C-41734 POINT I/O Module/RSLogix 5000 Controller Tag Reference

Digital 4 POINT Input

1734-IB4

4 POINT 10…28V dc Input, Sink

1734-IV4

4 POINT 10…28V dc Input, Source

Configuration Data

Data Type

Default

Valid Data Values

 

 

Value

 

 

 

 

 

Filter Off On Time - POINT 0

INT

1,000

-32,768…32,767 s(1)

 

 

 

(0…65,535)

 

 

 

 

Filter On Off Time - POINT 0

INT

1,000

-32,768…32,767 s(1)

 

 

 

(0…65,535)

 

 

 

 

Filter Off On Time - POINT 1

INT

1,000

-32,768…32,767 s(1)

 

 

 

(0…65,535)

 

 

 

 

Filter On Off Time - POINT 1

INT

1,000

-32,768…32,767 s(1)

 

 

 

(0…65,535)

 

 

 

 

Filter Off On Time - POINT 2

INT

1,000

-32,768…32,767 s(1)

 

 

 

(0…65,535)

 

 

 

 

Filter On Off Time - POINT 2

INT

1,000

-32,768…32,767 s(1)

 

 

 

(0…65,535)

 

 

 

 

Filter Off On Time - POINT 3

INT

1,000

-32,768…32,767 s (1)

 

 

 

(0…65,535)

 

 

 

 

Filter On Off Time - POINT 3

INT

1,000

-32,768…32,767 s (1)

 

 

 

(0… 65,535)

 

 

 

 

 

 

 

 

Input Data

Data Type

Default

Valid Data Values

 

 

Value

 

 

 

 

 

Input Data - POINT 0, 1, 2, 3

SINT, BIT

0

0=Off

 

 

 

1=On

 

 

 

 

 

 

 

 

Output Data

Data Type

Default

Valid Data Values

 

 

Value

 

 

 

 

 

None

 

 

 

 

 

 

 

(1)POINT I/O Modules support the Unsigned Integer data type UINT (0 to 65,535 range).

RSLogix 5000 software supports the signed Integer data type INT

(-32,768 to +32,767 range).

To enter Filter values from +32,768 to +65,535 s, use this conversion

formula:

Desired Filter Value (in s) - 65536 = Entered Filter Value (in s). As an example, for a 40 ms filter time, 40000 - 65536 = -25536

Publication 1734-UM011C-EN-P - January 2006

Page 118
Image 118
Bradley Smoker 1734-AENT manual Digital 4 Point Input, 1734-IB4, 1734-IV4