1734 POINT I/O Module/RSLogix 5000 Controller Tag Reference | |
|
|
1734-IT2
2 Channel Thermocouple Input, Isol.
Configuration Data | Data Type | Default | Valid Data Values |
|
| Value |
|
|
|
|
|
Temperature Mode Channel 0 | SINT | 1 | 0=mV/Custom Scale |
|
|
| 1=°C |
|
|
| 2=°F |
|
|
| 3=°K |
|
|
| 4=°R |
|
|
|
|
Cold Junction Enable Channel 0 | SINT | 1 | 0=Disabled |
|
|
| 1=Enabled |
|
|
|
|
Cold Junction Offset Channel 0 | INT | 0 | 0…7,000 (0.00…70.00) |
|
|
|
|
Low Engineering Channel 1 | INT | 0 | |
|
|
|
|
High Engineering Channel 1 | INT | 7,000 | |
|
|
|
|
Alarm Disable Channel 1 | SINT | 0 | 0=Alarms Enabled |
|
|
| 1=Alarms Disabled |
|
|
|
|
Limit Alarm Latch Channel 1 | SINT | 0 | 0=No Latching |
|
|
| 1=Alarms Latch |
|
|
|
|
Notch Filter Channel 1 | SINT | 1 | 0=50 Hz |
|
|
| 1=60 Hz |
|
|
| 2=100 Hz |
|
|
| 3=120 Hz |
|
|
| 4=200 Hz |
|
|
| 5=240 Hz |
|
|
| 6=300 Hz |
|
|
| 7=400 Hz |
|
|
| 8=480 Hz |
|
|
|
|
Sensor Type Channel 1 | SINT | 5 | 0=mV |
|
|
| 1=B |
|
|
| 2=C |
|
|
| 3=E |
|
|
| 4=J |
|
|
| 5=K |
|
|
| 6=N |
|
|
| 7=R |
|
|
| 8=S |
|
|
| 9=T |
|
|
|
|
Digital Filter Channel 1 | INT | 0 | 0…10,000 ms |
|
|
|
|
Low Alarm Limit Channel 1 | INT | ||
|
|
|
|
High Alarm Limit Channel 1 | INT | 32,767 | |
|
|
|
|
Low Low Alarm Limit Channel 1 | INT | ||
|
|
|
|
High High Alarm Limit Channel 1 | INT | 32,767 | |
|
|
|
|