Honeywell UDC3200 manual Shed SP, Units, CSP Rato, CSP Bias, Loopback, Shed Setpoint Recall

Page 64

Function

Selections or

Prompt

Range of Setting

Lower Display

Upper Display

 

LAST

 

TO MAN

 

FSAFE

 

TO AUTO

 

 

SHED SP

 

 

TO LSP

 

TO CSP

 

 

UNITS

 

 

ENG

 

PERCENT

 

 

CSP RATO

–20.0 to 20.0

 

 

CSP BIAS

–999. to 9999.

 

(engineering units)

 

 

LOOPBACK

 

 

DISABLE

 

ENABLE

 

 

Parameter

Definition

LAST—SAME MODE AND OUTPUT—The controller will return to the same mode (manual or automatic) at the same output level that it had before shed.

TO MAN—MANUAL MODE, SAME OUTPUT—The controller will return to manual mode at the same output level that it had before shed.

FSAFE—MANUAL MODE, FAILSAFE OUTPUT—The controller will return to manual mode at the output value selected at Control prompt FAILSAFE.

TO AUTO—AUTOMATIC MODE, LAST SP—The controller will return to the automatic mode and the last setpoint used before shed.

SHED SETPOINT RECALL

Note: If SHEDENAB=DISABLE, this prompt will not be configurable.

TO LSP—Controller will use last local or remote setpoint used.

TO CSP—When in “slave” mode, the controller will store the last host computer setpoint and use it at the Local setpoint. When in “monitor” mode, the controller will shed to the last instrument Local or Remote setpoint used, and the LSP is unchanged.

COMPUTER SETPOINT UNITS

ENG — Engineering units

PERCENT — Percent of PV range

COMPUTER SETPOINT RATIO—Computer setpoint ratio.

COMPUTER SETPOINT BIAS—Computer setpoint bias in Engineering Units.

LOCAL LOOPBACK tests the RS-485 communications port. It is not used for any other communications port.

DISABLE—Disables the Loopback test.

ENABLE—Allows loopback test. The instrument goes into Loopback mode in which it sends and receives its own message. The instrument displays PASS or FAIL status in the upper display and LOOPBACK in the lower display while the test is running. The instrument will go into manual mode when LOOPBACK is enabled with the output at the Failsafe value. The test will run until the operator disables it here, or until power is turned off and on.

ATTENTION The instrument does not have to be connected to the external communications link in order to perform this test. If it is connected, only one instrument should run the loopback test at a time. The host computer should not be transmitting on the link while the loopback test is active.

58

UDC3200 Universal Digital Controller Operator Manual

04/08

Image 64
Contents UDC3200 Universal Digital Controller Operator Manual WARRANTY/REMEDY ContactsWorld Wide Web TelephoneSymbol Definitions Symbol DefinitionContents TROUBLESHOOTING/SERVICE Page Function of Displays and Keys Operator InterfaceFunction of Displays and Keys CE Conformity Europe Keys and FunctionsUDC3200 Universal Digital Controller Operator Manual Page Pre-installation Information Model Number InterpretationControl and Alarm Relay Contact Information Alarm RelaysAlarm Relay Contact Information Control RelaysMounting Overall DimensionsPhysical Considerations Mounting Method Step ActionWiring Wiring Diagrams Permissible Wiring BundlingBundle No Wire Functions Universal Output Functionality and RestrictionsINU Callout Wiring the ControllerDetails AC/DC Earth Ground HotLine Neutral Voltage L2/N Input #1 RTDInput #2 Input 2 ConnectionsTime Simplex Time DuplexL2/N Power Supply PowerPower Load Relay Load Relay Load10 Open Collector Output Time Duplex with a Dual Relay Board L2/N Relay LoadUDC3200 Universal Digital Controller Operator Manual 04/08 15 RS-422/485 Communications Option Connections 17 Auxiliary Output and Digital Inputs Option Connections Digital Inputs26 + 12 +Configuration Configuration Prompt HierarchyConfiguration Procedure ProcedureConfiguration Procedure IntroductionTuning Set Up Group Configuration is Complete RSET2MIN02 to RSET2RPM CYC SEC CYC SX3 CYC2 SEC CYC2 SX3 Security LockoutDisable Enable Auto MAN Disable Enable RUN HoldSP SEL SP Ramp Set Up Group Keyreset EU/HR DNSP Prog Strt SEG END SEGSEG2TIME SEG3RATESEG4 SP SEG4TIME SEG5RATE SEG6 SP SEG6TIMEFuzzy Disable Enable Accutune Tune Accutune Set Up GroupAT Error Algorithm Set Up Group ALG ON-OFFTimer ALG PD+MRStart KEY Alarm LOW Disp TI REM Time Period000 to INP ALG1Summer with Ratio and BIAS-The following formula Input High Select with Ratio and BIAS-This selectionInput LOW Select with Ratio and BIAS- This selection Multiplier Divider with Square Root -The followingFCC Math KCalc HI Calc LOALG1 INB ALG1 INCPCT CO ALG1 BiasOUT ALG Output Set Up GroupOUT RNG Rlystate RLY TypeMotor TI CUR OUTLOW VAL High VALInput 1 Set Up Group IN1 TypeXmitter IN1 LOWRatio Bias IN1EMISSIV1 Burnout None01 to IN2 Type Input 2 Set Up GroupXMITTER2 IN2 High IN2 LOWBias IN2 Burnout Burnout Protection Sensor BreakEMISSIV2 Control Set Up Group PV Source Input ALG1 PID SetsInput Input Algorithm PID Sets 2PV SWPWR Mode RSP SRC None Input ALG1 AutobiasSP Track PWR OUTAction OUT RatePCT/M UP PCT/M DNFailsafe Mode DeadbandFailmode MAN OUTRPM MinutesOptions Group AUX OUTAuxiliary Output Selection No Auxiliary OutputNo Digital Input Selections DIG INP1Was not previously started via To RUN DIG 1COMB DIG INP2DIG2COMB Digital Input 2 Selections Digital Input 2 CombinationsCommunications Group Shed SP UnitsCSP Rato CSP BiasAlarms Set Up Group High Alarm LOW AlarmA1S1 EV Beginning of SegmentA1S2 EV A2S1TYPEA2S1 EV A2S2TYPEALARM12 DiagnostDisplay Set Up Group Page Entering a Security Code Operator InterfaceKey error Procedure to Enter a Security CodeIndividual key lockout Annunciators Monitoring Your Controller 4.4.1 AnnunciatorsALM 1 OUT 1 DI 1 Or MAN None, F or C Viewing the operating parameters Lower Display Key Parameter PromptsDiagnostic Messages Diagnostic MessagesDescription Functional Overview Block Diagram of the UDC3200 Controller Tuning indicators Configuration checkAccutune Procedure for Starting Tune Tune for Simplex OutputsOperation Step Operation Press ResultConfiguration Check for Duplex Tune for Duplex Heat/CoolUsing Automatic Tune at start-up for Duplex Heat/Cool Using Blended Tune at start-up for Duplex Heat/Cool Using Manual Tune at start-up for Duplex Heat/CoolStep Operation Press Result Error Codes 10 Procedure for Accessing Accutune Error Codes11 Accutune Error Codes Aborting AccutuneFuzzy Overshoot Suppression ConfigurationHow it works Background Tests Background TestsEE Fail INP1 RNGRV Limit SegerrCAL MTR CurfailController Failure Symptoms Other symptomsSales and Service Page Http//hpsweb.honeywell.com