Make the Telephone Connections
See Telephone Connections. If you are connecting the D9112 to a ground start phone system, you need to install D136 relay, see Install Modules and Relays on the previous page.
Connect the On-Board Points and Command Centers
Connect the
Power Up
Reconnect the battery and then plug in the transformer. Remember the buzzer sounds for 10 seconds when you first power up the panel.
Leave the reset pin locked down for now.
Yellow Charging Status LED doesn’t go out: If the yellow charging status LED doesn’t go out within 5 minutes of powering up the panel, the battery may be deeply discharged, or you may have connected too many powered devices to the panel. Combined continuous current draw for terminals 3, 8, 24, and 32, the Accessory Connector (J2), and the Expansion Port (J4) cannot exceed 1.4A. See the Power Outputs section for help.
Programming the Panel
If you haven’t created a program for the panel, review the D9112 Program Entry Guide
Use the D5200 Programmer or the RAM II remote programmer to load your custom program into the panel.
Move the reset pin to the normal position. See Figure 3. The panel transmits reboot and battery reports to the receiver.
Install the Point Chart Label
Radionics recommends you fill out the Point Chart Label
Point chart label required for fire systems with verification points: You must install the point chart label for fire or combined fire/burglary systems using verification points.
Use the program record sheet to gather the information you need to fill out the point chart. Install the label on the enclosure door as shown in figure 2. To avoid smearing your entries on the chart, use the label's peel off backing to press the label in place.