Quick Start

D-5

 

 

Configure 1734 POINT I/O Modules

For RSLogix 5000 software version 13 and earlier, configure your 1734 POINT I/O modules via the Controller Tags database, using the following steps. For RSLogix 5000 software, versions 15 or later, the preferred method for module configuration is to use the Module Properties dialog for each POINT I/O module, as described in the individual user manual for the module.

1.Double-click the Controller Tags in the project dialog.

Look at the bottom of the screen to make sure you are in the Monitor Tags tab.

We are going to assume there is an analog input module

1734-IE2V, which resides in slot 6. We configure Channel 0 of this module to operate over the range -10 to +10V dc.

2.Click the configuration tag remote_POINT_IO:3:C.

From here you can set the module’s configuration and alarms.

In this configuration dialog, you enter the values that would correspond to the desired range. The range type default value for a 1734-IE2V module is 2, which is equal to 0 to 10V dc.

3.Click the configuration tag for the module in slot 4, remote_POINT_IO:3:Ch0RangeType.

4.Check the value in the tag

remote_POINT_IO:3:C.Ch0RangeType.

Publication 1734-UM011C-EN-P - January 2006

Page 159
Image 159
Bradley Smoker 1734-AENT manual Configure 1734 Point I/O Modules