Bosch Appliances Installing the D8125 Popex Module, Listings, Wiring the D8125 to the D9112

Page 36

Listings

The D8125 POPEX and D8127 POPIT modules are UL listed for Local or Police Connected Burglar Alarm, Central Station Burglar Alarm, Household Burglar Alarm, Central Station Fire (NFPA 71), Local Fire (NFPA 72, Chapter 6), Remote Station Fire (NFPA 72, Chapter 8), Household Fire (NFPA 74) and Electrically Actuated Transmitter Applications. See the Installation Guide for UL and Fire Applications in this manual to determine the required equipment and enclosures for your application.

Installing the D8125 POPEX Module

Do not use the instructions packaged with the D8125: The manual packaged with the D8125 POPEX module does not include instructions for connecting the module to the D9112 panel. Follow the instructions below.

Save the D9112 POPIT Label Sheets: The D8125 is packaged with two sets of POPIT label sheets. One is marked For use with D9112. Save this set. You will use it later to label the POPITs.

Mounting

Follow the procedure below to install the D8125 in the enclosure with the D9112.

1.Align the D8125 POPEX module with any of the four mounting locations in the enclosure. See Figure 2.

2.Use the screws provided with the module to secure it in the enclosure.

Wiring the D8125 to the D9112

Follow the procedure below to wire one or two D8125 modules to the D9112.

See Figure 12.

Power down first: Power down the D9112 by disconnecting the positive (red) battery lead at the battery and unplugging the transformer.

Warning, reversed polarity damages the D8125: Make sure you correctly wire the D8125 AUX and GND terminals to the D9112.

For points 9 to 71:

1.Connect the GND terminal of the D8125 to terminal 23 on the D9112.

2.Connect the OUT terminal of the D8125 POPEX module to ZONEX IN 1, terminal 27 on the D9112.

3.Connect the IN terminal of the D8125 POPEX module to ZONEX OUT 1, terminal 28 on the D9112.

4.Connect the AUX terminal of the D8125 to terminal 24 on the D9112.

For point numbers from 73 to 135:

1.Connect the GND terminal of the D8125 to terminal 23 on the D9112.

2.Connect the OUT terminal of the D8125 POPEX module to ZONEX IN 2, terminal 25 on the D9112.

3.Connect the IN terminal of the D8125 POPEX module to ZONEX OUT 2, terminal 26 on the D9112.

4.Connect the AUX terminal of the D8125 to terminal 24 on the D9112.

 

D9112 Operation & Installation Manual

 

74-06144-000-C 2/96

Page 36

© 1993-1996 Radionics

Image 36
Contents D I O N I C S FCC Notices Part74-06144-000-C 2/96 Table of Contents Programmer and Accessory Connections Installation Guide for UL and Fire ApplicationsCurrent Rating Chart for Standby Battery Calculation forD8128A OctoPOPIT Switch Settings Figures and TablesIntroduction PointsD1255 Alpha III Command Center KeyswitchAreas and Accounts CommunicatorEvent Memory Event LogEMI/Lightning Transient Protection ProgrammingOther Features D9112 Control/Communicator Assembly D9112 AssemblyOrdered Separately Literature PackListings and Approvals FireBurglary Factory Mutual FMInstallation Beginning the InstallationBefore You Begin Enclosure OptionsConnecting Earth Ground Terminal Premises WiringInstalling the D9112 Assembly Locking the Reset Pin Lock the Reset Pin NowFinishing the Installation Charge the Battery as You FinishInstall and Wire Detection Devices Install Modules and RelaysInstall the Point Chart Label Connect the On-Board Points and Command CentersPower Up Programming the PanelTesting the System Power Supply Primary Power TerminalsPrimary AC Power Circuit Installing the TransformerSecondary Power Terminals Secondary DC PowerInstalling the Battery Battery SupervisionBattery Charging Circuit Battery Discharge/Recharge Schedule No AC PowerFloat Charge Discharge CycleCharging Status and Low Battery LEDs Low Battery LED RedCharging Status LED Yellow Power Outputs Available PowerCircuit Protection Continuous Power Outputs Terminals Accessory Connector J2Continuous Current Draw Expansion Port J4Programmable Power Outputs Terminals Relay InstallationProgramming Optional Relays RequiredAvailable Power Verification/Reset RelayTerminals 6 TerminalTelephone Connections RegistrationNotification LocationPhone Cord Connection Phone LED RedOperation Monitor LED Green Dialing FormatRelay Installation Ground StartD128 Dual Phone Line Switcher Ground Start JumperDescription OperationWatchdog Feature Installing the D128Primary Phone Lines, Primary Phone Numbers AC Power LED D128 Status LEDsPrimary Fail LED Secondary Fail LEDOn-Board Points Description Terminals 11 toPoint Sensor Loops Point Parameters Point Response TimeOff-Board Points Point Zonex Buss Terminals 23 toD8125 Popex Module D8127 Popit Modules Installing the D8125 Popex Module Wiring the D8125 to the D9112Listings MountingD9112 D8125Zonex +UP to 63 Point PointsWiring POPITs to the Data Expansion Loop Data Expansion Loop Wire SpecificationsWiring Data Expansion Loops to Popex Modules Popit Sensor LoopsPoint Assignments D9112 Program Record SheetVertical Grid for Popex #1 Popit LabelsInstalling the OctoPOPIT D8128A OctoPOPIT ModuleListing Wiring OctoPOPITs to the D9112 D8128A OctoPOPITsLine Termination Sensor Loop Switches Point Assignment SwitchesOctoPOPIT Sensor Loops D9112 Point # Sensor LoopTesting Off-board Points Configuring the D8129 OctoRelay Off-board RelaysD8129 OctoRelay Relay OutputsD8129 Switch Settings Installation Wiring ConnectionsD811 Arm Status Relay Module Relay OutputD811 Module Wiring D1255 Command Centers Terminals 29 to D1255 Address SettingsArming Devices DescriptionD9112 Command Center Terminal Function Wire Color D1255 ConnectionsPower at Command Centers D9112Keyswitch Operation Maintained ContactMomentary Contact Silencing the BellProgrammer and Accessory Connections Programmer Connector J7Accessory Connector J2 Programmer Access ReportsExpansion Port J4 D9112 Quick Reference Terminal Description Terminal Name DescriptionInstallation Guide for UL and Fire Applications Introduction Optional Compatible EquipmentBurglary Applications Fire ApplicationsFire Applications Enclosures System Chart D129 Class aSystem Wiring Diagram, Issue a Current Rating Chart for Standby Battery Calculations Total a = Total B = Total C 1 =Currents shown in milliamperes 1 ampere=1000 milliamperes Standby Battery Requirements Central Station or Local Fire AlarmRemote Station or Auxiliary Fire Alarm Household Burglary and Commercial BurglaryCurrent Chart First Central Station or Local SystemsRemote Station or Auxiliary Systems Household Fire Ampere-Hour Calculation FormulaTroubleshooting Guide Self DiagnosticsCall for Service Trouble at Command Center Panel Broken Hardware, Software FailedServc AC Fail AC Power Failed Servc Batt LOW Battery Voltage LowServc Batt Msing Battery Missing, Shorted, or Reversed Servc Keypad Supervised Command Center MissingSymptom Diagnosis Remedy Phone Line TroubleCommunications Failure Problems Programming the Panel Zonex BUSProblems with Points See Problems with Data Expansion LoopSymptom Diagnosis Remedy Symptom Diagnosis Remedy Problems with the D8125 Popex Data Expansion Loops Metering the LoopsEMI on Long Wire Runs Checking Shielded CableProblems with Command Centers NCI #1, #40Battery and Power Reports Watchdog Reset ReportsRunaway Reports to the Receiver Overloaded Power Supply Service Walk Test Service Walk ? Command 5 7 Toggles Default Idle Text Command 5 9 Shows Firmware RevisionPress Command 5 Specifications Compatible Accessories SDI BusTelephone Connections Environmental