1734 POINT I/O Module/RSLogix 5000 Controller Tag Reference

C-23

 

 

Specialty I/O

1734-VHSC24

1 Channel 15…24V dc Very High-speed Counter

1734-VHSC5

1 Channel 5V dc Very High-speed Counter

Configuration Data

Data Type

Default

Valid Data Values

 

 

Value

 

 

 

 

 

Counter Config

SINT

0

 

Config_0

BIT 0

 

0000=0=Counter

Config_1

BIT 1

 

0001=1=Encoder X1

Config_2

BIT 2

 

0010=2=Encoder X2

Config_3

BIT 3

 

0011=3=PWM

 

 

 

0100=4=Encoder X4

 

 

 

0101=5=Period/Rate

 

 

 

0110=6=Continuous/Rate

 

 

 

0111=7=Rate Measurement

 

 

 

1000=8=Pulse Generator

Mode_4

BIT 4

 

000=Store Count Disable

Mode_5

BIT 5

 

001=Store/Continue

Mode_6

BIT 6

 

010=Store/Wait/Resume

 

 

 

011=Store,Reset/Wait/Start

 

 

 

100=Store,Reset/Start

Z Input

BIT 7

 

0=Z Input Not Inverted

 

 

 

1=Z Input Is Inverted

 

 

 

 

Filter

SINT

120

 

Filter_0

BIT 0

(0x78H)

0000=No Filter

Filter_1

BIT 1

 

0001=50 kHz

Filter_2

BIT 2

 

0010=5 kHz

Filter_3

BIT 3

 

0100=500 Hz

 

 

 

1000=50 Hz

FilterA

BIT 4

 

0=Input A/B/Z Not Filtered

FilterB

BIT 5

 

1=Input A/B/Z Is Filtered

FilterZ

BIT 6

 

 

 

 

 

 

Decimal Position

SINT

0

Counter Config 0, 1, 2, 3, 4:

 

 

 

-128…+127 (0…255)

 

 

 

Counter Config 5, 6, & 7:

 

 

 

-4…+2

 

 

 

 

Time Base

INT

0

Counter Config 3 & 7 only:

(in 10 ms intervals)

 

 

0…3000 ms (10 ms…3 sec)

 

 

 

 

Gate Interval

SINT

0

Counter Config 3 & 7 only:

(Product of Time Base x Gate

 

 

-128…+127 (0…200)

Interval must be 3000 ms)

 

 

 

 

 

 

 

Publication 1734-UM011C-EN-P - January 2006