Hardware setup

Recommendations

The user can select the data rate from a range of 9.6 kbps to 12 Mbps. This selection, made when starting up the network, applies to all the bus subscribers.

The maximum segment length is in inverse proportion to the data rate.

Data rate in kbps

9.6

19.2

45.45

93.75

187.5

500

1500

3000

6000

12000

 

 

 

 

 

 

 

 

 

 

 

Distance/segment in meters (feet)

1200

1200

1200

1200

1000

400

200

100

100

100

 

(3937)

(3937)

(3937)

(3937)

(3281)

(1312)

(656)

(328)

(328)

(328)

Repeaters can be used to cover greater distances.

The bus ends with a line terminator at each end of the segment.

Do not connect more than 32 stations per segment without a repeater, or more than 127 with a repeater.

Keep the bus away from the power cables (clearance of at least 30 cm (11.9 in).

If it is necessary for power cables to cross each other, be sure they cross at right angles.

Wiring diagram for ATV 312 equipped with VW3 A312 07

(1)Line choke, if used (single phase or 3-phase).

(2)Fault relay contacts, for remote indication of the drive status.

(3)If a braking resistor is connected, set [Dec ramp adapt.] (brA) parameter to [No] (nO) (refer to the progamming manual).

Note: Use interference suppressors on all inductive circuits near the drive or coupled to the same circuit (relays, contactors, solenoid valves, etc).

Wire sizes

ATV312 Control terminals

Applicable wire size (1)

Tightening torque (2)

 

mm² (AWG)

N·m (lb.in)

R2A, R2B, R2C

0.75 to 2.5 (18 to 14)

0.5 to 0.6 (4.4 to 5.3)

 

 

Other terminals

0.14 to 2.5 (26 to 16)

 

 

 

 

(1)The value in bold corresponds to the minimum wire gauge to permit secureness.

(2)Recommended to maximum value.

S1A10386 10/2009

13

Image 13
Contents Altivar Page Contents Please Note Important InformationHazard of Electric SHOCK, EXPLOSION, or ARC Flash Before you beginDocumentation structure Presentation IntroductionDrive terminal displays FormatsInstalling the card in the drive Hardware setupReceipt Hardware setup Terminal Function Electrical characteristics Characteristics and functions of the terminalsTherefore the direction of operation Connection to the Modbus base port Number Terminal Electrical characteristicsConnection to the Profibus DP network Example of connection Connection accessoriesWire sizes Wiring diagram for ATV 312 equipped with VW3 A312Recommendations Address Switches 5-4-3-2-1 ConfigurationCoding the drive address At first power on with a Profibus DP option card Drive default valuesPower on after removing the Profibus DP option card Control of the drive when LAC = L3 Control of the drive when LAC = L1 or L2Control of an ATV 312 from a Profibus DP option card Parameter Value CommentControl via Profibus DP in native profile CiA402 Diagnostic LEDs DiagnosticsDX Green LED Status ST Red LED StatusCode Name Probable cause Remedy Communication fault managementProfibus DP protocol Profibus DP mappingInput PZDs Output PZDsPKW request Output PKWs PKW aperiodic serviceInput PKWs Examples of PKW aperiodic exchanges Project configuration Configuration of the communicationPL7 output word Altivar PL7 input word AltivarConfiguration of the slave Configuration with SyCON additional SoftwareSave the projet PLC IO image / Altivar 312 DP slave mappingPZD area Altivar TSX P57 354M TSX P57 354 M IO memory PKW areaExample of Control of the Drive Ready for switch onAnimated operator screen example Configuration of the device GSD installationS1A10386 10/2009 PZD area PLC IO image / Altivar 312 DP slave mappingPKW area Altivar S7-315 PEW S7 315 PAW Parameter IO memoryIEC 61800-7 status chart Supervision and control in Line modeSwitch on disabled Configuration Not ready to switch on InitializationReady to switch on and Switched on Drive initialized Operation enabled OperationalCMD control word W8501 MSK = ETA ETA status word W3201ATV312PROFIBUSDPS1A1038601 S1A10386 10/2009