1734 POINT I/O Module/RSLogix 5000 Controller Tag Reference | |
|
|
1734-SSI
1 Channel Synchronous Serial Interface
Input Data | Data Type | Default | Valid Data Values |
|
| Value |
|
|
|
|
|
Present Data | DINT | 0 | |
|
|
| (0…4,294,967,295) |
|
|
|
|
Latched Data | DINT | 0 | |
|
|
| (0…4,294,967,295) |
|
|
|
|
Status | INT | 0 | 0=Input is Off |
Input Status | BIT 0 |
| |
|
|
| 1=Input is On |
Run | BIT 1 |
| 0=Module is not Running |
|
|
| 1=Module is Running |
Decreasing Count | BIT 2 |
| 0=Count not Decreasing |
|
|
| 1=Count is Decreasing |
Increasing Count | BIT 3 |
| 0=Count not Increasing |
|
|
| 1=Count is Increasing |
Compare0 Reached | BIT 4 |
| 0=Compare not Reached |
Compare1 Reached | BIT 5 |
| 1=Compare was Reached |
Compare0 Status | BIT 6 |
| 0=Compare Off |
Compare1 Status | BIT 7 |
| 1=Compare On |
Power Fault | BIT 8 |
| 0=No 24Vdc Power Fault |
|
|
| 1=24Vdc Power Fault |
Configuration Fault | BIT 9 |
| 0=No FPGA Config Fault |
|
|
| 1=FPGA Config data bad |
Communication Fault | BIT 10 |
| 0=No FPGA Comm Fault |
|
|
| 1=FPGA Comm Fault |
Input Data Fault | BIT 11 |
| 0=No Input Data Fault |
|
|
| 1=Input Power Fault (short) |
Data Latched | BIT 12 |
| 0=Input Data Not Latched |
|
|
| 1=Input Data Latched |
|
|
|
|
Present / Latched Data
To interpret values from
Stored Data Tag Value + 4,294,967,296 = Actual Stored Data Tag Value.
As an example, for a read value of