D-6Quick Start

It is set to 2, which is the default value. There are two settings that this module supports:

2 = 0 to 10V dc

0 = -10 to +10V dc

5.Click the value 2 and change it to 0, which changes the voltage range to -10 to +10V dc for channel 0.

Note the following:

The controller sends the configuration data only when connection is being established.

Should you need to modify any of the tag values once you change the tag, you need to access the updated information and download it into the module. These are the ways to download the updated configuration information into the module.

Ideally, you enter the correct code number in the Range Type field at the same time that you add the I/O to the I/O Configuration tree. You then download later.

Publication 1734-UM011C-EN-P - January 2006