Standby Battery Requirements

Household Burglary and Commercial Burglary

Four hours of standby battery capacity required.

Central Station or Local Fire Alarm

24 hours of standby plus 5 minutes of alarm operation required. See Central Station or Local Systems Ampere-Hour Calculation Formula in the Standby Battery Calculation for NFPA 72 Fire Alarm Applications section.

Remote Station or Auxiliary Fire Alarm

60 hours of standby plus 5 minutes of alarm operation required. See Remote Station or Auxiliary System Ampere-Hour Calculation Formula in the Standby Battery Calculation for NFPA 72 Fire Alarm Applications section.

Household Fire Warning Equipment

24 hours of standby plus 4 minutes of alarm operation required. SeeHousehold Fire Ampere- Hour Calculation Formula in the Standby Battery Calculation for NFPA 72 Fire Alarm Applications section.

 

D9112

Operation & Installation Manual

 

 

 

74-06144-000-C 2/96

Page 67

© 1993-1996 Radionics

Image 67
Contents D I O N I C S Part FCC Notices74-06144-000-C 2/96 Table of Contents Standby Battery Calculation for Programmer and Accessory ConnectionsInstallation Guide for UL and Fire Applications Current Rating Chart forFigures and Tables D8128A OctoPOPIT Switch SettingsPoints IntroductionCommunicator D1255 Alpha III Command CenterKeyswitch Areas and AccountsProgramming Event MemoryEvent Log EMI/Lightning Transient ProtectionOther Features Literature Pack D9112 Control/Communicator AssemblyD9112 Assembly Ordered SeparatelyFactory Mutual FM Listings and ApprovalsFire BurglaryEnclosure Options InstallationBeginning the Installation Before You BeginPremises Wiring Connecting Earth Ground TerminalInstalling the D9112 Assembly Lock the Reset Pin Now Locking the Reset PinInstall Modules and Relays Finishing the InstallationCharge the Battery as You Finish Install and Wire Detection DevicesProgramming the Panel Install the Point Chart LabelConnect the On-Board Points and Command Centers Power UpTesting the System Installing the Transformer Power SupplyPrimary Power Terminals Primary AC Power CircuitBattery Supervision Secondary Power TerminalsSecondary DC Power Installing the BatteryDischarge Cycle Battery Charging CircuitBattery Discharge/Recharge Schedule No AC Power Float ChargeLow Battery LED Red Charging Status and Low Battery LEDsCharging Status LED Yellow Available Power Power OutputsCircuit Protection Expansion Port J4 Continuous Power Outputs TerminalsAccessory Connector J2 Continuous Current DrawOptional Relays Required Programmable Power Outputs TerminalsRelay Installation ProgrammingTerminal Available PowerVerification/Reset Relay Terminals 6Location Telephone ConnectionsRegistration NotificationDialing Format Phone Cord ConnectionPhone LED Red Operation Monitor LED GreenGround Start Relay InstallationOperation D128 Dual Phone Line SwitcherGround Start Jumper DescriptionInstalling the D128 Watchdog FeaturePrimary Phone Lines, Primary Phone Numbers Secondary Fail LED AC Power LEDD128 Status LEDs Primary Fail LEDDescription Terminals 11 to On-Board PointsPoint Sensor Loops Point Response Time Point ParametersPoint Zonex Buss Terminals 23 to Off-Board PointsD8125 Popex Module D8127 Popit Modules Mounting Installing the D8125 Popex ModuleWiring the D8125 to the D9112 Listings+UP to 63 Point Points D9112D8125 ZonexData Expansion Loop Wire Specifications Wiring POPITs to the Data Expansion LoopPopit Sensor Loops Wiring Data Expansion Loops to Popex ModulesD9112 Program Record Sheet Point AssignmentsPopit Labels Vertical Grid for Popex #1D8128A OctoPOPIT Module Installing the OctoPOPITListing D8128A OctoPOPITs Wiring OctoPOPITs to the D9112Line Termination Point Assignment Switches Sensor Loop SwitchesOctoPOPIT Sensor Loops Sensor Loop D9112 Point #Testing Off-board Points Relay Outputs Configuring the D8129 OctoRelayOff-board Relays D8129 OctoRelayD8129 Switch Settings Wiring Connections InstallationRelay Output D811 Arm Status Relay ModuleD811 Module Wiring Description D1255 Command Centers Terminals 29 toD1255 Address Settings Arming DevicesD1255 Connections D9112 Command Center Terminal Function Wire ColorD9112 Power at Command CentersSilencing the Bell Keyswitch OperationMaintained Contact Momentary ContactProgrammer Connector J7 Programmer and Accessory ConnectionsProgrammer Access Reports Accessory Connector J2Expansion Port J4 D9112 Terminal Name Description Quick Reference Terminal DescriptionInstallation Guide for UL and Fire Applications Fire Applications IntroductionOptional Compatible Equipment Burglary ApplicationsFire Applications Enclosures D129 Class a System ChartSystem Wiring Diagram, Issue a Total a = Total B = Total C 1 = Current Rating Chart for Standby Battery CalculationsCurrents shown in milliamperes 1 ampere=1000 milliamperes Household Burglary and Commercial Burglary Standby Battery RequirementsCentral Station or Local Fire Alarm Remote Station or Auxiliary Fire AlarmCentral Station or Local Systems Current Chart FirstHousehold Fire Ampere-Hour Calculation Formula Remote Station or Auxiliary SystemsPanel Broken Hardware, Software Failed Troubleshooting GuideSelf Diagnostics Call for Service Trouble at Command CenterServc Keypad Supervised Command Center Missing Servc AC Fail AC Power FailedServc Batt LOW Battery Voltage Low Servc Batt Msing Battery Missing, Shorted, or ReversedPhone Line Trouble Symptom Diagnosis RemedyCommunications Failure Zonex BUS Problems Programming the PanelSee Problems with Data Expansion Loop Problems with PointsSymptom Diagnosis Remedy Symptom Diagnosis Remedy Metering the Loops Problems with the D8125 Popex Data Expansion LoopsChecking Shielded Cable EMI on Long Wire RunsNCI #1, #40 Problems with Command CentersWatchdog Reset Reports Battery and Power ReportsRunaway Reports to the Receiver Overloaded Power Supply Service Walk Test Service Walk ? Command 5 9 Shows Firmware Revision Command 5 7 Toggles Default Idle TextPress Command 5 Specifications Environmental Compatible AccessoriesSDI Bus Telephone Connections