Bosch Appliances D9112 On-Board Points, Description Terminals 11 to, Point Sensor Loops

Page 33

On-Board Points

Description

Terminals

11 to

22

The D9112 panel provides eight on-board points. Each point functions independently and does not interfere with the operation of the others. The panel monitors the sensor loops for normal, shorted, or open conditions between an input terminal (11, 13, 14, 16, 17, 19, 20, or 22) and any of the point common terminals (12, 15, 18, and 21). Programming for the point determines how the panel responds to those conditions. See the D9112 Program Entry Guide (74-06145-000)for point programming options.

Point Sensor Loops

When wiring the on-board points, install a 1k ý resistor at the far end of the sensor loop to provide a reference for supervision. You can connect dry contact sensing devices in series (normally-closed) and/or in parallel (normally-open) to any of these loops.

The number normally-open and/or normally-closed detection devices each sensor loop can supervise is limited only by the resistance on the loop. Resistance on each sensor loop must be less than 100ý with the detection devices connected.

Ground shunts cause missed alarms: The possibility of “ground shunts” increases significantly if you don’t install the resistor at the end of the line. If you install the resistor for points 1 to 8 before a detection device on the sensor loop and the loop becomes grounded after the resistor, any devices beyond the ground are “ground shunted”. Alarm or trouble conditions beyond the ground are not seen by the panel.

POINT INPUT

TERMINAL

COMMON

NORMALLY CLOSED CONTACTS

POINT INPUT

TERMINAL

COMMON

NORMALLY OPEN CONTACTS

POINT INPUT

TERMINAL

COMMON

COMBINATION: NORMALLY OPEN AND NORMALLY CLOSED CONTACTS

1K Ω

BROWN RED BLACK

RADIONICS MODEL D105F OR D105BL (UL

LISTED BURGLAR APPLICATIONS) END-OF-LINE RESISTOR

Figure 11: On-board Point Sensor Loop Wiring

 

D9112

Operation & Installation Manual

 

 

© 1993 Radionics

74-06144-000-C 2/96

Page 33

Image 33
Contents D I O N I C S Part FCC Notices74-06144-000-C 2/96 Table of Contents Installation Guide for UL and Fire Applications Programmer and Accessory ConnectionsCurrent Rating Chart for Standby Battery Calculation forFigures and Tables D8128A OctoPOPIT Switch SettingsPoints IntroductionKeyswitch D1255 Alpha III Command CenterAreas and Accounts CommunicatorEvent Log Event MemoryEMI/Lightning Transient Protection ProgrammingOther Features D9112 Assembly D9112 Control/Communicator AssemblyOrdered Separately Literature PackFire Listings and ApprovalsBurglary Factory Mutual FMBeginning the Installation InstallationBefore You Begin Enclosure OptionsConnecting Earth Ground Terminal Premises WiringInstalling the D9112 Assembly Lock the Reset Pin Now Locking the Reset PinCharge the Battery as You Finish Finishing the InstallationInstall and Wire Detection Devices Install Modules and RelaysConnect the On-Board Points and Command Centers Install the Point Chart LabelPower Up Programming the PanelTesting the System Primary Power Terminals Power SupplyPrimary AC Power Circuit Installing the TransformerSecondary DC Power Secondary Power TerminalsInstalling the Battery Battery SupervisionBattery Discharge/Recharge Schedule No AC Power Battery Charging CircuitFloat Charge Discharge CycleCharging Status and Low Battery LEDs Low Battery LED RedCharging Status LED Yellow Power Outputs Available PowerCircuit Protection Accessory Connector J2 Continuous Power Outputs TerminalsContinuous Current Draw Expansion Port J4Relay Installation Programmable Power Outputs TerminalsProgramming Optional Relays RequiredVerification/Reset Relay Available PowerTerminals 6 TerminalRegistration Telephone ConnectionsNotification LocationPhone LED Red Phone Cord ConnectionOperation Monitor LED Green Dialing FormatGround Start Relay InstallationGround Start Jumper D128 Dual Phone Line SwitcherDescription OperationWatchdog Feature Installing the D128Primary Phone Lines, Primary Phone Numbers D128 Status LEDs AC Power LEDPrimary Fail LED Secondary Fail LEDOn-Board Points Description Terminals 11 toPoint Sensor Loops Point Response Time Point ParametersOff-Board Points Point Zonex Buss Terminals 23 toD8125 Popex Module D8127 Popit Modules Wiring the D8125 to the D9112 Installing the D8125 Popex ModuleListings MountingD8125 D9112Zonex +UP to 63 Point PointsData Expansion Loop Wire Specifications Wiring POPITs to the Data Expansion LoopPopit Sensor Loops Wiring Data Expansion Loops to Popex ModulesD9112 Program Record Sheet Point AssignmentsPopit Labels Vertical Grid for Popex #1Installing the OctoPOPIT D8128A OctoPOPIT ModuleListing D8128A OctoPOPITs Wiring OctoPOPITs to the D9112Line Termination Sensor Loop Switches Point Assignment SwitchesOctoPOPIT Sensor Loops Sensor Loop D9112 Point #Testing Off-board Points Off-board Relays Configuring the D8129 OctoRelayD8129 OctoRelay Relay OutputsD8129 Switch Settings Wiring Connections InstallationRelay Output D811 Arm Status Relay ModuleD811 Module Wiring D1255 Address Settings D1255 Command Centers Terminals 29 toArming Devices DescriptionD1255 Connections D9112 Command Center Terminal Function Wire ColorD9112 Power at Command CentersMaintained Contact Keyswitch OperationMomentary Contact Silencing the BellProgrammer Connector J7 Programmer and Accessory ConnectionsAccessory Connector J2 Programmer Access ReportsExpansion Port J4 D9112 Terminal Name Description Quick Reference Terminal DescriptionInstallation Guide for UL and Fire Applications Optional Compatible Equipment IntroductionBurglary Applications Fire ApplicationsFire Applications Enclosures D129 Class a System ChartSystem Wiring Diagram, Issue a Current Rating Chart for Standby Battery Calculations Total a = Total B = Total C 1 =Currents shown in milliamperes 1 ampere=1000 milliamperes Central Station or Local Fire Alarm Standby Battery RequirementsRemote Station or Auxiliary Fire Alarm Household Burglary and Commercial BurglaryCentral Station or Local Systems Current Chart FirstHousehold Fire Ampere-Hour Calculation Formula Remote Station or Auxiliary SystemsSelf Diagnostics Troubleshooting GuideCall for Service Trouble at Command Center Panel Broken Hardware, Software FailedServc Batt LOW Battery Voltage Low Servc AC Fail AC Power FailedServc Batt Msing Battery Missing, Shorted, or Reversed Servc Keypad Supervised Command Center MissingPhone Line Trouble Symptom Diagnosis RemedyCommunications Failure Zonex BUS Problems Programming the PanelSee Problems with Data Expansion Loop Problems with PointsSymptom Diagnosis Remedy Symptom Diagnosis Remedy Metering the Loops Problems with the D8125 Popex Data Expansion LoopsChecking Shielded Cable EMI on Long Wire RunsNCI #1, #40 Problems with Command CentersBattery and Power Reports Watchdog Reset ReportsRunaway Reports to the Receiver Overloaded Power Supply Service Walk Test Service Walk ? Command 5 7 Toggles Default Idle Text Command 5 9 Shows Firmware RevisionPress Command 5 Specifications SDI Bus Compatible AccessoriesTelephone Connections Environmental