C-101734 POINT I/O Module/RSLogix 5000 Controller Tag Reference

Analog 2 Channel Input

1734-IE2C

2 Channel Analog Current Input

Configuration Data

Data Type

Default

Valid Data Values

 

 

Value

 

 

 

 

 

Low Engineering Channel 0

INT

3,277

-32,768…32,767

 

 

 

 

High Engineering Channel 0

INT

16,383

-32,768…32,767

 

 

 

 

Digital Filter Channel 0

INT

0

0…10,000 ms

 

 

 

 

Low Alarm Limit Channel 0

INT

3,113

-32,768…32,767

 

 

 

 

High Alarm Limit Channel 0

INT

16,547

-32,768…32,767

 

 

 

 

Low Low Alarm Limit Channel 0

INT

2,867

-32,768…32,767

 

 

 

 

High High Alarm Limit Channel 0

INT

16,793

-32,768…32,767

 

 

 

 

Range Type Channel 0

SINT

3

3=420 mA

 

 

 

8=0…20 mA

 

 

 

 

Limit Alarm Latch Channel 0

SINT

0

0=No Latching

 

 

 

1=Alarms Latch

 

 

 

 

Alarm Disable Channel 0

SINT

0

0=Alarms Enabled

 

 

 

1=Alarms Disabled

 

 

 

 

Low Engineering Channel 1

INT

3,277

-32,768…32,767

 

 

 

 

High Engineering Channel 1

INT

16,383

-32,768…32,767

 

 

 

 

Digital Filter Channel 1

INT

0

0…10,000 ms

 

 

 

 

Low Alarm Limit Channel 1

INT

3,113

-32,768…32,767

 

 

 

 

High Alarm Limit Channel 1

INT

16,547

-32,768…32,767

 

 

 

 

Low Low Alarm Limit Channel 1

INT

2,867

-32,768…32,767

 

 

 

 

High High Alarm Limit Channel 1

INT

16,793

-32,768…32,767

 

 

 

 

Range Type Channel 1

SINT

3

3=4-20 mA

 

 

 

8=0-20 mA

 

 

 

 

Limit Alarm Latch Channel 1

SINT

0

0=No Latching

 

 

 

1=Alarms Latch

 

 

 

 

Alarm Disable Channel 1

SINT

0

0=Alarms Enabled

 

 

 

1=Alarms Disabled

 

 

 

 

Notch Filter (Channel 0 & 1)

SINT

2

1=50 Hz

 

 

 

2=60 Hz

 

 

 

4=250 Hz

 

 

 

6=500 Hz

 

 

 

 

Real-time Sample (Channel 0 & 1)

INT

100

0…10,000 ms

 

 

 

 

Publication 1734-UM011C-EN-P - January 2006