1734-IE2V
2 Channel Analog Voltage Input
Configuration Data | Data Type | Default | Valid Data Values |
|
| Value |
|
|
|
|
|
Low Engineering Channel 0 | INT | 0 | |
|
|
|
|
High Engineering Channel 0 | INT | 10,000 | |
|
|
|
|
Digital Filter Channel 0 | INT | 0 | 0…10,000 ms |
|
|
|
|
Low Alarm Limit Channel 0 | INT | 500 | |
|
|
|
|
High Alarm Limit Channel 0 | INT | 9,500 | |
|
|
|
|
Low Low Alarm Limit Channel 0 | INT | 200 | |
|
|
|
|
High High Alarm Limit Channel 0 | INT | 9,800 | |
|
|
|
|
Range Type Channel 0 | SINT | 2 | |
|
|
| 2=0…10V |
|
|
|
|
Limit Alarm Latch Channel 0 | SINT | 0 | 0=No Latching |
|
|
| 1=Alarms Latch |
|
|
|
|
Alarm Disable Channel 0 | SINT | 0 | 0=Alarms Enabled |
|
|
| 1=Alarms Disabled |
|
|
|
|
Low Engineering Channel 1 | INT | 0 | |
|
|
|
|
High Engineering Channel 1 | INT | 10,000 | |
|
|
|
|
Digital Filter Channel 1 | INT | 0 | 0…10,000 ms |
|
|
|
|
Low Alarm Limit Channel 1 | INT | 500 | |
|
|
|
|
High Alarm Limit Channel 1 | INT | 9,500 | |
|
|
|
|
Low Low Alarm Limit Channel 1 | INT | 200 | |
|
|
|
|
High High Alarm Limit Channel 1 | INT | 9,800 | |
|
|
|
|
Range Type Channel 1 | SINT | 2 | |
|
|
| 2=0…10V |
|
|
|
|
Limit Alarm Latch Channel 1 | SINT | 0 | 0=No Latching |
|
|
| 1=Alarms Latch |
|
|
|
|
Alarm Disable Channel 1 | SINT | 0 | 0=Alarms Enabled |
|
|
| 1=Alarms Disabled |
|
|
|
|
Notch Filter (Channel 0 & 1) | SINT | 2 | 1=50 Hz |
|
|
| 2=60 Hz |
|
|
| 4=250 Hz |
|
|
| 6=500 Hz |
|
|
|
|
INT | 100 | 0…10,000 ms | |
|
|
|
|