Bosch Appliances D9112 D8128A OctoPOPIT Module, Listing, Installing the OctoPOPIT

Page 42

D8128A OctoPOPIT Module

Description

The D8128A OctoPOPIT Module combines the functions of the D8125 POPEX module and the D8127 POPIT modules to provide eight off-board points in a single module. You can use OctoPOPIT and D8125 POPEX modules on the same D9112.

Warning, Do not use D8128 modules, they are not compatible with the D9112, only use D8128A modules: Using D8128 modules may cause intermittent missing and restoral reports. Be sure to only use D8128A modules.

Review the Power Outputs section of this manual to be sure you provide enough power for the OctoPOPITs and other powered devices you wish to connect to your system.

Do not use the instructions packaged with the OctoPOPIT: The literature packaged with the OctoPOPIT is not for use with the D9112 panel. Use the instructions below.

Listing

The D8128A OctoPOPIT Module is UL listed for Local or Police Connected Burglary Alarm, Central Station Burglary Alarm, and Household Burglary Alarm applications. The D8128A is also suitable for fire supervisory applications, such as indicating circuit supervision (using the D192A Bell Circuit Supervision Module), sprinkler supervision, and valve tamper protection. Do not connect fire alarm initiating devices to the D8128A

You must use the D125B Powered Loop Interface Module or D129 Dual Class A initiation Circuit Module for fire initiation applications. Connect the initiating devices, smoke detectors for example, to the D125B powered loops or D129 Class A loops.

Connect the zone outputs on the D125B or D129 to the OctoPOPIT sensor loop inputs. The D125B or D129 and the OctoPOPIT must be mounted in the enclosure with the D9112 or in an enclose connected to the D9112’s enclosure by conduit not more than 20 feet in length.

Installing the OctoPOPIT

You can install the D8128A OctoPOPIT Module in the enclosure with the D9112, or in a separate enclosure up to 200 feet from the panel. If you mount the OctoPOPIT in a separate enclosure, use shielded cable to avoid electro-magnetic interference. See EMI on Long Wire Runs in the Troubleshooting section of this manual.

Tampered enclosures for UL certificated systems: Mount the D8128A in a tampered enclosure for UL certificated systems.

Mounting

Follow the procedure below to install OctoPOPITs in the enclosure with the D9112.

1.It is easier to set the switches on the D8128A before you mount it in the enclosure. See Line Termination, Sensor Loop Switches, and Point Assignment Switches.

2.Align the OctoPOPIT module with any of the four mounting locations in the enclosure. See Figure 2.

3.Use the screws provided with the module to secure it in the enclosure.

Use the D137 Mounting Bracket to install OctoPOPITs in enclosures with no module mounting locations available.

 

D9112 Operation & Installation Manual

 

74-06144-000-C 2/96

Page 42

© 1993-1996 Radionics

Image 42
Contents D I O N I C S FCC Notices Part74-06144-000-C 2/96 Table of Contents Current Rating Chart for Programmer and Accessory ConnectionsInstallation Guide for UL and Fire Applications Standby Battery Calculation forD8128A OctoPOPIT Switch Settings Figures and TablesIntroduction PointsAreas and Accounts D1255 Alpha III Command CenterKeyswitch CommunicatorEMI/Lightning Transient Protection Event MemoryEvent Log ProgrammingOther Features Ordered Separately D9112 Control/Communicator AssemblyD9112 Assembly Literature PackBurglary Listings and ApprovalsFire Factory Mutual FMBefore You Begin InstallationBeginning the Installation Enclosure OptionsConnecting Earth Ground Terminal Premises WiringInstalling the D9112 Assembly Locking the Reset Pin Lock the Reset Pin NowInstall and Wire Detection Devices Finishing the InstallationCharge the Battery as You Finish Install Modules and RelaysPower Up Install the Point Chart LabelConnect the On-Board Points and Command Centers Programming the PanelTesting the System Primary AC Power Circuit Power SupplyPrimary Power Terminals Installing the TransformerInstalling the Battery Secondary Power TerminalsSecondary DC Power Battery SupervisionFloat Charge Battery Charging CircuitBattery Discharge/Recharge Schedule No AC Power Discharge CycleCharging Status and Low Battery LEDs Low Battery LED RedCharging Status LED Yellow Power Outputs Available PowerCircuit Protection Continuous Current Draw Continuous Power Outputs TerminalsAccessory Connector J2 Expansion Port J4Programming Programmable Power Outputs TerminalsRelay Installation Optional Relays RequiredTerminals 6 Available PowerVerification/Reset Relay TerminalNotification Telephone ConnectionsRegistration LocationOperation Monitor LED Green Phone Cord ConnectionPhone LED Red Dialing FormatRelay Installation Ground StartDescription D128 Dual Phone Line SwitcherGround Start Jumper OperationWatchdog Feature Installing the D128Primary Phone Lines, Primary Phone Numbers Primary Fail LED AC Power LEDD128 Status LEDs Secondary Fail LEDOn-Board Points Description Terminals 11 toPoint Sensor Loops Point Parameters Point Response TimeOff-Board Points Point Zonex Buss Terminals 23 toD8125 Popex Module D8127 Popit Modules Listings Installing the D8125 Popex ModuleWiring the D8125 to the D9112 MountingZonex D9112D8125 +UP to 63 Point PointsWiring POPITs to the Data Expansion Loop Data Expansion Loop Wire SpecificationsWiring Data Expansion Loops to Popex Modules Popit Sensor LoopsPoint Assignments D9112 Program Record SheetVertical Grid for Popex #1 Popit LabelsInstalling the OctoPOPIT D8128A OctoPOPIT ModuleListing Wiring OctoPOPITs to the D9112 D8128A OctoPOPITsLine Termination Sensor Loop Switches Point Assignment SwitchesOctoPOPIT Sensor Loops D9112 Point # Sensor LoopTesting Off-board Points D8129 OctoRelay Configuring the D8129 OctoRelayOff-board Relays Relay OutputsD8129 Switch Settings Installation Wiring ConnectionsD811 Arm Status Relay Module Relay OutputD811 Module Wiring Arming Devices D1255 Command Centers Terminals 29 toD1255 Address Settings DescriptionD9112 Command Center Terminal Function Wire Color D1255 ConnectionsPower at Command Centers D9112Momentary Contact Keyswitch OperationMaintained Contact Silencing the BellProgrammer and Accessory Connections Programmer Connector J7Accessory Connector J2 Programmer Access ReportsExpansion Port J4 D9112 Quick Reference Terminal Description Terminal Name DescriptionInstallation Guide for UL and Fire Applications Burglary Applications IntroductionOptional Compatible Equipment Fire ApplicationsFire Applications Enclosures System Chart D129 Class aSystem Wiring Diagram, Issue a Current Rating Chart for Standby Battery Calculations Total a = Total B = Total C 1 =Currents shown in milliamperes 1 ampere=1000 milliamperes Remote Station or Auxiliary Fire Alarm Standby Battery RequirementsCentral Station or Local Fire Alarm Household Burglary and Commercial BurglaryCurrent Chart First Central Station or Local SystemsRemote Station or Auxiliary Systems Household Fire Ampere-Hour Calculation FormulaCall for Service Trouble at Command Center Troubleshooting GuideSelf Diagnostics Panel Broken Hardware, Software FailedServc Batt Msing Battery Missing, Shorted, or Reversed Servc AC Fail AC Power FailedServc Batt LOW Battery Voltage Low Servc Keypad Supervised Command Center MissingSymptom Diagnosis Remedy Phone Line TroubleCommunications Failure Problems Programming the Panel Zonex BUSProblems with Points See Problems with Data Expansion LoopSymptom Diagnosis Remedy Symptom Diagnosis Remedy Problems with the D8125 Popex Data Expansion Loops Metering the LoopsEMI on Long Wire Runs Checking Shielded CableProblems with Command Centers NCI #1, #40Battery and Power Reports Watchdog Reset ReportsRunaway Reports to the Receiver Overloaded Power Supply Service Walk Test Service Walk ? Command 5 7 Toggles Default Idle Text Command 5 9 Shows Firmware RevisionPress Command 5 Specifications Telephone Connections Compatible AccessoriesSDI Bus Environmental