Publication 1734-UM011C-EN-P - January 2006
C-32 1734 POINT I/O Module/RSLogix 5000 Controller Tag Reference
Program Fault Note
Programming Fault Error bit - If an incomplete, incorrect, or
conflicting set of configuration parameters is sent to the module, the
Program Fault bit is asserted and an error code placed in the
Programming Error Code word (assembly 6816). The module will not
enter a normal operational state. Bit definitions (decimal) for the error
codes are:
10 An invalid assembly was chosen for poll consumption (0, 105,
or 106 are valid).
9 The decimal point position is outside of the acceptable range.
8 Counter 0 window ON & OFF values are equal and not zero OR
Counter 0 window ON & OFF value is greater than the Rollover.
7 A tie has been connected to an unprogrammed window.
6 A configuration was selected that requires the scalar and none
was programmed OR
Multiple scalars were selected.
5 The preset is out of range (Rollover).
4 A rollover of zero was programmed through PWM was not
selected OR
A rollover was programmed and PWM was selected OR
Rollover is out of range (>0x01000000).
3 A configuration requiring a time base was selected and no gate
interval was set OR
Gate interval is out of range (>200) OR
Product of time base and gate interval is greater than 3 seconds.
2 A time base was entered that is not a multiple of 10 OR
Time base is out of range (>3000, or 3 seconds).
1 ZF/BF/AF were selected and no filter was programmed OR
Multiple filters were selected.
0 A reserved configuration/mode was programmed.
1734-IJ
1 Channel 5V dc Encoder / Counter
1734-IK
1 Channel 15…24V dc Encoder / Counter
Output Data Data Type Default
Value Valid Data Values
Counter Control
Counter Reset
Counter Preset
Value Reset
(Stored / Accumulated Count)
SINT
BIT 0
BIT 1
BIT 2
0
0
0
0
0=Count Unchanged
1=Count Cleared
0=Count Unchanged
1=Count Set to Preset
0=Count Unchanged
1=Count Cleared