Service Walk Test

The Service Walk Test differs from the standard Walk Test in that POPITs whose switches are set for a point number not programmed in the panel appear in the test.

Service Walk Test only available at command centers with panel wide scope: See Command Center in the D9112 Control/Communicator Program Entry Guide (74-06145- 000) for a description of command center scope.

Warning, fire and other 24-hour points do not transmit reports during Service Walk Test!

The steps below outline a simple Service Walk Test procedure. The flow chart on the next page shows all the Service Walk Test options.

1.Choose a command center with panel wide scope to conduct the test. Be certain the display shows the idle disarmed text.

2.Press 9 9 ENT to display the first item in the Service Menu.

3.Press NEXT to step through the menu items until SERVICE WALK? appears in the display.

4.Press ENT.

5.ENTER PASSCODE appears in the display if you programmed Service Walk Test access to be restricted by authority level.

Enter a passcode assigned an authority level with access to the Service Walk Test function. Press ENT.

6.The display shows ### PTS TO TEST . Test the first detection device.

7.As you fault the detection devices, the command center emits a brief tone, briefly displays the point text for the point tested, and returns to the points to test display.

Extra Points display default text: If you incorrectly set the switches on a POPIT to a point number that is not in your program for the panel, the default text for that point number (POINT ###) displays when you fault the point. The D9112 Program Record Sheet shows the default text for all points.

Faulting the point a second time produces the tone and displays thepoint text, but does not reduce the PTS TO TEST count.

8.During the Service Walk Test you may want to see the points that remain untested. When point text is displayed, press ESC. The display shows ## PTS TO TEST. Press the ESC key. VIEW UNTESTED ? is displayed. Press ENT. ## PTS UNTESTED is displayed. Press NEXT to see a list of the points that have not yet been tested. Move through this list by pressing the NEXT key. To resume the Fire Test, press ESC. ## PTS UNTESTED is displayed. Press ESC. ## PTS TO TEST is displayed. Resume testing points. To end the Service Walk Test, press ESC twice.

9.After testing the last point, 0 PTS TO TEST displays. Press ESC. The display momentarily shows ALL PTS TESTED before returning to idle text.

Automatic time-out returns the system to idle text: If there is no point or command center activity for 20 minutes, the walk test ends automatically. The command center returns to idle text.

 

D9112

Operation & Installation Manual

 

 

 

74-06144-000-C 2/96

Page 83

© 1993-1996 Radionics

Image 83
Contents D I O N I C S Part FCC Notices74-06144-000-C 2/96 Table of Contents Standby Battery Calculation for Programmer and Accessory ConnectionsInstallation Guide for UL and Fire Applications Current Rating Chart forFigures and Tables D8128A OctoPOPIT Switch SettingsPoints IntroductionCommunicator D1255 Alpha III Command CenterKeyswitch Areas and AccountsProgramming Event MemoryEvent Log EMI/Lightning Transient ProtectionOther Features Literature Pack D9112 Control/Communicator AssemblyD9112 Assembly Ordered SeparatelyFactory Mutual FM Listings and ApprovalsFire BurglaryEnclosure Options InstallationBeginning the Installation Before You BeginInstalling the D9112 Assembly Connecting Earth Ground TerminalPremises Wiring Lock the Reset Pin Now Locking the Reset PinInstall Modules and Relays Finishing the InstallationCharge the Battery as You Finish Install and Wire Detection DevicesProgramming the Panel Install the Point Chart LabelConnect the On-Board Points and Command Centers Power UpTesting the System Installing the Transformer Power SupplyPrimary Power Terminals Primary AC Power CircuitBattery Supervision Secondary Power TerminalsSecondary DC Power Installing the BatteryDischarge Cycle Battery Charging CircuitBattery Discharge/Recharge Schedule No AC Power Float ChargeCharging Status LED Yellow Charging Status and Low Battery LEDsLow Battery LED Red Circuit Protection Power OutputsAvailable Power Expansion Port J4 Continuous Power Outputs TerminalsAccessory Connector J2 Continuous Current DrawOptional Relays Required Programmable Power Outputs TerminalsRelay Installation ProgrammingTerminal Available PowerVerification/Reset Relay Terminals 6Location Telephone ConnectionsRegistration NotificationDialing Format Phone Cord ConnectionPhone LED Red Operation Monitor LED GreenGround Start Relay InstallationOperation D128 Dual Phone Line SwitcherGround Start Jumper DescriptionPrimary Phone Lines, Primary Phone Numbers Watchdog FeatureInstalling the D128 Secondary Fail LED AC Power LEDD128 Status LEDs Primary Fail LEDPoint Sensor Loops On-Board PointsDescription Terminals 11 to Point Response Time Point ParametersD8125 Popex Module D8127 Popit Modules Off-Board PointsPoint Zonex Buss Terminals 23 to Mounting Installing the D8125 Popex ModuleWiring the D8125 to the D9112 Listings+UP to 63 Point Points D9112D8125 ZonexData Expansion Loop Wire Specifications Wiring POPITs to the Data Expansion LoopPopit Sensor Loops Wiring Data Expansion Loops to Popex ModulesD9112 Program Record Sheet Point AssignmentsPopit Labels Vertical Grid for Popex #1Listing Installing the OctoPOPITD8128A OctoPOPIT Module D8128A OctoPOPITs Wiring OctoPOPITs to the D9112Line Termination OctoPOPIT Sensor Loops Sensor Loop SwitchesPoint Assignment Switches Sensor Loop D9112 Point #Testing Off-board Points Relay Outputs Configuring the D8129 OctoRelayOff-board Relays D8129 OctoRelayD8129 Switch Settings Wiring Connections InstallationRelay Output D811 Arm Status Relay ModuleD811 Module Wiring Description D1255 Command Centers Terminals 29 toD1255 Address Settings Arming DevicesD1255 Connections D9112 Command Center Terminal Function Wire ColorD9112 Power at Command CentersSilencing the Bell Keyswitch OperationMaintained Contact Momentary ContactProgrammer Connector J7 Programmer and Accessory ConnectionsExpansion Port J4 Accessory Connector J2Programmer Access Reports D9112 Terminal Name Description Quick Reference Terminal DescriptionInstallation Guide for UL and Fire Applications Fire Applications IntroductionOptional Compatible Equipment Burglary ApplicationsFire Applications Enclosures D129 Class a System ChartSystem Wiring Diagram, Issue a Currents shown in milliamperes 1 ampere=1000 milliamperes Current Rating Chart for Standby Battery CalculationsTotal a = Total B = Total C 1 = Household Burglary and Commercial Burglary Standby Battery RequirementsCentral Station or Local Fire Alarm Remote Station or Auxiliary Fire AlarmCentral Station or Local Systems Current Chart FirstHousehold Fire Ampere-Hour Calculation Formula Remote Station or Auxiliary SystemsPanel Broken Hardware, Software Failed Troubleshooting GuideSelf Diagnostics Call for Service Trouble at Command CenterServc Keypad Supervised Command Center Missing Servc AC Fail AC Power FailedServc Batt LOW Battery Voltage Low Servc Batt Msing Battery Missing, Shorted, or ReversedPhone Line Trouble Symptom Diagnosis RemedyCommunications Failure Zonex BUS Problems Programming the PanelSee Problems with Data Expansion Loop Problems with PointsSymptom Diagnosis Remedy Symptom Diagnosis Remedy Metering the Loops Problems with the D8125 Popex Data Expansion LoopsChecking Shielded Cable EMI on Long Wire RunsNCI #1, #40 Problems with Command CentersRunaway Reports to the Receiver Battery and Power ReportsWatchdog Reset Reports Overloaded Power Supply Service Walk Test Service Walk ? Press Command 5 Command 5 7 Toggles Default Idle TextCommand 5 9 Shows Firmware Revision Specifications Environmental Compatible AccessoriesSDI Bus Telephone Connections