Diagnostics

Diagnostic LEDs

DX LED

ST LED

DX Green LED Status

The PROFIBUS DP card has two LEDs, ST and DX, visible on the communication card.

The status of the PROFIBUS DP card is indicated by the ST (status) red LED.

The status of the PROFIBUS DP communication link is indicated by the DX (data exchange) green LED.

The table below gives the meaning of the various states of these two LEDs:

State

Meaning

Corrective actions in the event of malfunction

 

The card is in the "data exchange" state,

 

On

and error-free data exchange is taking place.

 

 

 

 

 

 

 

No communication on the bus,

Check the connection to the PROFIBUS DP bus, start up the PLC.

Off

no data is being exchanged.

 

 

 

 

 

 

ST Red LED Status

State

Meaning

Corrective actions in the event of malfunction

 

The card has been configured and its parameters

 

Off

set correctly by the master.

 

 

 

 

 

 

 

The card is in Idle state, waiting configuration from

Enter an address value between 2 and 125 using the switches on

flashing 0.5 s

the master.

the option card.

 

 

 

 

 

 

The card is waiting parameters or waiting

Check the connection to the PROFIBUS DP bus,

 

configuration.

start up the PLC and, if the drive has a communication card

flashing 0.1 s

 

detected fault (CnF), reset it.

 

 

 

 

The card is in (ILF) detected fault mode.

Check the connection between the PROFIBUS DP card and the

On

 

drive.

 

 

 

 

 

LED states

LED state

Visual description of the LED state

 

The LED is OFF

The LED is FLASHING

The LED is ON

18

S1A10386 10/2009

Image 18
Contents Altivar Page Contents Important Information Please NoteBefore you begin Hazard of Electric SHOCK, EXPLOSION, or ARC FlashDocumentation structure Drive terminal displays IntroductionPresentation FormatsHardware setup Installing the card in the driveReceipt Hardware setup Characteristics and functions of the terminals Terminal Function Electrical characteristicsTherefore the direction of operation Number Terminal Electrical characteristics Connection to the Modbus base portConnection to the Profibus DP network Connection accessories Example of connectionWiring diagram for ATV 312 equipped with VW3 A312 Wire sizesRecommendations Configuration Address Switches 5-4-3-2-1Coding the drive address Drive default values At first power on with a Profibus DP option cardPower on after removing the Profibus DP option card Control of an ATV 312 from a Profibus DP option card Control of the drive when LAC = L1 or L2Control of the drive when LAC = L3 Parameter Value CommentControl via Profibus DP in native profile CiA402 DX Green LED Status DiagnosticsDiagnostic LEDs ST Red LED StatusCommunication fault management Code Name Probable cause RemedyProfibus DP mapping Profibus DP protocolOutput PZDs Input PZDsPKW request PKW aperiodic service Output PKWsInput PKWs Examples of PKW aperiodic exchanges PL7 output word Altivar Configuration of the communicationProject configuration PL7 input word AltivarConfiguration with SyCON additional Software Configuration of the slavePLC IO image / Altivar 312 DP slave mapping Save the projetPZD area PKW area Altivar TSX P57 354M TSX P57 354 M IO memoryReady for switch on Example of Control of the DriveAnimated operator screen example GSD installation Configuration of the deviceS1A10386 10/2009 PKW area PLC IO image / Altivar 312 DP slave mappingPZD area Altivar S7-315 PEW S7 315 PAW Parameter IO memorySupervision and control in Line mode IEC 61800-7 status chartReady to switch on and Switched on Drive initialized Not ready to switch on InitializationSwitch on disabled Configuration Operation enabled OperationalCMD control word W8501 ETA status word W3201 MSK = ETAATV312PROFIBUSDPS1A1038601 S1A10386 10/2009