Honeywell UDC3200 High Alarm, LOW Alarm, A1S1 EV, Beginning of Segment, END of Segment, A1S2TYPE

Page 66

Function

Prompt

Lower Display

Selections or

Range of Setting

Upper Display

Parameter Definition

regardless of whichever SP is active.

NOTE 4. Loop Break monitors the control loop to determine if it is working. When enabled, the control output is checked against the minimum and maximum output limit settings. When the output reaches one of these limits, a timer begins. If the timer expires and the output has not caused the PV to move by a pre- determined amount, then the alarm activates, thus signalling that the loop is broken. The loop break timer value must be configured by the operator as the AxSx VAL entry. This value is in seconds with a range of 0 to 3600 seconds. A setting of 0 is equivalent to an instantaneous loop break when the output reaches one of its limit values.

The amount of PV Movement required is determined by the “UNITS” setting in the Display Setup Group. For the Degrees F configuration, the PV must move by 3° in the desired direction in the time allowed. For the Degrees C configuration, the PV must move by 2° in the desired direction in the time allowed. For the “NONE” selection, the PV must move 1% of the PV range in the time allowed.

Loop Break alarms do not have a HIGH/LOW State configuration, they are always assumed to be a HIGH state alarm.

NOTE 5. Thermocouple Warning means that the instrument has detected that the Thermocouple Input is starting to fail. Not valid for other input types.

NOTE 6. Thermocouple Failing means that the instrument has detected that the Thermocouple Input is in imminent danger of failing. Not valid for other input types.

NOTE 7: For the Digital Input selections, DIG INP1 can be either enabled or disabled in the Options Group (See Sub-Section3.11), but DIG INP2 must be enabled in the Options Group for the alarm to function properly.

 

 

If Setpoint Programming is disabled or if the Alarm Type is

 

 

not configured for Event On/Off:

A1S1 H L

 

ALARM 1 SETPOINT 1 STATE—Select whether you want the

 

alarm type chosen in prompt A1S1TYPE to alarm High or Low.

 

 

 

HIGH

HIGH ALARM

 

LOW

LOW ALARM

 

 

If Setpoint Programming is enabled and if the Alarm Type is

 

 

configured for Event On/Off:

A1S1 EV

 

ALARM 1 SEGMENT EVENT 1—Select whether you want the

 

 

alarm type chosen in prompt A1S1TYPE to alarm the beginning

 

 

or end of a segment in setpoint Ramp/Soak programming.

 

BEGIN

BEGINNING OF SEGMENT

 

END

END OF SEGMENT

 

 

 

 

Alarms configured for events will not operate on

 

 

 

ATTENTION

 

 

 

Setpoint Program segments of zero length.

 

 

 

A1S2TYPE

Same as A1S1

ALARM 1 SETPOINT 2 TYPE—Select what you want Setpoint 2

 

TYPE

of Alarm 1 to represent.

 

 

The selections are the same as A1S1TYPE.

 

 

 

 

A1S2 H L

HIGH

 

ALARM 1 SETPOINT 2 STATE—Same as A1S1 H L.

 

LOW

 

 

 

 

 

 

 

 

60

UDC3200 Universal Digital Controller Operator Manual

04/08

Image 66
Contents UDC3200 Universal Digital Controller Operator Manual World Wide Web WARRANTY/REMEDYContacts TelephoneSymbol Definitions Symbol DefinitionContents TROUBLESHOOTING/SERVICE Page Operator Interface Function of Displays and KeysFunction of Displays and Keys CE Conformity Europe Keys and FunctionsUDC3200 Universal Digital Controller Operator Manual Page Pre-installation Information Model Number InterpretationAlarm Relay Contact Information Control and Alarm Relay Contact InformationAlarm Relays Control RelaysOverall Dimensions MountingPhysical Considerations Mounting Method Step ActionWiring Bundle No Wire Functions Wiring DiagramsPermissible Wiring Bundling Universal Output Functionality and RestrictionsINU Wiring the Controller CalloutDetails Earth Ground Hot AC/DCLine Neutral Voltage L2/N Input #1 RTDInput #2 Input 2 ConnectionsTime Simplex Time DuplexPower Load Relay Load L2/N PowerSupply Power Relay Load10 Open Collector Output Time Duplex with a Dual Relay Board L2/N Relay LoadUDC3200 Universal Digital Controller Operator Manual 04/08 15 RS-422/485 Communications Option Connections 17 Auxiliary Output and Digital Inputs Option Connections Digital Inputs26 + 12 +Configuration Configuration Prompt HierarchyConfiguration Procedure Configuration ProcedureProcedure IntroductionTuning Set Up Group 02 to Configuration is CompleteRSET2MIN RSET2RPM CYC SEC CYC SX3 CYC2 SEC CYC2 SX3 Security LockoutAuto MAN Disable Enable RUN Hold Disable EnableSP SEL SP Ramp Set Up Group SP Prog KeyresetEU/HR DN Strt SEG END SEGSEG4 SP SEG4TIME SEG2TIMESEG3RATE SEG5RATE SEG6 SP SEG6TIMEAccutune Set Up Group Fuzzy Disable Enable Accutune TuneAT Error Algorithm Set Up Group ALG ON-OFFTimer ALG PD+MR000 to Start KEY Alarm LOW Disp TI REM TimePeriod INP ALG1Input LOW Select with Ratio and BIAS- This selection Summer with Ratio and BIAS-The following formulaInput High Select with Ratio and BIAS-This selection Multiplier Divider with Square Root -The followingCalc HI FCCMath K Calc LOPCT CO ALG1 INBALG1 INC ALG1 BiasOutput Set Up Group OUT ALGOUT RNG Rlystate RLY TypeLOW VAL Motor TICUR OUT High VALInput 1 Set Up Group IN1 TypeRatio XmitterIN1 LOW Bias IN1Burnout None EMISSIV101 to Input 2 Set Up Group IN2 TypeXMITTER2 Bias IN2 IN2 HighIN2 LOW Burnout Burnout Protection Sensor BreakEMISSIV2 Input Input Algorithm Control Set Up GroupPV Source Input ALG1 PID Sets PID Sets 2PV SWSP Track PWR ModeRSP SRC None Input ALG1 Autobias PWR OUTPCT/M UP ActionOUT Rate PCT/M DNFailmode Failsafe ModeDeadband MAN OUTRPM MinutesAuxiliary Output Selection Options GroupAUX OUT No Auxiliary OutputDIG INP1 No Digital Input SelectionsWas not previously started via To RUN DIG2COMB DIG 1COMBDIG INP2 Digital Input 2 Selections Digital Input 2 CombinationsCommunications Group CSP Rato Shed SPUnits CSP BiasAlarms Set Up Group A1S1 EV High AlarmLOW Alarm Beginning of SegmentA2S1 EV A1S2 EVA2S1TYPE A2S2TYPEALARM12 DiagnostDisplay Set Up Group Page Entering a Security Code Operator InterfaceProcedure to Enter a Security Code Key errorIndividual key lockout Monitoring Your Controller 4.4.1 Annunciators AnnunciatorsALM 1 OUT 1 DI 1 Or MAN None, F or C Viewing the operating parameters Lower Display Key Parameter PromptsDiagnostic Messages Diagnostic MessagesDescription Functional Overview Block Diagram of the UDC3200 Controller Configuration check Tuning indicatorsAccutune Operation Procedure for Starting TuneTune for Simplex Outputs Step Operation Press ResultConfiguration Check for Duplex Tune for Duplex Heat/CoolUsing Automatic Tune at start-up for Duplex Heat/Cool Using Blended Tune at start-up for Duplex Heat/Cool Using Manual Tune at start-up for Duplex Heat/CoolStep Operation Press Result 11 Accutune Error Codes Error Codes10 Procedure for Accessing Accutune Error Codes Aborting AccutuneConfiguration Fuzzy Overshoot SuppressionHow it works EE Fail Background TestsBackground Tests INP1 RNGCAL MTR RV LimitSegerr CurfailController Failure Symptoms Other symptomsSales and Service Page Http//hpsweb.honeywell.com