Honeywell UDC3200 manual Configuration Prompt Hierarchy

Page 30

3 Configuration

3.1 Configuration Prompt Hierarchy

Set Up Group

Function Prompts

TUNING

PROP BD or

 

GAINVALn

 

RATE MIN

 

RSET MIN or

 

MAN RSET

 

PROPBD2 or

 

RATE2MIN

 

 

RSET2MIN

 

 

GAIN

 

 

 

 

 

RSET RPM

 

 

 

GAIN 2

 

 

 

 

or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RSET2RPM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CYC SEC or

 

CYC2 SEC or

 

SECURITY

 

LOCKOUT

 

AUTO MAN

 

SP SEL

 

RUN HOLD

 

 

 

 

CYC SX3

 

CYC2 SX3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPRAMP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP RAMP

 

TIME MIN

 

FINAL SP

 

SP RATE

 

EU/HR UP

 

EU/HR DN

 

EUHRUP2

 

 

EUHRDN2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP PROG

 

STRT SEG

 

END SEG

 

RAMPUNIT

 

RECYCLES

 

SOAK DEV

 

PROG END

 

 

STATE

 

 

 

 

 

 

 

 

 

* x = 1 to 12. Program concludes after segment 12

 

 

 

KEYRESET

 

HOTSTART

 

SEGxRAMP

 

SEGx SP*

 

 

 

 

 

 

 

 

or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SEGxRATE

 

 

 

 

 

 

 

 

 

 

 

 

ACCUTUNE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FUZZY

 

ACCUTUNE

 

DUPLEX

 

AT ERROR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALGORTHM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONT ALG

 

TIMER

 

PERIOD

 

START

 

LOW DISP

 

INP ALG1

 

MATH K

 

 

CALC HI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CALC LO

 

ALG1 INA

 

ALG1 INB

 

ALG1 INC

 

PCT CO

 

PCT H2

 

ALG1BIAS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUT ALG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUT ALG

 

RLYSTATE

 

RLY TYPE

 

CUR OUT

 

LOW VAL

 

HIGH VAL

 

CO RANGE

 

 

MOTOR TI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INPUT1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IN1 TYPE

 

XMITTER1

 

IN1 HIGH

 

IN1 LOW

 

RATIO 1

 

BIAS IN1

 

FILTER 1

 

 

BURNOUT1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EMISSIV1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INPUT2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IN2 TYPE

 

XMITTER2

 

IN2 HIGH

 

IN2 LOW

 

RATIO 2

 

BIAS IN2

 

FILTER 2

 

 

BURNOUT2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EMISSIV2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTRL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PV SOURC

 

PID SETS

 

SW VALUE

 

LSP'S

 

RSP SRC

 

AUTOBIAS

 

SP TRACK

 

 

PWR MODE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PWR OUT

 

SP HiLIM

 

SP LoLIM

 

ACTION

 

OUT RATE

 

PCT/M UP

 

PCT/M DN

 

 

OUTHiLIM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTLoLIM

 

I Hi LIM

 

I Lo LIM

 

DROPOFF

 

DEADBAND

 

OUT HYST

 

FAILSAFE

 

 

FAILMODE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAN OUT

 

AUTO OUT

 

PBorGAIN

 

MINorRPM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OPTIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AUX OUT

 

LOW VAL

 

HIGH VAL

 

CORANGE

 

DIG1 INP

 

DIG1 COM

 

DIG2 INP

 

 

DIG2 COM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Com ADDR

 

ComSTATE

 

IR ENABLE

 

BAUD

 

TX DELAY

 

WSFLOAT

 

SHEDENAB

 

 

SHEDTIME

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHEDMODE

 

SHEDSP

 

UNITS

 

CSP RATO

 

CSP BIAS

 

LOOPBACK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALARMS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A1S1TYPE

 

A1S1 VAL

 

A1S1 H L

 

A1S1 EV

 

A1S2 TYPE

 

A1S2 VAL

 

A1S2 H L

 

 

A1S2 EV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A2S1TYPE

 

A2S1 VAL

 

A2S1 H L

 

A2S1 EV

 

A2S2TYPE

 

A2S2 VAL

 

A2S2 H L

 

 

A2S2 EV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL HYST

 

ALM OUT1

 

BLOCK

 

DIAGNOST

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DISPLAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DECIMAL

 

TEMPUNIT

 

PWR FREQ

 

RATIO 2

 

LANGUAGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CALIB

USED FOR FIELD CALIBRATION

 

 

 

 

 

 

 

 

 

 

 

 

 

24

UDC3200 Universal Digital Controller Operator Manual

04/08

Image 30
Contents UDC3200 Universal Digital Controller Operator Manual World Wide Web WARRANTY/REMEDYContacts TelephoneSymbol Definitions Symbol DefinitionContents TROUBLESHOOTING/SERVICE Page Operator Interface Function of Displays and KeysFunction of Displays and Keys CE Conformity Europe Keys and FunctionsUDC3200 Universal Digital Controller Operator Manual Page Pre-installation Information Model Number InterpretationAlarm Relay Contact Information Control and Alarm Relay Contact InformationAlarm Relays Control RelaysOverall Dimensions MountingPhysical Considerations Mounting Method Step ActionWiring Bundle No Wire Functions Wiring DiagramsPermissible Wiring Bundling Universal Output Functionality and RestrictionsINU Wiring the Controller CalloutDetails Earth Ground Hot AC/DCLine Neutral Voltage L2/N Input #1 RTDInput #2 Input 2 ConnectionsTime Simplex Time DuplexPower Load Relay Load L2/N PowerSupply Power Relay Load10 Open Collector Output Time Duplex with a Dual Relay Board L2/N Relay LoadUDC3200 Universal Digital Controller Operator Manual 04/08 15 RS-422/485 Communications Option Connections 17 Auxiliary Output and Digital Inputs Option Connections Digital Inputs26 + 12 +Configuration Configuration Prompt HierarchyConfiguration Procedure Configuration ProcedureProcedure IntroductionTuning Set Up Group 02 to Configuration is CompleteRSET2MIN RSET2RPM CYC SEC CYC SX3 CYC2 SEC CYC2 SX3 Security LockoutAuto MAN Disable Enable RUN Hold Disable EnableSP SEL SP Ramp Set Up Group SP Prog KeyresetEU/HR DN Strt SEG END SEGSEG4 SP SEG4TIME SEG2TIMESEG3RATE SEG5RATE SEG6 SP SEG6TIMEAccutune Set Up Group Fuzzy Disable Enable Accutune TuneAT Error Algorithm Set Up Group ALG ON-OFFTimer ALG PD+MR000 to Start KEY Alarm LOW Disp TI REM TimePeriod INP ALG1Input LOW Select with Ratio and BIAS- This selection Summer with Ratio and BIAS-The following formulaInput High Select with Ratio and BIAS-This selection Multiplier Divider with Square Root -The followingCalc HI FCCMath K Calc LOPCT CO ALG1 INBALG1 INC ALG1 BiasOutput Set Up Group OUT ALGOUT RNG Rlystate RLY TypeLOW VAL Motor TICUR OUT High VALInput 1 Set Up Group IN1 TypeRatio XmitterIN1 LOW Bias IN1Burnout None EMISSIV101 to Input 2 Set Up Group IN2 TypeXMITTER2 Bias IN2 IN2 HighIN2 LOW Burnout Burnout Protection Sensor BreakEMISSIV2 Input Input Algorithm Control Set Up GroupPV Source Input ALG1 PID Sets PID Sets 2PV SWSP Track PWR ModeRSP SRC None Input ALG1 Autobias PWR OUTPCT/M UP ActionOUT Rate PCT/M DNFailmode Failsafe ModeDeadband MAN OUTRPM MinutesAuxiliary Output Selection Options GroupAUX OUT No Auxiliary OutputDIG INP1 No Digital Input SelectionsWas not previously started via To RUN DIG2COMB DIG 1COMBDIG INP2 Digital Input 2 Selections Digital Input 2 CombinationsCommunications Group CSP Rato Shed SPUnits CSP BiasAlarms Set Up Group A1S1 EV High AlarmLOW Alarm Beginning of SegmentA2S1 EV A1S2 EVA2S1TYPE A2S2TYPEALARM12 DiagnostDisplay Set Up Group Page Entering a Security Code Operator InterfaceProcedure to Enter a Security Code Key errorIndividual key lockout Monitoring Your Controller 4.4.1 Annunciators AnnunciatorsALM 1 OUT 1 DI 1 Or MAN None, F or C Viewing the operating parameters Lower Display Key Parameter PromptsDiagnostic Messages Diagnostic MessagesDescription Functional Overview Block Diagram of the UDC3200 Controller Configuration check Tuning indicatorsAccutune Operation Procedure for Starting TuneTune for Simplex Outputs Step Operation Press ResultConfiguration Check for Duplex Tune for Duplex Heat/CoolUsing Automatic Tune at start-up for Duplex Heat/Cool Using Blended Tune at start-up for Duplex Heat/Cool Using Manual Tune at start-up for Duplex Heat/CoolStep Operation Press Result 11 Accutune Error Codes Error Codes10 Procedure for Accessing Accutune Error Codes Aborting AccutuneConfiguration Fuzzy Overshoot SuppressionHow it works EE Fail Background TestsBackground Tests INP1 RNGCAL MTR RV LimitSegerr CurfailController Failure Symptoms Other symptomsSales and Service Page Http//hpsweb.honeywell.com