Bosch Appliances D9112 D128 Status LEDs, AC Power LED, Primary Fail LED, Secondary Fail LED

Page 32

D128 Status LEDs

Four LEDs mounted on the front edge of the D128 module show the status of AC power for the D9112, the status of the two phone lines, and communication failure. See Figure 10.

AC Power LED

The green AC power status LED lights when there is AC power at terminals 1 and 2 on the D9112 panel.

Primary Fail LED

The yellow Primary Fail LED lights when the D9112’s phone line monitor determines the primary phone line is faulted. See Phone Line Monitor in this section for a description of phone line monitor operation.

Secondary Fail LED

The yellow Secondary Fail LED lights when the D9112’s phone line monitor determines the secondary phone line is faulted. See Phone Line Monitor in this section for a description of phone line monitor operation.

Communication Failure LED

The yellow Communication Failure LED lights when the D9112 is in communication failure. See Communication Failure in this section.

CONNECT TO D9112 ACCESSORY

CONNECTOR (J2) WITH RIBBON CABLE

 

GREEN ÊÑ TO D9112

PHONE JACK TO PRIMARY

TERMINAL 1

PHONE LINE - RJ31X

 

 

BLK ÊÑ TO D9112

 

TERMINAL 9

PHONE JACK TO SECONDARY

AC POWER

PHONE LINE - RJ31X

LED

 

(GREEN)

PHONE JACK TO D9112 TELCO

PRIMARY

CONNECTOR (J3)

FAIL LED

 

(YELLOW)

 

SECONDARY

 

FAIL LED

 

(YELLOW)

 

COMMUNICATIONS

 

FAILURE LED

 

(YELLOW)

Figure 10: D128 Dual Phone Line Switcher

D9112 Operation & Installation Manual

74-06144-000-C 2/96

Page 32

© 1993-1996 Radionics

Image 32
Contents D I O N I C S FCC Notices Part74-06144-000-C 2/96 Table of Contents Programmer and Accessory Connections Installation Guide for UL and Fire ApplicationsCurrent Rating Chart for Standby Battery Calculation forD8128A OctoPOPIT Switch Settings Figures and TablesIntroduction PointsD1255 Alpha III Command Center KeyswitchAreas and Accounts CommunicatorEvent Memory Event LogEMI/Lightning Transient Protection ProgrammingOther Features D9112 Control/Communicator Assembly D9112 AssemblyOrdered Separately Literature PackListings and Approvals FireBurglary Factory Mutual FMInstallation Beginning the InstallationBefore You Begin Enclosure OptionsInstalling the D9112 Assembly Connecting Earth Ground TerminalPremises Wiring Locking the Reset Pin Lock the Reset Pin NowFinishing the Installation Charge the Battery as You FinishInstall and Wire Detection Devices Install Modules and RelaysInstall the Point Chart Label Connect the On-Board Points and Command CentersPower Up Programming the PanelTesting the System Power Supply Primary Power TerminalsPrimary AC Power Circuit Installing the TransformerSecondary Power Terminals Secondary DC PowerInstalling the Battery Battery SupervisionBattery Charging Circuit Battery Discharge/Recharge Schedule No AC PowerFloat Charge Discharge CycleCharging Status LED Yellow Charging Status and Low Battery LEDsLow Battery LED Red Circuit Protection Power OutputsAvailable Power Continuous Power Outputs Terminals Accessory Connector J2Continuous Current Draw Expansion Port J4Programmable Power Outputs Terminals Relay InstallationProgramming Optional Relays RequiredAvailable Power Verification/Reset RelayTerminals 6 TerminalTelephone Connections RegistrationNotification LocationPhone Cord Connection Phone LED RedOperation Monitor LED Green Dialing FormatRelay Installation Ground StartD128 Dual Phone Line Switcher Ground Start JumperDescription OperationPrimary Phone Lines, Primary Phone Numbers Watchdog FeatureInstalling the D128 AC Power LED D128 Status LEDsPrimary Fail LED Secondary Fail LEDPoint Sensor Loops On-Board PointsDescription Terminals 11 to Point Parameters Point Response TimeD8125 Popex Module D8127 Popit Modules Off-Board PointsPoint Zonex Buss Terminals 23 to Installing the D8125 Popex Module Wiring the D8125 to the D9112Listings MountingD9112 D8125Zonex +UP to 63 Point PointsWiring POPITs to the Data Expansion Loop Data Expansion Loop Wire SpecificationsWiring Data Expansion Loops to Popex Modules Popit Sensor LoopsPoint Assignments D9112 Program Record SheetVertical Grid for Popex #1 Popit LabelsListing Installing the OctoPOPITD8128A OctoPOPIT Module Wiring OctoPOPITs to the D9112 D8128A OctoPOPITsLine Termination OctoPOPIT Sensor Loops Sensor Loop SwitchesPoint Assignment Switches D9112 Point # Sensor LoopTesting Off-board Points Configuring the D8129 OctoRelay Off-board RelaysD8129 OctoRelay Relay OutputsD8129 Switch Settings Installation Wiring ConnectionsD811 Arm Status Relay Module Relay OutputD811 Module Wiring D1255 Command Centers Terminals 29 to D1255 Address SettingsArming Devices DescriptionD9112 Command Center Terminal Function Wire Color D1255 ConnectionsPower at Command Centers D9112Keyswitch Operation Maintained ContactMomentary Contact Silencing the BellProgrammer and Accessory Connections Programmer Connector J7Expansion Port J4 Accessory Connector J2Programmer Access Reports D9112 Quick Reference Terminal Description Terminal Name DescriptionInstallation Guide for UL and Fire Applications Introduction Optional Compatible EquipmentBurglary Applications Fire ApplicationsFire Applications Enclosures System Chart D129 Class aSystem Wiring Diagram, Issue a Currents shown in milliamperes 1 ampere=1000 milliamperes Current Rating Chart for Standby Battery CalculationsTotal a = Total B = Total C 1 = Standby Battery Requirements Central Station or Local Fire AlarmRemote Station or Auxiliary Fire Alarm Household Burglary and Commercial BurglaryCurrent Chart First Central Station or Local SystemsRemote Station or Auxiliary Systems Household Fire Ampere-Hour Calculation FormulaTroubleshooting Guide Self DiagnosticsCall for Service Trouble at Command Center Panel Broken Hardware, Software FailedServc AC Fail AC Power Failed Servc Batt LOW Battery Voltage LowServc Batt Msing Battery Missing, Shorted, or Reversed Servc Keypad Supervised Command Center MissingSymptom Diagnosis Remedy Phone Line TroubleCommunications Failure Problems Programming the Panel Zonex BUSProblems with Points See Problems with Data Expansion LoopSymptom Diagnosis Remedy Symptom Diagnosis Remedy Problems with the D8125 Popex Data Expansion Loops Metering the LoopsEMI on Long Wire Runs Checking Shielded CableProblems with Command Centers NCI #1, #40Runaway Reports to the Receiver Battery and Power ReportsWatchdog Reset Reports Overloaded Power Supply Service Walk Test Service Walk ? Press Command 5 Command 5 7 Toggles Default Idle TextCommand 5 9 Shows Firmware Revision Specifications Compatible Accessories SDI BusTelephone Connections Environmental