Honeywell UDC3200 Control Set Up Group, PV Source Input ALG1 PID Sets, Input Input Algorithm

Page 54

3.10 Control Set Up Group

Function

Selections or

Prompt

Range of Setting

Lower Display

Upper Display

PV SOURCE

 

 

INPUT 1

 

INPUT 2

 

IN ALG1

 

 

PID SETS

 

1 ONLY

2KEYBD

Lower

Display

Parameter Definition

PROCESS VARIABLE SOURCE —Selects the source of the Process Variable.

INPUT 1

INPUT 2

INPUT ALGORITHM 1

NUMBER OF TUNING PARAMETER SETS—This selection lets you choose one or two sets of tuning constants (gain, rate, and reset). NOTE: The Tuning Group is automatically configured to have two PID sets when a Duplex Control Algorithm is configured.

ONE SET ONLY—Only one set of tuning parameters is available. Configure the values for: Gain (proportional band), Rate, Reset Time, and Cycle Time (if time proportional is used).

TWO SETS KEYBOARD SELECTABLE—Two sets of tuning parameters can be configured and can be selected at the operator interface or by using the Digital Inputs.

Press this key until you see PID SET1 or PID SET2 then press

orto switch between sets. Configure the values for: Gain, Rate, Reset, Cycle Time, Gain #2, Rate #2, Reset #2, Cycle #2 Time

PID SETS

2PV SW

(continued)

 

2SP SW

SW VALUE Value in engineering units within PV or SP range limits

LSP’S

1 ONLY TWO

THREE

TWO SETS PV AUTOMATIC SWITCHOVER—When the process variable is GREATER than the value set at prompt SW VALUE (Switchover Value), the controller will use Gain, Rate, Reset, and Cycle Time. The active PID SET can be read in the lower display. When the process variable is LESS than the value set at prompt SW VALUE, the controller will use Gain#2, Rate#2, Reset#2, and Cycle#2 Time. The active PID SET can be read in the lower display.

TWO SETS SP AUTOMATIC SWITCHOVER—When the setpoint is GREATER than the value set at prompt SW VALUE (Switchover Value), the controller will use Gain, Rate, Reset, and Cycle. When the setpoint is LESS than the value set at prompt SW VALUE, the controller will use Gain #2, Rate #2, Reset #2, and Cycle #2.

ATTENTION Other prompts affected: SW VALUE

AUTOMATIC SWITCHOVER VALUE—This is the value of Process Variable or Setpoint at which the controller will switch from Tuning Constant Set #2 to Set #1.

LOCAL SETPOINT SOURCE—This selection determines what your local setpoint source will be.

LOCAL SETPOINT—The setpoint entered from the keyboard. TWO LOCAL SETPOINTS—This selection lets you switch

SP

between two local setpoints using the Select key.

THREE LOCAL SETPOINTS—This selection lets you switch

SP

between three local setpoints using the Select key

48

UDC3200 Universal Digital Controller Operator Manual

04/08

Image 54
Contents UDC3200 Universal Digital Controller Operator Manual World Wide Web WARRANTY/REMEDYContacts TelephoneSymbol Definitions Symbol DefinitionContents TROUBLESHOOTING/SERVICE Page Operator Interface Function of Displays and KeysFunction of Displays and Keys CE Conformity Europe Keys and FunctionsUDC3200 Universal Digital Controller Operator Manual Page Pre-installation Information Model Number InterpretationAlarm Relay Contact Information Control and Alarm Relay Contact InformationAlarm Relays Control RelaysOverall Dimensions MountingPhysical Considerations Mounting Method Step ActionWiring Bundle No Wire Functions Wiring DiagramsPermissible Wiring Bundling Universal Output Functionality and RestrictionsINU Wiring the Controller CalloutDetails Earth Ground Hot AC/DCLine Neutral Voltage L2/N Input #1 RTDInput #2 Input 2 ConnectionsTime Simplex Time DuplexPower Load Relay Load L2/N PowerSupply Power Relay Load10 Open Collector Output Time Duplex with a Dual Relay Board L2/N Relay LoadUDC3200 Universal Digital Controller Operator Manual 04/08 15 RS-422/485 Communications Option Connections 17 Auxiliary Output and Digital Inputs Option Connections Digital Inputs26 + 12 +Configuration Configuration Prompt HierarchyConfiguration Procedure Configuration ProcedureProcedure IntroductionTuning Set Up Group 02 to Configuration is CompleteRSET2MIN RSET2RPM CYC SEC CYC SX3 CYC2 SEC CYC2 SX3 Security LockoutAuto MAN Disable Enable RUN Hold Disable EnableSP SEL SP Ramp Set Up Group SP Prog KeyresetEU/HR DN Strt SEG END SEGSEG4 SP SEG4TIME SEG2TIMESEG3RATE SEG5RATE SEG6 SP SEG6TIMEAccutune Set Up Group Fuzzy Disable Enable Accutune TuneAT Error Algorithm Set Up Group ALG ON-OFFTimer ALG PD+MR000 to Start KEY Alarm LOW Disp TI REM TimePeriod INP ALG1Input LOW Select with Ratio and BIAS- This selection Summer with Ratio and BIAS-The following formulaInput High Select with Ratio and BIAS-This selection Multiplier Divider with Square Root -The followingCalc HI FCCMath K Calc LOPCT CO ALG1 INBALG1 INC ALG1 BiasOutput Set Up Group OUT ALGOUT RNG Rlystate RLY TypeLOW VAL Motor TICUR OUT High VALInput 1 Set Up Group IN1 TypeRatio XmitterIN1 LOW Bias IN1Burnout None EMISSIV101 to Input 2 Set Up Group IN2 Type XMITTER2 Bias IN2 IN2 HighIN2 LOW Burnout Burnout Protection Sensor BreakEMISSIV2 Input Input Algorithm Control Set Up GroupPV Source Input ALG1 PID Sets PID Sets 2PV SWSP Track PWR ModeRSP SRC None Input ALG1 Autobias PWR OUTPCT/M UP ActionOUT Rate PCT/M DNFailmode Failsafe ModeDeadband MAN OUTRPM MinutesAuxiliary Output Selection Options GroupAUX OUT No Auxiliary OutputDIG INP1 No Digital Input SelectionsWas not previously started via To RUN DIG2COMB DIG 1COMBDIG INP2 Digital Input 2 Selections Digital Input 2 CombinationsCommunications Group CSP Rato Shed SPUnits CSP BiasAlarms Set Up Group A1S1 EV High AlarmLOW Alarm Beginning of SegmentA2S1 EV A1S2 EVA2S1TYPE A2S2TYPEALARM12 DiagnostDisplay Set Up Group Page Entering a Security Code Operator InterfaceProcedure to Enter a Security Code Key errorIndividual key lockout Monitoring Your Controller 4.4.1 Annunciators AnnunciatorsALM 1 OUT 1 DI 1 Or MAN None, F or C Viewing the operating parameters Lower Display Key Parameter PromptsDiagnostic Messages Diagnostic MessagesDescription Functional Overview Block Diagram of the UDC3200 Controller Configuration check Tuning indicatorsAccutune Operation Procedure for Starting TuneTune for Simplex Outputs Step Operation Press ResultConfiguration Check for Duplex Tune for Duplex Heat/CoolUsing Automatic Tune at start-up for Duplex Heat/Cool Using Blended Tune at start-up for Duplex Heat/Cool Using Manual Tune at start-up for Duplex Heat/CoolStep Operation Press Result 11 Accutune Error Codes Error Codes10 Procedure for Accessing Accutune Error Codes Aborting AccutuneConfiguration Fuzzy Overshoot SuppressionHow it works EE Fail Background TestsBackground Tests INP1 RNGCAL MTR RV LimitSegerr CurfailController Failure Symptoms Other symptomsSales and Service Page Http//hpsweb.honeywell.com