C-38 1734 POINT I/O Module/RSLogix 5000 Controller Tag Reference
1734-232ASC
1 Channel ASCII Interface Module
Configuration Data | Data Type | Default | Valid Data Values |
|
| Value |
|
|
|
|
|
Transmit End Delimiter Mode | SINT | 2 | 0=No End Delimiter |
|
|
| 1=Exclude End Delimiter |
|
|
| 2=Include End Delimiter |
|
|
|
|
Transmit End Delimiter Character | SINT | 13 | Any Valid ASCII Character |
|
| (0x0d) | (Default is Carr. Return) |
|
|
|
|
Consume String Data Type | SINT | 1 | 0=Array |
|
|
| 1=Short String |
|
|
| 2=String |
|
|
|
|
Transmit Swap Mode | SINT | 0 | 0=Disabled |
|
|
| |
|
|
| |
|
|
| |
|
|
|
|
DeviceNet Record Header Mode | SINT | 0 | 0=Transmit Handshake |
|
|
| 1=Transmit Immediate |
|
|
|
|
Transmit Data / Receive Data / Delimiter / Pad Character
Note that 7 data bits allows ASCII Character data values of 0 to 127, which RSLogix 5000 software does support in the signed Short Integer data type SINT
Note that 8 data bits allows ASCII Character data values of 0 to 255.
To enter values from +128 to +255, use this conversion formula:
Desired Decimal Value - 256 = Entered Decimal Value. As an example, for an ASCII Character value of 128, 128 - 256 =