3.10 Control Set Up Group
Function | Selections or |
Prompt | Range of Setting |
Lower Display | Upper Display |
PV SOURCE |
|
| INPUT 1 |
| INPUT 2 |
| IN ALG1 |
|
|
PID SETS |
|
1 ONLY
2KEYBD
Lower
Display
Parameter Definition
PROCESS VARIABLE SOURCE
INPUT 1
INPUT 2
INPUT ALGORITHM 1
NUMBER OF TUNING PARAMETER
ONE SET
TWO SETS KEYBOARD
Press this key until you see PID SET1 or PID SET2 then press
orto switch between sets. Configure the values for: Gain, Rate, Reset, Cycle Time, Gain #2, Rate #2, Reset #2, Cycle #2 Time
PID SETS | 2PV SW |
(continued) |
|
2SP SW
SW VALUE Value in engineering units within PV or SP range limits
LSP’S
1 ONLY TWO
THREE
TWO SETS PV AUTOMATIC
TWO SETS SP AUTOMATIC
ATTENTION Other prompts affected: SW VALUE
AUTOMATIC SWITCHOVER
LOCAL SETPOINT
LOCAL
SP
between two local setpoints using the Select key.
THREE LOCAL
SP
between three local setpoints using the Select key
48 | UDC3200 Universal Digital Controller Operator Manual | 04/08 |