1734 POINT I/O Module/RSLogix 5000 Controller Tag Reference | |
|
|
Digital 4 POINT Output –
With Over Load Diagnostic
Status
1734-OV4E
4 POINT 10V…28V dc Electronically Fused Output, Sink
Configuration Data | Data Type | Default | Valid Data Values |
|
| Value |
|
|
|
|
|
Fault Mode - POINT 0, 1, 2, 3 | SINT, BIT | 0 | 0=Fault Value |
|
|
| 1=Hold Last State |
|
|
|
|
Fault Value - POINT 0, 1, 2, 3 | SINT, BIT | 0 | 0=Off |
|
|
| 1=On |
|
|
|
|
Program Mode - POINT 0, 1, 2, 3 | SINT, BIT | 0 | 0=Program Value |
|
|
| 1=Hold Last State |
|
|
|
|
Program Value - POINT 0, 1, 2, 3 | SINT, BIT | 0 | 0=Off |
|
|
| 1=On |
|
|
|
|
Auto Restart Enable - POINT 0, 1, 2, 3 | SINT, BIT | 0 | 0=Latch Off |
(Over Load Behavior) |
|
| 1=Auto Retry |
|
|
|
|
Fault Latch Enable - POINT 0, 1, 2, 3 | SINT, BIT | 0 | 0=No Latching |
(Over Load) |
|
| 1=Alarms Latch |
|
|
|
|
Input Data | Data Type | Default | Valid Data Values |
|
| Value |
|
|
|
|
|
Status Data - POINT 0, 1, 2, 3 | SINT, BIT | 0 | 0=Off |
(Over Load) |
|
| 1=On (Load Fault) |
|
|
|
|
|
|
|
|
Output Data | Data Type | Default | Valid Data Values |
|
| Value |
|
|
|
|
|
Output Data - POINT 0, 1, 2, 3 | SINT, BIT | 0 | 0=Off |
|
|
| 1=On |
|
|
|
|