Bradley Smoker 1734-AENT manual Analog 2 Channel Output, 1734-OE2C

Models: 1734-AENT

1 170
Download 170 pages 3.68 Kb
Page 133
Image 133

1734 POINT I/O Module/RSLogix 5000 Controller Tag Reference

C-19

 

 

Analog 2 Channel Output

1734-OE2C

2 Channel Analog Current Output

Configuration Data

Data Type

Default

Valid Data Values

 

 

Value

 

 

 

 

 

Fault Value Channel 0

INT

0

-32,768…32,767

 

 

 

 

Program Value Channel 0

INT

0

-32,768…32,767

 

 

 

 

Low Engineering Channel 0

INT

1,638

-32,768…32,767

 

 

 

 

High Engineering Channel 0

INT

8,191

-32,768…32,767

 

 

 

 

Low Limit Channel 0

INT

-32,768

-32,768…32,767

 

 

 

 

High Limit Channel 0

INT

32,767

-32,768…32,767

 

 

 

 

Range Type Channel 0

SINT

0

0=420 mA

 

 

 

2=0…20 mA

 

 

 

 

Fault Mode Channel 0

SINT

1

0=Hold Last State

 

 

 

1=Go to Low Clamp

 

 

 

2=Go to High Clamp

 

 

 

3=Go to Fault Value

 

 

 

 

Idle Mode Channel 0

SINT

1

0=Hold Last State

 

 

 

1=Go to Low Clamp

 

 

 

2=Go to High Clamp

 

 

 

3=Go to Fault Value

 

 

 

 

Limit Alarm Latch Channel 0

SINT

0

0=No Latching

 

 

 

1=Alarms Latch

 

 

 

 

Alarm Disable Channel 0

SINT

0

0=Alarms Enabled

 

 

 

1=Alarms Disabled

 

 

 

 

Fault Value Channel 1

INT

0

-32,768…32,767

 

 

 

 

Program Value Channel 1

INT

0

-32,768…32,767

 

 

 

 

Low Engineering Channel 1

INT

1,638

-32,768…32,767

 

 

 

 

High Engineering Channel 1

INT

8,191

-32,768…32,767

 

 

 

 

Low Limit Channel 1

INT

-32,768

-32,768…32,767

 

 

 

 

High Limit Channel 1

INT

32,767

-32,768…32,767

 

 

 

 

Range Type Channel 1

SINT

0

0=420 mA

 

 

 

2=0…20 mA

 

 

 

 

Fault Mode Channel 1

SINT

1

0=Hold Last State

 

 

 

1=Go to Low Clamp

 

 

 

2=Go to High Clamp

 

 

 

3=Go to Fault Value

 

 

 

 

Publication 1734-UM011C-EN-P - January 2006