Schneider Electric 312 manual Communication fault management, Code Name Probable cause Remedy

Page 19

Diagnostics

Communication fault management

The behaviour of the drive in case of communication interruption is described in the ATV312 programming manual.

The communication between the master (external management system) and the drive is broken:

In this case, the drive will generate a (CnF) error message.

The communication card is not working properly:

In this case, the drive will generate a (COF) message.

 

 

Code

 

Name

 

Probable cause

 

Remedy

 

 

 

 

 

 

 

 

 

 

 

CFF

 

[INCORRECT

• The current configuration is

Return to factory settings or retrieve the backup

 

 

 

 

 

CONFIG.]

 

inconsistent.

 

configuration, if it is valid. See the [Restore config.]

 

 

 

 

 

 

• Addition or removal of an option

 

(FCS) parameter in ATV312 programming manual.

 

 

 

CnF

 

[NETWORK

• Communication detected fault on the

Check the environment (electromagnetic

 

 

 

 

 

FAULT]

 

communication card

 

compatibility).

 

 

 

 

 

 

 

 

Check the wiring.

 

 

 

 

 

 

 

 

Check the time out.

 

 

 

 

 

 

 

 

Replace the option card.

 

 

 

 

 

 

 

 

• See the [CANopen fault mgt] (COL) parameter in the

 

 

 

 

 

 

 

 

 

ATV312 programming manual to define the stop

 

 

 

 

 

 

 

 

 

mode with a (CnF).

 

 

 

COF

 

[CANopen FAULT]

Interruption in communication

Check the communication bus.

 

 

 

 

 

 

 

between the option card and the

Check the option card.

 

 

 

 

 

 

 

drive

 

 

 

 

 

ILF

 

[INTERNAL LINK

Interruption in communication

Replace the option card.

 

 

 

 

 

FAULT]

 

between the option card and the

 

 

 

 

 

 

 

 

 

drive

 

 

 

 

 

 

 

 

 

 

 

 

 

(CnF) [Network fault]: Option card fault code

This parameter is read-only and is only visible if an option card is present. The fault code remains saved in the parameter, even if the cause disappears. The parameter is reset after the drive is disconnected and then reconnected.

The values of this parameter is:

1: Time out on the reception of the periodic variables addressed to the drive

For the full list of the fault detected codes, see ATV312 programming manual on www.schneider-electric.com

S1A10386 10/2009

19

Image 19
Contents Altivar Page Contents Please Note Important InformationHazard of Electric SHOCK, EXPLOSION, or ARC Flash Before you beginDocumentation structure Formats IntroductionPresentation Drive terminal displaysInstalling the card in the drive Hardware setupReceipt Hardware setup Terminal Function Electrical characteristics Characteristics and functions of the terminalsTherefore the direction of operation Connection to the Modbus base port Number Terminal Electrical characteristicsConnection to the Profibus DP network Example of connection Connection accessoriesWire sizes Wiring diagram for ATV 312 equipped with VW3 A312Recommendations Address Switches 5-4-3-2-1 ConfigurationCoding the drive address At first power on with a Profibus DP option card Drive default valuesPower on after removing the Profibus DP option card Parameter Value Comment Control of the drive when LAC = L1 or L2Control of the drive when LAC = L3 Control of an ATV 312 from a Profibus DP option cardControl via Profibus DP in native profile CiA402 ST Red LED Status DiagnosticsDiagnostic LEDs DX Green LED StatusCode Name Probable cause Remedy Communication fault managementProfibus DP protocol Profibus DP mappingInput PZDs Output PZDsPKW request Output PKWs PKW aperiodic serviceInput PKWs Examples of PKW aperiodic exchanges PL7 input word Altivar Configuration of the communicationProject configuration PL7 output word AltivarConfiguration of the slave Configuration with SyCON additional SoftwareSave the projet PLC IO image / Altivar 312 DP slave mappingPZD area Altivar TSX P57 354M TSX P57 354 M IO memory PKW areaExample of Control of the Drive Ready for switch onAnimated operator screen example Configuration of the device GSD installationS1A10386 10/2009 Altivar S7-315 PEW S7 315 PAW Parameter IO memory PLC IO image / Altivar 312 DP slave mappingPZD area PKW areaIEC 61800-7 status chart Supervision and control in Line modeOperation enabled Operational Not ready to switch on InitializationSwitch on disabled Configuration Ready to switch on and Switched on Drive initializedCMD control word W8501 MSK = ETA ETA status word W3201ATV312PROFIBUSDPS1A1038601 S1A10386 10/2009