1734 POINT I/O Module/RSLogix 5000 Controller Tag Reference

C-7

 

 

Digital 2 POINT Output –

With Over Load Diagnostic

Status

1734-OV2E

2 POINT 10V…28V dc Electronically Fused Output, Sink

Configuration Data

Data Type

Default

Valid Data Values

 

 

Value

 

 

 

 

 

Fault Mode - POINT 0, 1

SINT, BIT

0

0=Fault Value

 

 

 

1=Hold Last State

 

 

 

 

Fault Value - POINT 0, 1

SINT, BIT

0

0=Off

 

 

 

1=On

 

 

 

 

Program Mode - POINT 0, 1

SINT, BIT

0

0=Program Value

 

 

 

1=Hold Last State

 

 

 

 

Program Value - POINT 0, 1

SINT, BIT

0

0=Off

 

 

 

1=On

 

 

 

 

Auto Restart Enable - POINT 0, 1

SINT, BIT

0

0=Latch Off

(Over Load Behavior)

 

 

1=Auto Retry

 

 

 

 

Fault Latch Enable - POINT 0, 1

SINT, BIT

0

0=No Latching

(Over Load)

 

 

1=Alarms Latch

 

 

 

 

 

 

 

 

Input Data

Data Type

Default

Valid Data Values

 

 

Value

 

 

 

 

 

Status Data - POINT 0, 1

SINT, BIT

0

0=Off

(Over Load)

 

 

1=On (Load Fault)

 

 

 

 

 

 

 

 

Output Data

Data Type

Default

Valid Data Values

 

 

Value

 

 

 

 

 

Output Data - POINT 0, 1

SINT, BIT

0

0=Off

 

 

 

1=On

 

 

 

 

Publication 1734-UM011C-EN-P - January 2006

Page 121
Image 121