1734 POINT I/O Module/RSLogix 5000 Controller Tag Reference | |
|
|
Digital 2 POINT Output –
Without Diagnostic Status
2 POINT 120V ac Output
2 POINT ac/dc Relay Output
2 POINT Relay Output N.O./N.C.
Configuration Data | Data Type | Default | Valid Data Values |
|
| Value |
|
|
|
|
|
Fault Mode - POINT 0, 1 | SINT, BIT | 0 | 0=Fault Value |
|
|
| 1=Hold Last State |
|
|
|
|
Fault Value - POINT 0, 1 | SINT, BIT | 0 | 0=Off |
|
|
| 1=On |
|
|
|
|
Program Mode - POINT 0, 1 | SINT, BIT | 0 | 0=Program Value |
|
|
| 1=Hold Last State |
|
|
|
|
Program Value - POINT 0, 1 | SINT, BIT | 0 | 0=Off |
|
|
| 1=On |
|
|
|
|
|
|
|
|
Input Data | Data Type | Default | Valid Data Values |
|
| Value |
|
|
|
|
|
None |
|
|
|
|
|
|
|
|
|
|
|
Output Data | Data Type | Default | Valid Data Values |
|
| Value |
|
|
|
|
|
Output Data - POINT 0, 1 | SINT, BIT | 0 | 0=Off |
|
|
| 1=On |
|
|
|
|