Schneider Electric 312 manual Output PZDs, Input PZDs, PKW request

Page 21

PROFIBUS DP mapping

Output PZDs

The first eight bytes contain an aperiodic request (PKW) to write or read a parameter. The remaining 4 bytes contain the output PZDs (written from the PROFIBUS DP master).

1

 

2

3

4

 

5

6

 

7

8

9

 

10

11

 

12

 

 

 

 

PKW

 

 

 

 

 

 

PZD1

 

 

PZD2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PKE

 

0

R/W

 

 

 

PWE

 

 

CMD

 

 

LFRD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PKW request

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PKE

Parameter logic address

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RIW

Request code:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0:No request

1:Read

2:Write

PWE

For a read request: Not used

 

For a write request: Parameter value

Cyclic control and adjustment parameters:

PZD1: Communication scanner output word 1 (NC1)

PZD2: Communication scanner output word 2 (NC2)

The default assignment of the periodic output data is:

PZD1 = Command word

PZD2 = Speed target

1

2

3

4

5

6

7

8

9

10

11

12

 

 

 

PKW

 

 

 

 

 

PZD1

 

PZD2

 

PKE

0

R/W

 

 

PWE

 

Command word

Speed target

Input PZDs

The first eight bytes contain the response (PKW) to the aperiodic read/write request.

The remaining 4 bytes contain the input PZDs (read mode).

1

 

2

3

 

4

 

5

6

 

7

8

9

 

10

11

 

12

 

 

 

 

 

PKW

 

 

 

 

 

PZD1

 

 

PZD2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PKE

 

0

 

R/W/N

 

 

 

PWE

 

ETA

 

 

RFRD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PKW request

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PKE

Parameter logic address

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R/W/N

Response code:

 

 

 

 

 

 

 

 

 

 

 

 

 

0:No request

1:Successful read report

2:Successful write report

7:Error report

PWE

For a successful request: Parameter value

 

For an incorrect request:

0:Incorrect address

1:Write access denied

Cyclic monitoring parameters:

PZD1: Communication scanner input word 1 (ETA)

PZD2: Communication scanner input word 2 (RFRD)

The default assignment of the periodic input data is:

PZD1 = Status word (ETA)

PZD2 = Output speed (RFRD)

1

2

3

4

5

6

7

8

9

10

11

12

 

 

 

PKW

 

 

 

 

 

PZD1

 

PZD2

 

PKE

0

R/W

 

 

PWE

 

Status word

Output speed

S1A10386 10/2009

21

Image 21
Contents Altivar Page Contents Please Note Important InformationHazard of Electric SHOCK, EXPLOSION, or ARC Flash Before you beginDocumentation structure Presentation IntroductionDrive terminal displays FormatsHardware setup Installing the card in the driveReceipt Hardware setup Characteristics and functions of the terminals Terminal Function Electrical characteristicsTherefore the direction of operation Number Terminal Electrical characteristics Connection to the Modbus base portConnection to the Profibus DP network Example of connection Connection accessoriesWiring diagram for ATV 312 equipped with VW3 A312 Wire sizesRecommendations Configuration Address Switches 5-4-3-2-1Coding the drive address Drive default values At first power on with a Profibus DP option cardPower on after removing the Profibus DP option card Control of the drive when LAC = L3 Control of the drive when LAC = L1 or L2Control of an ATV 312 from a Profibus DP option card Parameter Value CommentControl via Profibus DP in native profile CiA402 Diagnostic LEDs DiagnosticsDX Green LED Status ST Red LED StatusCode Name Probable cause Remedy Communication fault managementProfibus DP protocol Profibus DP mappingOutput PZDs Input PZDsPKW request PKW aperiodic service Output PKWsInput PKWs Examples of PKW aperiodic exchanges Project configuration Configuration of the communicationPL7 output word Altivar PL7 input word AltivarConfiguration of the slave Configuration with SyCON additional SoftwarePLC IO image / Altivar 312 DP slave mapping Save the projetPZD area Altivar TSX P57 354M TSX P57 354 M IO memory PKW areaExample of Control of the Drive Ready for switch onAnimated operator screen example Configuration of the device GSD installationS1A10386 10/2009 PZD area PLC IO image / Altivar 312 DP slave mappingPKW area Altivar S7-315 PEW S7 315 PAW Parameter IO memoryIEC 61800-7 status chart Supervision and control in Line modeSwitch on disabled Configuration Not ready to switch on InitializationReady to switch on and Switched on Drive initialized Operation enabled OperationalCMD control word W8501 MSK = ETA ETA status word W3201ATV312PROFIBUSDPS1A1038601 S1A10386 10/2009