1734 POINT I/O Module/RSLogix 5000 Controller Tag Reference

C-29

 

 

1734-IJ

1 Channel 5V dc Encoder / Counter

1734-IK

1 Channel 15…24V dc Encoder / Counter

Configuration Data

Data Type

Default

Valid Data Values

 

 

Value

 

 

 

 

 

Counter Config

SINT

0

0000=0=Counter

Config_0

BIT 0

 

Config_1

BIT 1

 

0001=1=Encoder X1

Config_2

BIT 2

 

0010=2=Encoder X2

Config_3

BIT 3

 

0100=4=Encoder X4

 

 

 

0101=5=Period/Rate

 

 

 

0111=7=Rate Measurement

Mode_4

BIT 4

 

000=Store Count Disable

Mode_5

BIT 5

 

001=Store/Continue

Mode_6

BIT 6

 

010=Store/Wait/Resume

 

 

 

011=Store,Reset/Wait/Start

 

 

 

100=Store,Reset/Start

Z Input

BIT 7

 

0=Z Input Not Inverted

 

 

 

1=Z Input Is Inverted

 

 

 

 

Filter

SINT

120

 

Filter_0

BIT 0

(0x78H)

0000=No Filter

Filter_1

BIT 1

 

0001=50 kHz

Filter_2

BIT 2

 

0010=5 kHz

Filter_3

BIT 3

 

0100=500 Hz

 

 

 

1000=50 Hz

FilterA

BIT 4

 

0=Input A/B/Z Not Filtered

FilterB

BIT 5

 

1=Input A/B/Z Is Filtered

FilterZ

BIT 6

 

 

 

 

 

 

Decimal Position

SINT

0

Counter Config 0, 1, 2, 4:

 

 

 

-128…+127 (0…255)

 

 

 

Counter Config 5 & 7:

 

 

 

-4…+2

 

 

 

 

Time Base

INT

0

Counter Config 7 only:

(in 10 ms intervals)

 

 

0…3000 ms (10 ms…3 s)

 

 

 

 

Gate Interval

SINT

0

Counter Config 7 only:

(Product of Time Base x Gate Interval

 

 

-128…+127 (0…200)

must be 3000 ms)

 

 

 

 

 

 

 

Scalar

SINT

0

Counter Config 5 only:

 

 

 

-128…+127 (0…255)

 

 

 

0, 1, 2, 4, 8, 16, 32, 64, -128

 

 

 

 

Rollover

DINT

16,777,215

1…16,777,216

 

 

 

 

Preset (< Rollover)

DINT

0

0…16,777,215

 

 

 

 

Publication 1734-UM011C-EN-P - January 2006