C-281734 POINT I/O Module/RSLogix 5000 Controller Tag Reference

1734-VHSC24

1 Channel 15…24V dc Very High-speed Counter

1734-VHSC5

1 Channel 5V dc Very High-speed Counter

Output Data

Data Type

Default

Valid Data Values

 

 

Value

 

 

 

 

 

PWM Value

INT

0

0…9500

 

 

 

(0.00…95.00%)

 

 

 

 

Counter Control

SINT

0

 

Counter Reset

BIT 0

0

0=Count Unchanged

 

 

 

1=Count Cleared

Counter Preset

BIT 1

0

0=Count Unchanged

 

 

 

1=Count Set to Preset

Value Reset

BIT 2

0

0=Count Unchanged

(Stored / Accumulated Count)

 

 

1=Count Cleared

 

 

 

 

Output Control

SINT

0

 

Output 0 Force

BIT 0

0

0=Output Off

 

 

 

1=Output Forced On

Output 0 Enable

BIT 1

0

0=Output Disabled

 

 

 

1=Output Enabled

Output 0 Electronic Fuse

BIT 2

0

0=Auto Retry

 

 

 

1=Latch Off

Output 0 Diagnostic Speed

BIT 3

0

0< 8 ms Response

 

 

 

1=50 ms Response

Output 1 Force

BIT 4

0

0=Output Off

 

 

 

1=Output Forced On

Output 1 Enable

BIT 5

0

0=Output Disabled

 

 

 

1=Output Enabled

Output 1 Electronic Fuse

BIT 6

 

0=Auto Retry

 

 

0

1=Latch Off

Output 1 Diagnostic Speed

BIT 7

0

0< 8 ms Response

 

 

 

1=50 ms Response

 

 

 

 

Publication 1734-UM011C-EN-P - January 2006