1734 POINT I/O Module/RSLogix 5000 Controller Tag Reference

C-15

 

 

1734-IR2

2 Channel RTD Input

Configuration Data

Data Type

Default Value

Valid Data Values

 

 

 

 

Sensor Type Channel 1

SINT

1

0=Ohms

 

 

 

1=100 Pt α 385

 

 

 

2=200 Ω Pt α 385

 

 

 

5=100 Ω JPt α 3916

 

 

 

6=200 Ω JPt α 3916

 

 

 

9=10 Ω Cu α 427

 

 

 

10=120 Ω Ni α 672

 

 

 

11=100 Ω Ni α 618

 

 

 

12=120 Ω Ni α 618

 

 

 

 

Temperature Mode Channel 1

SINT

1

0=Custom Scale

 

 

 

1=°C

 

 

 

2=°F

 

 

 

3=°K

 

 

 

4=°R

 

 

 

 

Notch Filter (Channel 0 & 1)

SINT

1

0=50 Hz

 

 

 

1=60 Hz

 

 

 

2=100 Hz

 

 

 

3=120 Hz

 

 

 

4=200 Hz

 

 

 

5=240 Hz

 

 

 

6=300 Hz

 

 

 

7=400 Hz

 

 

 

8=480 Hz

 

 

 

 

 

 

 

 

Input Data

Data Type

Default Value

Valid Data Values

 

 

 

 

Data Channel 0

INT

0

-32,768…32,767

 

 

 

 

Data Channel 1

INT

0

-32,768…32,767

 

 

 

 

Status Byte Channel 0

SINT

0

Bit 0 Fault

 

 

 

Bit 1 Calibration

 

 

 

Bit 2 LowAlarm

 

 

 

Bit 3 HighAlarm

 

 

 

Bit 4 LowLowAlarm

 

 

 

Bit 5 HighHighAlarm

 

 

 

Bit 6 Underrange

 

 

 

Bit 7 Overrange

 

 

 

 

Status Byte Channel 1

SINT

0

Bit 0 Fault

 

 

 

Bit 1 Calibration

 

 

 

Bit 2 LowAlarm

 

 

 

Bit 3 HighAlarm

 

 

 

Bit 4 LowLowAlarm

 

 

 

Bit 5 HighHighAlarm

 

 

 

Bit 6 Underrange

 

 

 

Bit 7 Overrange

 

 

 

 

Output Data

Data Type

Default Value

Valid Data Values

 

 

 

 

None

 

 

 

 

 

 

 

Publication 1734-UM011C-EN-P - January 2006

Page 129
Image 129
Bradley Smoker 1734-AENT manual Input Data Data Type Default Value Valid Data Values