Bosch Appliances D9112 installation manual Off-Board Points, Point Zonex Buss Terminals 23 to

Page 35

Off-Board Points

Point (ZONEX) Buss

Terminals

23 to 28

You can use POPIT (Point of Protection Input Transponder) modules to provide up to 126 off-board points, bringing the total number of points the D9112 can monitor to 134. Each off-board point requires a POPIT module.

POPITs connect to supervised two-wire data expansion loops run from POPIT to POPIT throughout the premises. Data expansion loops connect to a D8125 POPEX (Point of Protection Expander) module. POPEX modules connect to the point buss on the panel, terminals 23 and 24 for power, and terminals 25 and 26, or 27 and 28 for data.

If a POPIT is disconnected from the expansion loop, a trouble message appears immediately. See the D9112 Program Entry Guide (74-06145-000) for programming options.

If you connect a POPIT that is programmed for a point number that does not appear in the program for the D9112 to the expansion loop, it appears as an extra point at the command centers when the point is faulted, and during the service walk test.

Placing a short on the data expansion loop generates a PT BUS TROUBLE report. The panel sees all points on the shorted expansion loop as shorted, and responds according to point programming.

POPIT modules monitor their sensor loops for three conditions, loop normal, loop open, and loop shorted. They report these three conditions to the D9112. A ground on a POPIT sensor loop reports as an open.

The D9112 uses point programming to interpret the sensor loop information reported by the POPITs and make the appropriate system response.

D8125 POPEX Module

D8127 POPIT Modules

D8127 POPITs use the D8125 POPEX module to report to the D9112. Each D8125 supports up to 63 POPIT points. Connect two D8125 modules to the D9112 to bring the combined total number of POPIT and on-board points to 134. Points 9 to 71 connect to the first POPEX module. The D9112 reserves Points 72 and 136 for internal use. Points 73 to 135 connect to the second POPEX module. The D9112 only annunciates activity for each POPIT, not each detection device connected to the sensor loop.

There are two versions of the D8127 modules. Both module enclosures are made of UL listed fire resistant material. D8127T modules contain tamper switches. D8127U modules come with an untampered cover. Unless the module is mounted in a tampered enclosure, UL requires D8127T modules for certificated accounts.

POPEXs manufactured prior to the expiration date (located on the packaging box) of X9434 may cause POPITs to report as missing after the AC has failed and after the panel goes into a low battery condition but before the panel goes into load shed. POPEXs manufactured after X9434 will not cause missing POPITs prior to load shed on an AC FAIL.

 

D9112

Operation & Installation Manual

 

 

© 1993 Radionics

74-06144-000-C 2/96

Page 35

Image 35
Contents D I O N I C S Part FCC Notices74-06144-000-C 2/96 Table of Contents Standby Battery Calculation for Programmer and Accessory ConnectionsInstallation Guide for UL and Fire Applications Current Rating Chart forFigures and Tables D8128A OctoPOPIT Switch SettingsPoints IntroductionCommunicator D1255 Alpha III Command CenterKeyswitch Areas and AccountsProgramming Event MemoryEvent Log EMI/Lightning Transient ProtectionOther Features Literature Pack D9112 Control/Communicator AssemblyD9112 Assembly Ordered SeparatelyFactory Mutual FM Listings and ApprovalsFire BurglaryEnclosure Options InstallationBeginning the Installation Before You BeginInstalling the D9112 Assembly Connecting Earth Ground TerminalPremises Wiring Lock the Reset Pin Now Locking the Reset PinInstall Modules and Relays Finishing the InstallationCharge the Battery as You Finish Install and Wire Detection DevicesProgramming the Panel Install the Point Chart LabelConnect the On-Board Points and Command Centers Power UpTesting the System Installing the Transformer Power SupplyPrimary Power Terminals Primary AC Power CircuitBattery Supervision Secondary Power TerminalsSecondary DC Power Installing the BatteryDischarge Cycle Battery Charging CircuitBattery Discharge/Recharge Schedule No AC Power Float ChargeCharging Status LED Yellow Charging Status and Low Battery LEDsLow Battery LED Red Circuit Protection Power OutputsAvailable Power Expansion Port J4 Continuous Power Outputs TerminalsAccessory Connector J2 Continuous Current DrawOptional Relays Required Programmable Power Outputs TerminalsRelay Installation ProgrammingTerminal Available PowerVerification/Reset Relay Terminals 6Location Telephone ConnectionsRegistration NotificationDialing Format Phone Cord ConnectionPhone LED Red Operation Monitor LED GreenGround Start Relay InstallationOperation D128 Dual Phone Line SwitcherGround Start Jumper DescriptionPrimary Phone Lines, Primary Phone Numbers Watchdog FeatureInstalling the D128 Secondary Fail LED AC Power LEDD128 Status LEDs Primary Fail LEDPoint Sensor Loops On-Board PointsDescription Terminals 11 to Point Response Time Point ParametersD8125 Popex Module D8127 Popit Modules Off-Board PointsPoint Zonex Buss Terminals 23 to Mounting Installing the D8125 Popex ModuleWiring the D8125 to the D9112 Listings+UP to 63 Point Points D9112D8125 ZonexData Expansion Loop Wire Specifications Wiring POPITs to the Data Expansion LoopPopit Sensor Loops Wiring Data Expansion Loops to Popex ModulesD9112 Program Record Sheet Point AssignmentsPopit Labels Vertical Grid for Popex #1Listing Installing the OctoPOPITD8128A OctoPOPIT Module D8128A OctoPOPITs Wiring OctoPOPITs to the D9112Line Termination OctoPOPIT Sensor Loops Sensor Loop SwitchesPoint Assignment Switches Sensor Loop D9112 Point #Testing Off-board Points Relay Outputs Configuring the D8129 OctoRelayOff-board Relays D8129 OctoRelayD8129 Switch Settings Wiring Connections InstallationRelay Output D811 Arm Status Relay ModuleD811 Module Wiring Description D1255 Command Centers Terminals 29 toD1255 Address Settings Arming DevicesD1255 Connections D9112 Command Center Terminal Function Wire ColorD9112 Power at Command CentersSilencing the Bell Keyswitch OperationMaintained Contact Momentary ContactProgrammer Connector J7 Programmer and Accessory ConnectionsExpansion Port J4 Accessory Connector J2Programmer Access Reports D9112 Terminal Name Description Quick Reference Terminal DescriptionInstallation Guide for UL and Fire Applications Fire Applications IntroductionOptional Compatible Equipment Burglary ApplicationsFire Applications Enclosures D129 Class a System ChartSystem Wiring Diagram, Issue a Currents shown in milliamperes 1 ampere=1000 milliamperes Current Rating Chart for Standby Battery CalculationsTotal a = Total B = Total C 1 = Household Burglary and Commercial Burglary Standby Battery RequirementsCentral Station or Local Fire Alarm Remote Station or Auxiliary Fire AlarmCentral Station or Local Systems Current Chart FirstHousehold Fire Ampere-Hour Calculation Formula Remote Station or Auxiliary SystemsPanel Broken Hardware, Software Failed Troubleshooting GuideSelf Diagnostics Call for Service Trouble at Command CenterServc Keypad Supervised Command Center Missing Servc AC Fail AC Power FailedServc Batt LOW Battery Voltage Low Servc Batt Msing Battery Missing, Shorted, or ReversedPhone Line Trouble Symptom Diagnosis RemedyCommunications Failure Zonex BUS Problems Programming the PanelSee Problems with Data Expansion Loop Problems with PointsSymptom Diagnosis Remedy Symptom Diagnosis Remedy Metering the Loops Problems with the D8125 Popex Data Expansion LoopsChecking Shielded Cable EMI on Long Wire RunsNCI #1, #40 Problems with Command CentersRunaway Reports to the Receiver Battery and Power ReportsWatchdog Reset Reports Overloaded Power Supply Service Walk Test Service Walk ? Press Command 5 Command 5 7 Toggles Default Idle TextCommand 5 9 Shows Firmware Revision Specifications Environmental Compatible AccessoriesSDI Bus Telephone Connections