4.5.3 Using AUTOMATIC TUNE at start-up for Duplex (Heat/Cool)

Used when DUPLEX has been configured for AUTOMATIC. This is the preferred selection for most Heat/Cool applications when tuning a new chamber. This selection will sequentially perform both Heat and Cool tuning without further operator intervention.

Table 4-6 Procedure for Using AUTOMATIC TUNE at Start-up for Duplex

Control

Step

Operation

 

Press

Result

1

Configure LSP1

 

 

 

Until SP (Local Setpoint 1) shows

 

Lower

 

 

 

 

Display

 

in the lower display.

 

 

 

 

 

2

 

 

or

 

Until LSP1 is a value within the

 

 

 

 

 

Heat Zone (output above 50%).

3

Configure LSP2

 

 

 

Until 2SP (Local Setpoint 2) shows

 

Lower

 

 

 

 

Display

 

in the lower display.

 

 

 

 

 

4

 

 

or

 

Until LSP2 is a value within the

 

 

 

 

 

Cool Zone (output below 50%).

5

Switch to

 

 

 

Until the “A” indicator is lighted (on

 

Man

 

 

“Automatic” Mode

 

Auto

 

controllers with Manual option).

 

 

 

 

 

6

Show Tuning

 

 

 

Until “TUNE OFF” is shown on

 

Lower

 

 

Prompt

 

Display

 

lower display.

 

 

 

 

 

7

Initiate Tuning

 

 

 

Select “DO SLOW” or “DO FAST”

 

 

 

 

 

in lower display.

 

Tuning in operation

 

 

 

Upper display will show a “T” as

 

 

Lower

 

 

 

 

Display

 

long as ACCUTUNE process is

 

 

 

 

 

operating. When process

 

 

 

 

 

completes, tuning parameters are

 

 

 

 

 

calculated and lower display will

 

 

 

 

 

show “NO TUNE” prompt.

74

UDC3200 Universal Digital Controller Operator Manual

04/08

Image 80
Contents UDC3200 Universal Digital Controller Operator Manual WARRANTY/REMEDY ContactsWorld Wide Web TelephoneSymbol Definitions Symbol DefinitionContents TROUBLESHOOTING/SERVICE Page Function of Displays and Keys Operator InterfaceFunction of Displays and Keys CE Conformity Europe Keys and FunctionsUDC3200 Universal Digital Controller Operator Manual Page Pre-installation Information Model Number InterpretationControl and Alarm Relay Contact Information Alarm RelaysAlarm Relay Contact Information Control RelaysPhysical Considerations Overall DimensionsMounting Mounting Method Step ActionWiring Wiring Diagrams Permissible Wiring BundlingBundle No Wire Functions Universal Output Functionality and RestrictionsINU Details Wiring the ControllerCallout Line Neutral Voltage L2/N Earth Ground HotAC/DC Input #1 RTDInput #2 Input 2 ConnectionsTime Simplex Time DuplexL2/N Power Supply PowerPower Load Relay Load Relay Load10 Open Collector Output Time Duplex with a Dual Relay Board L2/N Relay LoadUDC3200 Universal Digital Controller Operator Manual 04/08 15 RS-422/485 Communications Option Connections 17 Auxiliary Output and Digital Inputs Option Connections Digital Inputs26 + 12 +Configuration Configuration Prompt HierarchyConfiguration Procedure ProcedureConfiguration Procedure IntroductionTuning Set Up Group Configuration is Complete RSET2MIN02 to RSET2RPM CYC SEC CYC SX3 CYC2 SEC CYC2 SX3 Security LockoutSP SEL Auto MAN Disable Enable RUN HoldDisable Enable SP Ramp Set Up Group Keyreset EU/HR DNSP Prog Strt SEG END SEGSEG2TIME SEG3RATESEG4 SP SEG4TIME SEG5RATE SEG6 SP SEG6TIMEAT Error Accutune Set Up GroupFuzzy Disable Enable Accutune Tune Algorithm Set Up Group ALG ON-OFFTimer ALG PD+MRStart KEY Alarm LOW Disp TI REM Time Period000 to INP ALG1Summer with Ratio and BIAS-The following formula Input High Select with Ratio and BIAS-This selectionInput LOW Select with Ratio and BIAS- This selection Multiplier Divider with Square Root -The followingFCC Math KCalc HI Calc LOALG1 INB ALG1 INCPCT CO ALG1 BiasOUT RNG Output Set Up GroupOUT ALG Rlystate RLY TypeMotor TI CUR OUTLOW VAL High VALInput 1 Set Up Group IN1 TypeXmitter IN1 LOWRatio Bias IN101 to Burnout NoneEMISSIV1 XMITTER2 Input 2 Set Up GroupIN2 Type IN2 High IN2 LOWBias IN2 Burnout Burnout Protection Sensor BreakEMISSIV2 Control Set Up Group PV Source Input ALG1 PID SetsInput Input Algorithm PID Sets 2PV SWPWR Mode RSP SRC None Input ALG1 AutobiasSP Track PWR OUTAction OUT RatePCT/M UP PCT/M DNFailsafe Mode DeadbandFailmode MAN OUTRPM MinutesOptions Group AUX OUTAuxiliary Output Selection No Auxiliary OutputWas not previously started via DIG INP1No Digital Input Selections To RUN DIG 1COMB DIG INP2DIG2COMB Digital Input 2 Selections Digital Input 2 CombinationsCommunications Group Shed SP UnitsCSP Rato CSP BiasAlarms Set Up Group High Alarm LOW AlarmA1S1 EV Beginning of SegmentA1S2 EV A2S1TYPEA2S1 EV A2S2TYPEALARM12 DiagnostDisplay Set Up Group Page Entering a Security Code Operator InterfaceIndividual key lockout Procedure to Enter a Security CodeKey error ALM 1 OUT 1 DI 1 Or MAN None, F or C Monitoring Your Controller 4.4.1 AnnunciatorsAnnunciators Viewing the operating parameters Lower Display Key Parameter PromptsDescription Diagnostic MessagesDiagnostic Messages Functional Overview Block Diagram of the UDC3200 Controller Accutune Configuration checkTuning indicators Procedure for Starting Tune Tune for Simplex OutputsOperation Step Operation Press ResultConfiguration Check for Duplex Tune for Duplex Heat/CoolUsing Automatic Tune at start-up for Duplex Heat/Cool Using Blended Tune at start-up for Duplex Heat/Cool Using Manual Tune at start-up for Duplex Heat/CoolStep Operation Press Result Error Codes 10 Procedure for Accessing Accutune Error Codes11 Accutune Error Codes Aborting AccutuneHow it works ConfigurationFuzzy Overshoot Suppression Background Tests Background TestsEE Fail INP1 RNGRV Limit SegerrCAL MTR CurfailController Failure Symptoms Other symptomsSales and Service Page Http//hpsweb.honeywell.com