Bradley Smoker 1734-AENT manual =Output 0 Not Tied, =Output 1 Not Tied, =Count Unchanged

Models: 1734-AENT

1 170
Download 170 pages 3.68 Kb
Page 138
Image 138

C-241734 POINT I/O Module/RSLogix 5000 Controller Tag Reference

1734-VHSC24

1 Channel 15…24V dc Very High-speed Counter

1734-VHSC5

1 Channel 5V dc Very High-speed Counter

Configuration Data

Data Type

Default

Valid Data Values

 

 

Value

 

 

 

 

 

Scalar

SINT

0

Counter Config 5, 6, 8 only:

 

 

 

-128…+127 (0…255) Single Bit

 

 

 

only:

 

 

 

0, 1, 2, 4, 8, 16, 32, 64, -128

 

 

 

 

Output Ties 0

SINT

0

0=Output 0 Not Tied

Out 0 Window 1

BIT 0

 

Out 0 Window 2

BIT 1

 

1=Output 0 Tied to Window

Out 0 Window 3

BIT 2

 

Counter Config 3 (PWM):

Out 0 Window 4

BIT 3

 

Output 0 Window 1 PWM In

 

 

 

 

Output Ties 1

SINT

0

0=Output 1 Not Tied

Out 1 Window 1

BIT 0

 

Out 1 Window 2

BIT 1

 

1=Output 1 Tied to Window

Out 1 Window 3

BIT 2

 

Counter Config 3 (PWM):

Out 1 Window 4

BIT 3

 

Output 1 Window 1 PWM In

 

 

 

 

Rollover

DINT

16,777,215

1…16,777,216

 

 

 

 

Preset (< Rollover)

DINT

0

0…16,777,215

 

 

 

 

On Value 1

DINT

0

Counter Config 3, 5, 6, 7:

Off Value 1

DINT

0

0…16,777,215

On Value 2

DINT

0

Counter Config 0, 1, 2, 4:

Off Value 2

DINT

0

0 to Rollover Value

On Value 3

DINT

0

 

Off Value 3

DINT

0

 

On Value 4

DINT

0

 

Off Value 4

DINT

0

 

 

 

 

 

SS PWM Value

INT

0

0…9500

(<0 or >9500 =Hold Last State)

 

 

(0.00…95.00%)

 

 

 

 

SS Counter Control

SINT

0

 

SS Counter Reset

BIT 0

 

0=Count Unchanged

 

 

 

1=Count Cleared

SS Counter Preset

BIT 1

 

0=Count Unchanged

 

 

 

1=Count Set to Preset

SS Value Reset

BIT 2

 

0=Count Unchanged

(Stored / Accum. Count)

 

 

1=Count Cleared

 

 

 

 

Publication 1734-UM011C-EN-P - January 2006

Page 138
Image 138