4.4.3 Diagnostic Messages
The UDC3200 performs background tests to verify data and memory integrity. If there is a malfunction, a diagnostic message will be shown on the lower display. In the case of more than one simultaneous malfunction, only the highest priority diagnostic message will be displayed. Table
Prompt
EEFAIL FAILSAFE
INP1FAIL
INP2FAIL
SW FAIL
CONF ERR
SOOTING
IN1 RNG
IN2 RNG
PV LIMIT
FAILSAFE RV LIMIT
SEG ERR
CAL MTR SW FAIL TC1 WARN TC2 WARN TC1 FAIL TC2 FAIL OUT1FAIL OUT2FAIL
Table 4-4 Diagnostic Messages
Description
Unable to write to nonvolatile memory. A subsequent successful write to nonvolatile memory removes this message.
This error message appears whenever the controller goes into a failsafe mode of operation. Failsafe operation occurs when an analog input fails or when configuration is corrupted.
Two consecutive failures of input 1 integration or input value is outside of
Two consecutive failures of input 2 integration or input value is outside of
Slidewire input failure. Position Proportional Control automatically switched to Three Position Step Control.
Configuration
Carbon Potential
Input 1
Linear range: ± 10 %
Characterized range: ± 1 %
Input 2
PV beyond
Remote Variable beyond
Segment
Slidewire not calibrated. Perform Slidewire calibration. Position Proportional slidewire input failure.
The Thermocouple on Input 1 is starting to burnout.
The Thermocouple on Input 2 is starting to burnout.
Thermocouple on Input 1 is in imminent danger of burning out.
Thermocouple on Input 2 is in imminent danger of burning out.
Current Output is less than 3.5 mA.
Current Output 2 is less than 3.5 mA.