Schneider Electric 312 manual Characteristics and functions of the terminals

Page 10

Hardware setup

Characteristics and functions of the terminals

Terminal

Function

Electrical characteristics

R2A

Configurable relay outputs:

• Minimum switching capacity: 10 mA for 5 V c

R2B

1 relay logic output, one “N/C”

• Maximum switching capacity on resistive load (cos ϕ = 1 and L/R = 0 ms):

R2C

contact and one “N/O” contact

5 A for 250 V a and 30 V c

 

with common point.

• Maximum switching capacity on inductive load (cos ϕ = 0.4 and L/R = 7 ms):

 

 

2 A for 250 V a and 30 V c

 

 

• Sampling time: 8 ms

 

 

• Service life: 100,000 operations at maximum switching power

COM

Analog I/O common

0 V

+10

Power supply for reference

• +10 V (+ 8% - 0%)

 

potentiometer (2.2 to 10 kΩ)

• 10 mA max

 

 

• Protected against short-circuits and overloads

AI2

Analog voltage input

Bipolar analog input 0 ± 10 V (maximum safe voltage ± 30 V)

 

 

The + or - polarity of the voltage on AI2 affects the direction of the setpoint and

 

 

therefore the direction of operation.

 

 

• Impedance: 30 kΩ

 

 

• Resolution: 0.01 V, 10-bit + sign converter

 

 

• Precision ± 4.3%, linearity ± 0.2%, of maximum value

 

 

• Sampling time: 8 ms

 

 

• Operation with shielded cable 100 m maximum

AI3

Analog current input

Analog current input X-Y mA by programming X and Y from 0 to 20 mA:

 

 

• Impedance: 250 Ω

+24

Logic input power supply

• + 24 V protected against short-circuits and overloads, minimum 19 V, maximum 30 V

 

 

• Maximum customer current available: 100 mA

LI1

Logic inputs

Programmable logic inputs

LI2

 

• Impedance: 3.5 kΩ

LI3

 

• + 24 V internal or 24 V external power supply (min. 19 V, max. 30 V)

 

 

• Max. current: 100 mA

 

 

• Max. sampling time: 4 ms

 

 

Source position: Positive logic State 0 if < 5 V or logic input not wired, state 1 if > 11 V

RJ45

Communication port

Connection for SoMove software, Modbus, remote display, loader tools.

SW1

Addressing switches

See page 14.

SW2

Line termination switches

See page 11.

PROFIBUS

Communication

PROFIBUS DP open style connector for connection to the fieldbus, see page 11.

DP

 

 

10

S1A10386 10/2009

Image 10
Contents Altivar Page Contents Important Information Please NoteBefore you begin Hazard of Electric SHOCK, EXPLOSION, or ARC FlashDocumentation structure Drive terminal displays IntroductionPresentation FormatsInstalling the card in the drive Hardware setupReceipt Hardware setup Terminal Function Electrical characteristics Characteristics and functions of the terminalsTherefore the direction of operation Connection to the Modbus base port Number Terminal Electrical characteristicsConnection to the Profibus DP network Connection accessories Example of connectionWire sizes Wiring diagram for ATV 312 equipped with VW3 A312Recommendations Address Switches 5-4-3-2-1 ConfigurationCoding the drive address At first power on with a Profibus DP option card Drive default valuesPower on after removing the Profibus DP option card Control of an ATV 312 from a Profibus DP option card Control of the drive when LAC = L1 or L2Control of the drive when LAC = L3 Parameter Value CommentControl via Profibus DP in native profile CiA402 DX Green LED Status DiagnosticsDiagnostic LEDs ST Red LED StatusCommunication fault management Code Name Probable cause RemedyProfibus DP mapping Profibus DP protocolInput PZDs Output PZDsPKW request Output PKWs PKW aperiodic serviceInput PKWs Examples of PKW aperiodic exchanges PL7 output word Altivar Configuration of the communicationProject configuration PL7 input word AltivarConfiguration with SyCON additional Software Configuration of the slaveSave the projet PLC IO image / Altivar 312 DP slave mappingPZD area PKW area Altivar TSX P57 354M TSX P57 354 M IO memoryReady for switch on Example of Control of the DriveAnimated operator screen example GSD installation Configuration of the deviceS1A10386 10/2009 PKW area PLC IO image / Altivar 312 DP slave mappingPZD area Altivar S7-315 PEW S7 315 PAW Parameter IO memorySupervision and control in Line mode IEC 61800-7 status chartReady to switch on and Switched on Drive initialized Not ready to switch on InitializationSwitch on disabled Configuration Operation enabled OperationalCMD control word W8501 ETA status word W3201 MSK = ETAATV312PROFIBUSDPS1A1038601 S1A10386 10/2009