4.4.2 Viewing the operating parameters

Press the LOWER DISPLAY key to scroll through the operating parameters. The lower display will show only those parameters and their values that apply to your specific model.

Table 4-3 Lower Display Key Parameter Prompts

Lower Display

OUT XX.X

SP XXXX

2SP XXXX 3SP XXXX RSP XXXX 1IN XXXX 2IN XXXX POS XX CSP XXXX DEV XXXX PIDSET X ET HR.MN OTR HR.MN

RAMPXXXM

SPN XXXX

XXRAHR.MN

XXSKHR.MN

RECYC XX

To BEGIN

RERUN

AUX XXXX

BIA XXXX

TUNE OFF

DO FAST

DO SLOW

Description

OUTPUT—Output value is shown in percent with one decimal point for all output types except Three Position Step Control (TPSC). For TPSC, when no slidewire is connected, this display is an estimated motor position and is shown with no decimal point. For Position Proportional Control, if the slidewire fails, then the instrument automatically switches over to TPSC and the OUT display changes with it.

LOCAL SETPOINT #1—Also current setpoint when using SP Ramp.

LOCAL SETPOINT #2

LOCAL SETPOINT #3

REMOTE SETPOINT

INPUT 1—Used only with combinational input algorithms.

INPUT 2

SLIDEWIRE POSITION—Used only with TPSC applications that use a slidewire input. COMPUTER SETPOINT—When SP is in override.

DEVIATION—Maximum negative display is –999.9. TUNING PARAMETER —where X is either 1 or 2.

ELAPSED TIME—Time that has elapsed on the Timer in Hours.Minutes.

TIME REMAINING—Time remaining on the Timer in Hours.Minutes. The “O” is a rotating clock face.

SETPOINT RAMP TIME—Time remaining in the Setpoint Ramp in minutes.

SETPOINT NOW—Current Setpoint when SP Rate is enabled. The SP XXXX display shows the “target” or final setpoint value.

RAMP SEGMENT NUMBER AND TIME REMAINING—Set Point Programming display. XX is the current segment number and HR.MN is the time remaining for this segment in Hours.Minutes.

SOAK SEGMENT NUMBER AND TIME REMAINING— Set Point Programming display. XX is the current segment number and HR.MN is the time remaining for this segment in Hours.Minutes.

NUMBER OF SP PROGRAM RECYCLES REMAINING

RESET SP PROGRAM TO START OF FIRST SEGMENT RESET SP PROGRAM TO START OF CURRENT SEGMENT

AUXILIARY OUTPUT—Displayed only when output algorithm is not Current Duplex. BIAS—Displays the manual reset value for algorithm PD+MR.

LIMIT CYCLE TUNING NOT RUNNING—Appears when Accutune is enabled but not operating.

Limit Cycle Tuning with the objective of producing quarter-damped tuning parameters. This tuning may result in PV overshoot of the SP setting.

Limit Cycle Tuning with the objective of producing damped or Dahlin tuning parameters, depending upon the detected process deadtime. The tuning parameters calculated by this selection are aimed at reducing PV overshoot of the SP setting.

68

UDC3200 Universal Digital Controller Operator Manual

04/08

Image 74
Contents UDC3200 Universal Digital Controller Operator Manual World Wide Web WARRANTY/REMEDYContacts TelephoneSymbol Definitions Symbol DefinitionContents TROUBLESHOOTING/SERVICE Page Function of Displays and Keys Operator InterfaceFunction of Displays and Keys CE Conformity Europe Keys and FunctionsUDC3200 Universal Digital Controller Operator Manual Page Pre-installation Information Model Number InterpretationAlarm Relay Contact Information Control and Alarm Relay Contact InformationAlarm Relays Control RelaysPhysical Considerations Overall DimensionsMounting Mounting Method Step ActionWiring Bundle No Wire Functions Wiring DiagramsPermissible Wiring Bundling Universal Output Functionality and RestrictionsINU Details Wiring the ControllerCallout Line Neutral Voltage L2/N Earth Ground HotAC/DC Input #1 RTDInput #2 Input 2 ConnectionsTime Simplex Time DuplexPower Load Relay Load L2/N PowerSupply Power Relay Load10 Open Collector Output Time Duplex with a Dual Relay Board L2/N Relay LoadUDC3200 Universal Digital Controller Operator Manual 04/08 15 RS-422/485 Communications Option Connections 17 Auxiliary Output and Digital Inputs Option Connections Digital Inputs26 + 12 +Configuration Configuration Prompt HierarchyConfiguration Procedure Configuration ProcedureProcedure IntroductionTuning Set Up Group 02 to Configuration is CompleteRSET2MIN RSET2RPM CYC SEC CYC SX3 CYC2 SEC CYC2 SX3 Security LockoutSP SEL Auto MAN Disable Enable RUN HoldDisable Enable SP Ramp Set Up Group SP Prog KeyresetEU/HR DN Strt SEG END SEGSEG4 SP SEG4TIME SEG2TIMESEG3RATE SEG5RATE SEG6 SP SEG6TIMEAT Error Accutune Set Up GroupFuzzy Disable Enable Accutune Tune Algorithm Set Up Group ALG ON-OFFTimer ALG PD+MR000 to Start KEY Alarm LOW Disp TI REM TimePeriod INP ALG1Input LOW Select with Ratio and BIAS- This selection Summer with Ratio and BIAS-The following formulaInput High Select with Ratio and BIAS-This selection Multiplier Divider with Square Root -The followingCalc HI FCCMath K Calc LOPCT CO ALG1 INBALG1 INC ALG1 BiasOUT RNG Output Set Up GroupOUT ALG Rlystate RLY TypeLOW VAL Motor TICUR OUT High VALInput 1 Set Up Group IN1 TypeRatio XmitterIN1 LOW Bias IN101 to Burnout NoneEMISSIV1 XMITTER2 Input 2 Set Up GroupIN2 Type Bias IN2 IN2 HighIN2 LOW Burnout Burnout Protection Sensor BreakEMISSIV2 Input Input Algorithm Control Set Up GroupPV Source Input ALG1 PID Sets PID Sets 2PV SWSP Track PWR ModeRSP SRC None Input ALG1 Autobias PWR OUTPCT/M UP ActionOUT Rate PCT/M DNFailmode Failsafe ModeDeadband MAN OUTRPM MinutesAuxiliary Output Selection Options GroupAUX OUT No Auxiliary OutputWas not previously started via DIG INP1No Digital Input Selections To RUN DIG2COMB DIG 1COMBDIG INP2 Digital Input 2 Selections Digital Input 2 CombinationsCommunications Group CSP Rato Shed SPUnits CSP BiasAlarms Set Up Group A1S1 EV High AlarmLOW Alarm Beginning of SegmentA2S1 EV A1S2 EVA2S1TYPE A2S2TYPEALARM12 DiagnostDisplay Set Up Group Page Entering a Security Code Operator InterfaceIndividual key lockout Procedure to Enter a Security CodeKey error ALM 1 OUT 1 DI 1 Or MAN None, F or C Monitoring Your Controller 4.4.1 AnnunciatorsAnnunciators Viewing the operating parameters Lower Display Key Parameter PromptsDescription Diagnostic MessagesDiagnostic Messages Functional Overview Block Diagram of the UDC3200 Controller Accutune Configuration checkTuning indicators Operation Procedure for Starting TuneTune for Simplex Outputs Step Operation Press ResultConfiguration Check for Duplex Tune for Duplex Heat/CoolUsing Automatic Tune at start-up for Duplex Heat/Cool Using Blended Tune at start-up for Duplex Heat/Cool Using Manual Tune at start-up for Duplex Heat/CoolStep Operation Press Result 11 Accutune Error Codes Error Codes10 Procedure for Accessing Accutune Error Codes Aborting AccutuneHow it works ConfigurationFuzzy Overshoot Suppression EE Fail Background TestsBackground Tests INP1 RNGCAL MTR RV LimitSegerr CurfailController Failure Symptoms Other symptomsSales and Service Page Http//hpsweb.honeywell.com