Chapter 4

Configure the Adapter for Direct Connection in RSLogix 5000 Software

What This Chapter Contains In this example, a ControlLogix controller communicates with POINT I/O modules via the 1734-AENT adapter using a direct connection.

The adapter makes a direct connection to each of the modules referenced by the data. The modules presented in this chapter use RSLogix 5000 software, version 11.

What You Do

See Page

 

Set Up the Hardware

4-1

 

 

 

 

Create the Example Application

4-2

 

 

 

 

Configure the I/O

4-4

 

 

 

 

Add the Local EtherNet/IP Bridge to the I/O Configuration

4-4

 

 

 

 

Add the POINT I/O Adapter to the I/O Configuration

4-7

 

 

 

 

Add the POINT I/O Modules to the I/O Configuration

4-10

 

 

 

 

Add the Relay Output Module

4-10

 

 

 

 

Add the Digital Output Module

4-13

 

 

 

 

Edit the Controller Tags

4-16

 

 

 

 

Create the Ladder Program

4-18

 

 

 

 

Download the Program to the Controller

4-18

 

 

 

 

Verify the Module Chassis Size

4-20

 

 

 

 

Configure the Adapter with Fixed IP Address

4-16

 

 

 

 

Recover From an Overloaded Adapter

4-24

 

 

 

 

 

 

 

Set Up the Hardware

ATTENTION

You must use series C POINT I/O modules with

the 1734-AENT adapter. Series A or B POINT I/O

 

 

 

 

 

 

 

 

 

modules will not work with this adapter.

 

 

 

 

 

 

 

 

 

 

 

 

In this example, a ControlLogix chassis contains the Logix5555 processor in slot 1 and a 1756-ENBT bridge module in slot 3.

Publication 1734-UM011C-EN-P - January 2006

Page 43
Image 43
Bradley Smoker 1734-AENT manual Set Up the Hardware, What You Do See