Quick Start

D-7

 

 

If you downloaded the offline configuration into the module and then realize that you must modify any of the module’s configuration parameters, then the preferred way to make these changes online is to go to the Module Connection tab and inhibit the module, apply the changes, and then uninhibit the module. Doing this breaks the connection, causing the configuration information to be downloaded right after the connection is made.

IMPORTANT

Switching the controller from Program to Run mode does not change the module connection status and does not re-send module configuration data.

We highly recommend that you use the inhibit/uninhibit process and avoid power cycling.

6.Right-click the 1734-AENT adapter and select Properties.

7.Click the Connection tab.

You see the following message:

The module is faulted because, even though you set up the adapters POINT I/O chassis size to the actual number of the modules plus the adapter, the adapter still remembers the size of 1 (the factory default value) until you reset this size manually. This option is available only online.

8.Click the Chassis Size tab.

9.Click the Set Chassis Size in Module button and set the chassis size in the adapter.

Publication 1734-UM011C-EN-P - January 2006

Page 161