D811 Arm Status Relay Module
The 811 Arm Status Relay Module allows you to add a single
Relay numbers for D811 not programmable: If you connect the D811 to ZONEX 1, terminal 28 on the D9112, you must use relay number 53 for the relay output. If you connect the D811 to ZONEX 2, terminal 26 on the D9112, you must use relay number 117 for the relay output.
D811 modules connect as shown in Figure 18. Review the Power Outputs section of this manual to be sure you provide enough power for the powered devices you wish to connect to your system. See Relay Parameters in the D9112 Program Entry Guide (74-
D811 restricted for fire systems: The D811 relay output is not supervised and can not be used in fire or combined fire/burglary installations for primary indication devices.
Relay Output
Each D811 relay output provides a Form C dry contact rated for 1.0A at 12 VDC.
Warning: Relay outputs may activate while programming the panel. You may wish to disconnect equipment connected to relay outputs while performing these functions.
Installation
Do not use the instructions packaged with the D811: The literature packaged with the D811 module is not for use with the D9112 panel. Use the instructions below.
You can install the D811 in the enclosure with the D9112 (see Figure 2) or in an adjacent enclosure not more than 5 feet from the D9112. Use 16 to 22 AWG wire.
Follow the procedure below to install D811 modules in the enclosure with the D9112.
1.Align the D811 module with any of the four mounting locations in the enclosure. See Figure 2.
2.Use the screws provided with the module to secure it in the enclosure.
Use the D137 Mounting Bracket to install D811 modules in enclosures with no module mounting locations available.
| D9112 | Operation & Installation Manual |
|
|
| ||
Page 51 | © |