Schneider Electric 312 Drive default values, At first power on with a Profibus DP option card

Page 15

Configuration

Drive behaviour at first Power on with a PROFIBUS DP option card

At the first power on, the message (CFF) [Incorrect config.] appears on the product.

Press Enter to see [Restore config.] (FCS) menu.

Select the [Config. CFG] (InI) parameter to recover the factory settings.

For more information, see the [Restore config.] (FCS) parameter in ATV312 programming manual on www.schneider-electric.com

DANGER

UNINTENDED EQUIPMENT OPERATION

Check that the modification of the current configuration is compatible with the wiring diagram used.

Failure to follow these instructions will result in death or serious injury.

Drive default values

At first power on with a PROFIBUS DP option card

After a first power on, the following parameter settings are applied to the drive: [Ref.1 channel] (Fr1) = AIV1

[Ref.2 channel] (Fr2) = No [Summing ref. 2] (SA2) = AI2 [HMI command] (LCC) = No [4 preset speeds] (PS4) = No

[8 preset speeds] (PS8) = No

Power on after removing the PROFIBUS DP option card

If the PROFIBUS DP option card is removed and replaced by the orignal terminal board, the drive recovers the following default values: [CANopen address] (AdCO) = 0

[CANopen bit rate] (bdCO) = 125.0 [Ref.1 channel] (Fr1) = AI1

[Ref.2 channel] (Fr2) = No [HMI command] (LCC) = No [Select ATV31 conf.] (ArE) = No

S1A10386 10/2009

15

Image 15
Contents Altivar Page Contents Please Note Important InformationHazard of Electric SHOCK, EXPLOSION, or ARC Flash Before you beginDocumentation structure Formats IntroductionPresentation Drive terminal displaysHardware setup Installing the card in the driveReceipt Hardware setup Characteristics and functions of the terminals Terminal Function Electrical characteristicsTherefore the direction of operation Number Terminal Electrical characteristics Connection to the Modbus base portConnection to the Profibus DP network Example of connection Connection accessoriesWiring diagram for ATV 312 equipped with VW3 A312 Wire sizesRecommendations Configuration Address Switches 5-4-3-2-1Coding the drive address Drive default values At first power on with a Profibus DP option cardPower on after removing the Profibus DP option card Parameter Value Comment Control of the drive when LAC = L1 or L2Control of the drive when LAC = L3 Control of an ATV 312 from a Profibus DP option cardControl via Profibus DP in native profile CiA402 ST Red LED Status DiagnosticsDiagnostic LEDs DX Green LED StatusCode Name Probable cause Remedy Communication fault managementProfibus DP protocol Profibus DP mappingOutput PZDs Input PZDsPKW request PKW aperiodic service Output PKWsInput PKWs Examples of PKW aperiodic exchanges PL7 input word Altivar Configuration of the communicationProject configuration PL7 output word AltivarConfiguration of the slave Configuration with SyCON additional SoftwarePLC IO image / Altivar 312 DP slave mapping Save the projetPZD area Altivar TSX P57 354M TSX P57 354 M IO memory PKW areaExample of Control of the Drive Ready for switch onAnimated operator screen example Configuration of the device GSD installationS1A10386 10/2009 Altivar S7-315 PEW S7 315 PAW Parameter IO memory PLC IO image / Altivar 312 DP slave mappingPZD area PKW areaIEC 61800-7 status chart Supervision and control in Line modeOperation enabled Operational Not ready to switch on InitializationSwitch on disabled Configuration Ready to switch on and Switched on Drive initializedCMD control word W8501 MSK = ETA ETA status word W3201ATV312PROFIBUSDPS1A1038601 S1A10386 10/2009