5-18Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software

You see the Download dialog.

Verify the Module Chassis Size

5.From the Download dialog, click Download. You see this RSLogix 5000 dialog.

6.Notice that the 1756-ENBT Bridge is now online.

7.If yellow triangles are present, see the following section.

You have now built the I/O tree in RSLogix 5000, and the RSLogix 5000 software used the chassis size from the 1734-AENT General tab. Now you need to download this new chassis size value into the 1734-AENT adapter hardware. This procedure synchronizes the chassis size value from the RSLogix 5000 software into the 1734-AENT hardware. You must be online to perform this procedure.

1.Verify that RSLogix 5000 software is online.

2.Right-click the 1734-AENT adapter under I/O Configuration in the Project dialog.

3.Select Properties.

4.Click the Connection tab.

Publication 1734-UM011C-EN-P - January 2006