Toro SA41 owner manual Installation of SA-KP-01 Optional Keypad, Ext. Keypad no Set Parameters

Page 27

INSTALLATION OF SA-KP-01 OPTIONAL KEYPAD

Installation of the optional keypad requires the interface board (SA-SB-01) plus a suitable length of 6 conductor (3 pair) shielded 7 / 0.2 data cable.

1.Carefully unpack the Keypad Kit. The front cover has been left loose to allow access to the 4 mounting holes as shown.

2.Prior to attaching the keypad to the wall, bulkhead, etc., complete the electrical connections to the user screw connector as shown in Diagram 1 on page 26. Please take careful note of the orientation. Plug the screw connector into the back of the keypad and secure the keypad chassis in its intended location

3. Clip the grey plastic front cover over the chassis, applying firm pressure at the points shown at right.

4.At the SA41 end of the shielded cable, connect the 6 wires to the SA-SB-01 Interface Board, using screw terminals 4 to 9, as shown in Diagram 1. Connect the cable shield to the 0V terminal (No. 4, Black) to reduce radiated electrical noise from the cable.

5.Ensure that the SA41 is switched off at the front panel circuit breaker.

6.Plug the SA-SB-01 Interface Board into the rear DB25 connector of the SA41.

7.Switch on the SA41 at the circuit breaker. The keypad will not display any information at this stage.

8.Via the SA41 front panel, access the “Settings” menu as described in Page 8 of the manual. Scroll slowly through the screens until the following display is seen:

Ext. Keypad: NO

[Set Parameters]

Select YES using the ”UP” key. Scroll through the remainder of the “Settings” screens until the “Readings” screen is reached.

9. The external keypad will now display the same information as appears on the SA41 front panel.

27

Image 27
Contents Selectronic Australia Warranty Card InstallationIntroduction Supply Connection of AC and DC WiringRED = Battery Positive + Black = Battery Negative Status Status Standby Inverter OFF Inverter on Status ResetOperation Energy ManagementWhere the Optional 200 AMP Current Shunt is Installed Minimum Charge Settings Controller OutputsOn with OFF Set Control On with on On with Time Set Control Duration LockoutSET DAY More SettingsBuzzer on / OFF Buzzer LockoutLockout Current Shunt Settings External Shunt AC Volts SettingAlarm Inputs Alarm InputLOW Charge Alarm Battery CapacityCharge in Battery Minimum Charge in BatteryOverload Shutdown and Alarms Heatsink TOO HOT Fault FindingAlarm 1 Active Alarm 2 ActiveInverter Shuts Down with LOW Volts System Maintenance SA41 MaintenanceBattery Maintenance Demand Start Section SA41 Electrical SpecificationsHandy Hint Radio Frequency InterferenceDemand Start Current Appendix I DiagnosticsTransformer Temperature Heatsink TemperatureAppendix II Flow Diagram for Displays and Settings Minimum charge Displays Switching Between READINGS, Minimum CHARGE, and DiagnosticsDiagnostic Displays Minimum Charge DisplayCO+LAH INV CO, LO A/H orFrom previous Appendix III SA Inverter Options GeneralSA-SB-01 Interface KIT SA-SB-01 Interface Connections Alarm Inputs ExamplesExt. Keypad no Set Parameters Installation of SA-KP-01 Optional KeypadZero DC Amps OFF Set Parameters Installation of SA-S200 Optional Current ShuntAmps 0.0A OUT Battery Ext. Shunt no Set ParametersProduct Warranty Conditions Mounting Template for SA-KP-01 Keypad