auxiliary Output and Digital Inputs Option Connections12 + 26 +Configuration Prompt Hierarchy ConfigurationProcedure Configuration ProcedureConfiguration Procedure IntroductionTuning Set Up Group RSET2MIN Configuration is Complete02 to RSET2RPM CYC SEC CYC SX3 CYC2 SEC CYC2 SX3 Security LockoutSP SEL Auto MAN Disable Enable RUN HoldDisable Enable SP Ramp Set Up Group EU/HR DN KeyresetSP Prog Strt SEG END SEGSEG3RATE SEG2TIMESEG4 SP SEG4TIME SEG5RATE SEG6 SP SEG6TIMEAT Error Accutune Set Up GroupFuzzy Disable Enable Accutune Tune ALG ON-OFF Algorithm Set Up GroupALG PD+MR TimerPeriod Start KEY Alarm LOW Disp TI REM Time000 to INP ALG1Input High Select with Ratio and BIAS-This selection Summer with Ratio and BIAS-The following formulaInput LOW Select with Ratio and BIAS- This selection Multiplier Divider with Square Root -The followingMath K FCCCalc HI Calc LOALG1 INC ALG1 INBPCT CO ALG1 BiasOUT RNG Output Set Up GroupOUT ALG RLY Type RlystateCUR OUT Motor TILOW VAL High VALIN1 Type Input 1 Set Up GroupIN1 LOW XmitterRatio Bias IN101 to Burnout NoneEMISSIV1 XMITTER2 Input 2 Set Up GroupIN2 Type IN2 LOW IN2 HighBias IN2 Burnout Burnout Protection Sensor BreakEMISSIV2 PV Source Input ALG1 PID Sets Control Set Up GroupInput Input Algorithm PID Sets 2PV SWRSP SRC None Input ALG1 Autobias PWR ModeSP Track PWR OUTOUT Rate ActionPCT/M UP PCT/M DNDeadband Failsafe ModeFailmode MAN OUTMinutes RPMAUX OUT Options GroupAuxiliary Output Selection No Auxiliary OutputWas not previously started via DIG INP1No Digital Input Selections To RUN DIG INP2 DIG 1COMB DIG2COMB Digital Input 2 Selections Digital Input 2 CombinationsCommunications Group Units Shed SPCSP Rato CSP BiasAlarms Set Up Group LOW Alarm High AlarmA1S1 EV Beginning of SegmentA2S1TYPE A1S2 EVA2S1 EV A2S2TYPEDiagnost ALARM12Display Set Up Group Page Operator Interface Entering a Security CodeIndividual key lockout Procedure to Enter a Security CodeKey error ALM 1 OUT 1 DI 1 Or MAN None, F or C Monitoring Your Controller 4.4.1 AnnunciatorsAnnunciators Lower Display Key Parameter Prompts Viewing the operating parametersDescription Diagnostic MessagesDiagnostic Messages Functional Overview Block Diagram of the UDC3200 Controller Accutune Configuration checkTuning indicators Tune for Simplex Outputs Procedure for Starting TuneOperation Step Operation Press ResultTune for Duplex Heat/Cool Configuration Check for DuplexUsing Automatic Tune at start-up for Duplex Heat/Cool Using Manual Tune at start-up for Duplex Heat/Cool Using Blended Tune at start-up for Duplex Heat/CoolStep Operation Press Result 10 Procedure for Accessing Accutune Error Codes Error Codes11 Accutune Error Codes Aborting AccutuneHow it works ConfigurationFuzzy Overshoot Suppression Background Tests Background TestsEE Fail INP1 RNGSegerr RV LimitCAL MTR CurfailOther symptoms Controller Failure SymptomsSales and Service Page Http//hpsweb.honeywell.com